U 1000 R2V 0.6/1 kV XLPE Copper Power Cable – NFC 32-321

The U 1000 R2V 0.6/1 kV cable delivers dependable power distribution for industrial installations and urban networks. Constructed with copper conductors, XLPE insulation, and a black PVC outer sheath, it offers excellent thermal and mechanical protection. Because it meets NFC 32-321 standards and is RoHS compliant, it provides a safe and reliable solution for cable ducts, tunnels, and outdoor installations under shelters.

Application
U 1000 R2V cables provide reliable power distribution and supply for consumers in industrial installations and urban networks. They operate efficiently with a nominal voltage of 0.6/1 kV and a frequency of 50 Hz. Because of their robust design, installers use them for fixed indoor assembly in cable ducts, tunnels, and conduits. Furthermore, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters. Consequently, they deliver consistent performance provided the conditions for the determined type of cable are met.

Cable construction
This cable strictly adheres to NFC 32-321 standards. It features copper wires that comply with NFC 32-321 (IEC 60228). The conductors range from class 1 for 1.5 to 18mm², class 2 for 1.5 to 500mm², and class 2 from 50 to 240mm². The insulation uses an XLPE compound for superior thermal resistance. Additionally, a tape or extrusion forms the inner sheath. Finally, a black PVC compound sheath protects the entire assembly. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to NFC 32-321. The operating temperature reaches a maximum of 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of 0.6/1 kV, while the highest system voltage is 1.2 kV. The temperature range for laying, installing, explosion, and storage is -5 °C to +60 °C, while the operating range is -25 °C to +70 °C. Installers must respect a minimum bending radius of 10 times the cable diameter.

Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are black or yellow/green. Double core cables feature blue and brown, or yellow-green and black. Multi-core configurations include specific color sequences for easy identification.

Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data U 1000 R2V 0.6/1 kV

Number of conductors and nominal cross section Shape Outer diameter approx. Cu weight Cable weight approx.
N x mm² mm kg/km kg/km
1×1,0 rm 9,2 9 147
1×1,5 rm 9,2 14 147
1×2,5 rm 9,2 23 164
1×6 rm 13,5 325 396
1×10 rm 15,0 460 559
1×16 rm 17,0 648 738
1×25 rm 19,0 889 990
1×35 rm 21,0 1120 1235
1×50 rm 23,0 1578 1755
1×70 rm 25,5 2178 2423
1×95 rm 28,5 2285 2370
1×120 rm 28,5
2×1,5 rm 8,7 28 110
2×2,5 rm 10,5 46 173
2×4 rm 11,5 75 223
2×6 rm 12,5 110 295
2×10 rm 15,0 188 480
2×16 rm 20,3 303 585
3×1,5 rm 10,1 42 160
3×2,5 rm 11,0 69 202
3×4 rm 12,0 112 290
3×6 rm 13,2 165 352
3×10 rm 14,9 275 498
3×16 rm 17,0 450 720
3×25 rm 21,5 700 1085
3×35 rm 23,5 959 1435
3×50 rm 27,0 1350 1930
3×70 rm 30,5 1862 2800
3×95 rm 35,5 2565 3590
3×120 rm 38,5 3274 4380
3×150 rm 42,0 4193 5440
3×185 rm 48,0 5160 6604
3×240 rm 55,0 6760 8612
3×1,5 re 10,1 42 160
3×2,5 re 11,0 69 202
3×4 re 13,0 148 330
3×6 re 13,2 162 357
3×10 re 15,5 270 451
3×16 re 17,0 432 697
3×185+35 sm 48,5 5170 6830
3×50+50 sm 28,5 1755 2380
3×150+70 sm 42,8 4151 5710
3×120+70 sm 40,0 3410 4677
3×185+95 sm 50,3 5338 7006
3×240+95 sm 51,8 5805 7086
3×240+95 sm 54,8 7605 9241
4×1,5 re 10,3 58 186
4×2,5 re 12,7 95 296
4×6 re 13,2 146 312
4×10 re 14,3 218 416
4×16 re 18,5 385 588
4×25 re 18,2 592 888
4×35 re 22,6 925 1310
4×1,5 re 10,8 55 182
4×2,5 re 11,6 92 236
4×4 re 13,2 149 296
4×6 re 14,3 218 418
4×10 re 16,5 363 605
4×16 re 19,3 565 888
4×25 re 22,6 925 1310
4×35 re 25,3 1303 1730
4×50 re 29,7 1857 2290
4×70 re 34,7 2601 3240
4×95 re 39,0 3520 4310
4×120 re 45,0 4467 5440
4×150 re 49,0 5575 6650
4×185 re 55,5 6860 8400
4×240 re 62,1 8829 10687
5×1,5 re 11,6 55 182
5×2,5 re 12,7 95 297
5×4 re 13,2 146 312
5×6 re 14,3 218 418
5×10 re 18,2 383 653
5×16 re 22,2 592 888
5×25 re 25,3 1165 1585
5×1,5 re 12,5 96 230
7×1,5 re 11,7 96 230
10×1,5 re 13,7 110 260
12×1,5 re 14,3 140 317
14×1,5 re 15,4 161 315
16×1,5 re 16,5 195 403
19×1,5 re 18,7 260 511
20×1,5 re 23,7 260 700
24×1,5 re 24,5 306 748
37×1,5 re 24,8 506 890
7×2,5 re 13,7 160 312
10×2,5 re 17,9 222 350
12×2,5 re 17,9 227 427
14×2,5 re 18,7 320 545
19×2,5 re 20,9 435 701
24×2,5 re 25,3 540 1042
30×2,5 re 27,5 685 1045
37×2,5 re 25,3 845 1247

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer

Q:- What is the primary application of the U 1000 R2V cable?
A:- It is used for the distribution and supply of consumers with electrical power with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks.

Q:- Where can this cable be installed?
A:- It is suitable for fixed indoor assembly in cable ducts, tunnels and conduits, on shelves and grilles, directly underground in ditch and outdoor under shelters.

Q:- What standards does the cable construction follow?
A:- The construction adheres to NFC 32-321 standards, and the conductor complies with NFC 32-321 (IEC 60228).

Q:- What type of conductor and insulation does it use?
A:- It uses Cu wires for the conductor and XLPE compound for insulation.

Q:- What is the nominal voltage and highest system voltage?
A:- The nominal voltage Uo/U is 0.6/1 kV, and the highest system voltage is 1.2 kV.

Q:- What are the maximum continuous and short circuit temperatures?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the overload temperature capacity?
A:- It can withstand an overload temperature of 130°C for 100% per year maximum.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter (10 x D cable).

Q:- What are the temperature limits for laying and operation?
A:- The temperature range for laying and installing is -5°C to +60°C, while the operating temperature range is -25°C to +70°C.

Q:- What type of outer sheath protects the cable?
A:- A black PVC compound sheath protects the entire cable assembly.

Reviews

There are no reviews yet.

Be the first to review “U 1000 R2V 0.6/1 kV XLPE Copper Power Cable – NFC 32-321”

Your email address will not be published. Required fields are marked *