NA2XY-O & NA2XY-J 0.6/1 kV XLPE Aluminum Power Cable – VDE 0276-603

The NA2XY-O and NA2XY-J 0.6/1 kV cables deliver dependable power distribution for industrial installations and urban networks. Constructed with solid or stranded aluminum conductors, XLPE insulation, and a black PVC outer sheath, they offer excellent thermal and mechanical protection. Because they meet VDE 0276-603 standards and are CE/RoHS compliant, they provide a safe and reliable solution for cable ducts, conduits, and outdoor installations under shelters.

Application
NA2XY-O and NA2XY-J cables provide reliable power distribution and supply for consumers in industrial installations and urban networks. They operate with a nominal voltage of 0.6/1 kV and a frequency of 50 Hz. Because of their robust design, installers use them for fixed assembly in cable ducts and conduits. Furthermore, they function well directly underground in ditch and outdoor under shelters, provided that the specified conditions for the determined type of cable are met. Consequently, they deliver consistent performance in demanding infrastructure environments.

Cable construction
This cable strictly adheres to VDE 0276-603/5G standards. It features aluminum wires (solid or stranded class 1 or 2) that comply with VDE 0295 and HD 383 (IEC 60228). The insulation uses XLPE type DM3 (acc. to VDE 0276-603/5G) for superior thermal resistance. Additionally, a filling compound is included, and core identification follows the color code acc. to VDE 0276-603. Finally, a black PVC type DMV8 sheath (acc. to VDE 0276-603/see.1) protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to VDE 0295. The operating temperature reaches a maximum of 90 °C. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of 0.6/1 kV, while the highest system voltage is 1.2 kV. The test voltage AC is 4.0 kV at 50 Hz. Installers must respect a minimum bending radius of 15 times the cable diameter for single-core cables, or 12 times for multi-core cables. The laying temperature ranges from -5 °C to +70 °C (for PVC sheath). The explosion temperature ranges from -30 °C to +70 °C. Testing is performed according to DIN VDE 0276-603.

Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are black or yellow/green. Double core cables feature blue and brown, or yellow-green and black. Multi-core configurations include specific color sequences for easy identification.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data NA2XY-o/j 0.6/1 kV

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Outer diameter approx. Al weight Cable weight approx.
N x mm² mm mm mm kg/km kg/km
1×50 1,0 1,8 14,6 135 245
1×70 1,1 1,8 16,5 195 318
1×95 1,1 1,8 18,5 270 391
1×120 1,2 1,8 20,0 341 500
1×150 1,4 1,8 21,9 419 565
1×185 1,6 1,8 24,1 526 681
1×240 1,7 1,8 26,6 690 846
1×300 1,8 1,8 29,4 863 1043
1×400 2,0 1,9 32,9 1109 1304
1×500 2,2 2,0 36,7 1461 1673
4×16 0,7 1,8 20,5 176 546
4×25 0,9 1,8 24,1 288 702
4×35 0,9 1,8 26,3 394 922
4×50 1,0 1,9 28,2 539 1259
4×70 1,1 2,1 32,8 779 1811
4×95 1,1 2,3 35,6 1079 2101
4×120 1,2 2,3 39,8 1364 2233
4×150 1,4 2,4 44,0 1676 2696
4×185 1,6 2,6 48,4 2105 3206
4×240 1,7 2,7 62,8 2762 4129
4×35 0,9 1,8 25,5 388 977
4×50 1,0 1,9 30,0 522 1259
4×70 1,1 2,0 33,6 756 1461
4×95 1,1 2,1 38,8 1023 1812
4×120 1,2 2,2 40,2 1324 2233
4×150 1,4 2,4 43,8 1626 2696
4×185 1,6 2,5 48,8 2105 3285
4×240 1,7 2,7 54,0 2079 4233

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview



Packaging & Shipping


What is the primary application of the NA2XY-O and NA2XY-J cables?
A:- They are designed for the distribution and supply of consumers with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks, suitable for fixed assembly in cable ducts, conduits, and directly underground in ditch and outdoor under shelters.

Q:- What standards does the cable construction follow?
A:- The construction adheres to VDE 0276-603/5G standards, and the conductor complies with VDE 0295 and HD 383 (IEC 60228).

Q:- What type of conductor and insulation does it use?
A:- It uses Al solid or stranded wires class 1 or 2 for the conductor and XLPE type DM3 for insulation.

Q:- What type of outer sheath protects the cable?
A:- A black PVC type DMV8 sheath (acc. to VDE 0276-603/see.1) protects the entire cable assembly.

Q:- What is the nominal voltage and highest system voltage?
A:- The nominal voltage Uo/U is 0.6/1 kV, and the highest system voltage is 1.2 kV.

Q:- What are the maximum continuous and short circuit temperatures?
A:- The maximum conductor operating temperature is 90°C, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the overload temperature capacity?
A:- It can withstand an overload temperature of 130°C for 100% per year maximum.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter for single-core cables and 12 times for multi-core cables.

Q:- What is the test voltage and testing standard?
A:- The test voltage is 4.0 kV AC at 50 Hz, and testing is performed according to DIN VDE 0276-603.

Q:- What are the temperature limits for laying and explosion?
A:- The laying temperature is between -5°C to +70°C for PVC sheath, and the explosion temperature range is -30°C to +70°C.

 