SAPEmT-et 0.6/1 kV Aluminium Conductor PE Insulated Copper Screened Power Cable – BDS 2581-86
The SAPEmT-et aluminium conductor power cable is designed for electrical power transfer and distribution in public and metropolitan transportation networks. Manufactured according to BDS 2581-86, it features Class 2 aluminium conductors, PE insulation, copper tape screening, and a protective PVC Type P-1 outer sheath. Suitable for fixed installations in underground systems, cable ducts, tunnels, and conduits, it provides reliable electrical performance with a continuous operating temperature of +90°C and a maximum short-circuit temperature of +250°C.
Application
SAPEmT-et cables are designed for electrical power systems with a nominal voltage of 3 kV and are suitable for electrical public and metropolitan transportation networks. They are used for power transfer, distribution, and electrical power supply with a nominal voltage of Uo/U 0.6/1 kV and a frequency of 50 Hz.
These cables are suitable for fixed installation in lines with unlimited differences in level, underground installations, cable ducts, tunnels, conduits, over shelves, and grilles under shelters.
Cable Construction
The SAPEmT-et cable is manufactured according to BDS 2581-86 standards.
-
Conductor: Aluminium solid round multi-core conductor, according to BDS 2581-86 (IEC 60228), Class 2.
-
Insulation: PE (Polyethylene) compound.
-
Metal screen: Copper tapes.
-
Outer sheath: PVC compound, Type P-1.
-
Outer sheath colour: Grey.
-
Compliance: RoHS compliant.
Technical Data
| Parameter | Specification |
|---|---|
| Applicable standard | BDS 2581-86 |
| Conductor standard | BDS 904 (IEC 60228), Class 2 |
| Conductor material | Aluminium |
| Conductor resistance at 20°C | According to BDS 904 (IEC 60228), Class 2 |
| Operating temperature | 90°C continuous operation |
| Maximum overload temperature | 130°C, max. 100 hours/year |
| Maximum short-circuit temperature | 250°C / 5 seconds maximum |
| Nominal voltage | 0.6/1 kV; 3 kV |
| Highest system voltage | 0.6/1 kV; 1.2 kV and 3 kV |
| Test voltage AC, 5 minutes | 3.5 kV |
| Minimum bending radius | 15 × D (cable diameter) |
| Temperature of laying | Not less than +5°C |
| Operating temperature range | -30°C to +50°C |
| Maximum pulling force during laying | 30 N/mm² for aluminium conductors and 50 N/mm² for copper conductors |
Conductor Construction Identification
| Parameter | Description |
|---|---|
| Conductor material | Aluminium |
| Conductor type | Solid round multi-core |
| Conductor class | Class 2 |
| Metal screen | Copper tapes |
| Insulation | PE |
| Outer sheath | PVC Type P-1 |
Colour Coding
-
Outer sheath colour: Grey.
-
Individual core insulation colour coding is not specified in the supplied product datasheet.
3. Construction Data Tables
Construction Data – SAPEmT-et 0.6/1 kV, U(=) 3 kV
| Nominal cross-section (N × mm²) | Insulation thickness (mm) | Minimum copper screen section (mm²) | Sheath thickness (mm) | Cable diameter approx. (mm) | Aluminium weight (kg/km) | Cable weight approx. (kg/km) |
|---|---|---|---|---|---|---|
| 1 × 300 | 2.4 | 2.5 | 2.0 | 30.8 | 830 | 1358 |
| 1 × 400 | 2.6 | 2.5 | 2.1 | 34.3 | 1060 | 1691 |
| 1 × 500 | 3.0 | 2.5 | 2.2 | 38.3 | 1410 | 2158 |
Factory Overview
Packaging & Shipping
Frequently Asked Questions (FAQ)
Q:- What is the primary application of SAPEmT-et cable?
A:- It is designed for electrical power transfer and distribution in electrical public and metropolitan transportation networks, including underground installations, cable ducts, tunnels, and conduits.
Q:- What standard does SAPEmT-et cable follow?
A:- The cable is manufactured according to BDS 2581-86.
Q:- What type of conductor is used in SAPEmT-et cable?
A:- It uses solid round aluminium conductors, Class 2, according to IEC 60228.
Q:- What insulation material is used in SAPEmT-et cable?
A:- It uses polyethylene (PE) compound insulation.
Q:- What is the purpose of the copper screen?
A:- Copper tape screening provides a metallic screening layer within the cable construction.
Q:- What material is used for the outer sheath?
A:- The outer sheath is made of PVC compound, Type P-1, with a grey colour.
Q:- What is the operating temperature of SAPEmT-et cable?
A:- The continuous operating temperature is +90°C, with a maximum overload temperature of +130°C for up to 100 hours per year.
Q:- What is the maximum short-circuit temperature?
A:- The maximum short-circuit temperature is +250°C for a maximum of 5 seconds.
Q:- What is the minimum bending radius?
A:- The specified minimum bending radius is 15 times the cable diameter (15 × D).
Q:- Is SAPEmT-et cable suitable for underground installation?
A:- Yes. It is suitable for underground installations, cable ducts, tunnels, conduits, and other fixed-installation environments.