SVBT 0.6/1 kV Copper Conductor Steel Tape Armoured PVC Power Cable – BDS 16291-85
The SVBT 0.6/1 kV copper conductor armoured power cable is designed for reliable electrical power transmission and distribution in industrial, commercial, and infrastructure applications. Manufactured according to BDS 16291-85, it features solid or stranded copper conductors, PVC insulation, a PVC inner sheath, steel tape armour, and a protective PVC outer sheath. Suitable for indoor and outdoor installations, including ducts, tunnels, canals, and shafts, this cable provides additional mechanical protection and dependable performance.
Application
SVBT cables are designed for transferring and distributing electrical power in switching installations and static installations. They are suitable for indoor installations, open-air installations, ducts, tunnels, canals, and shafts. Operating at a rated voltage of Uo/U 0.6/1 kV and a frequency of 50 Hz, these cables provide reliable power distribution for various electrical infrastructure and industrial applications.
Cable Construction
The SVBT cable is manufactured according to BDS 16291-85 standards.
-
Conductor: Solid or stranded copper wires, Class 1 or Class 2, according to BDS 904-84 (IEC 60228).
-
Insulation: PVC compound.
-
Inner sheath: PVC compound.
-
Armour: Steel tapes (STA).
-
Outer sheath: PVC compound.
-
Outer sheath colour: Grey or black.
-
Conductor shape: Circular solid, circular stranded, or sector stranded conductor.
-
Compliance: RoHS compliant.
Technical Data
| Parameter | Specification |
|---|---|
| Applicable standard | BDS 16291-85 |
| Conductor standard | BDS 904-84 (IEC 60228) |
| Conductor resistance at 20°C | According to BDS 904-84 |
| Maximum conductor temperature | +70°C |
| Maximum short-circuit temperature | +160°C, not more than 5 seconds |
| Rated voltage | 0.6/1 kV |
| Test voltage | AC 4 kV, 50 Hz / DC 12 kV |
| Minimum bending radius | 15 × D (cable diameter) |
| Temperature of laying | -5°C |
| Temperature range | -30°C to +50°C |
| Flame test | BDS IEC 332-1 |
| Frequency | 50 Hz |
| RoHS | Compliant, as indicated in the product specification |
Conductor Shape Identification
| Code | Conductor construction |
|---|---|
| re | Circular, solid conductor |
| rm | Circular, stranded conductor |
| sm | Sector, stranded conductor |
Color Coding
-
Single-core: Black, brown, blue, yellow/green, or other colours upon request.
-
Double-core: Blue and brown, or yellow/green and black.
-
3-core: Brown, black, grey; yellow/green and blue; or other combinations according to the construction table.
-
4-core: Brown, black, grey, blue, or yellow/green combinations.
-
5-core: Blue, brown, black, grey, and yellow/green combinations.
-
Multiple-core: Black cores with number markings, or black cores with number markings and a yellow/green core in the outer cover.
Other constructions are available according to the product specification.
3. Construction Data Tables
The following tables reproduce the supplied SVBT 0.6/1 kV product specification. Copper weight and approximate cable weight are expressed in kg/km.
Construction Data – SVBT 0.6/1 kV (Table 1)
| Nominal cross-section (N × mm²) | Shape | Outer diameter (mm) | Cu weight (kg/km) | Cable weight (kg/km) |
|---|---|---|---|---|
| 1 × 10 | rm | 12.5 | 93 | 302 |
| 1 × 16 | rm | 13.5 | 148 | 381 |
| 1 × 25 | rm | 15.3 | 229 | 515 |
| 1 × 35 | rm | 16.4 | 325 | 624 |
| 1 × 50 | rm | 17.6 | 458 | 771 |
| 1 × 70 | rm | 19.9 | 648 | 1025 |
| 1 × 95 | rm | 21.6 | 885 | 1305 |
| 1 × 120 | rm | 23.3 | 1120 | 1575 |
| 1 × 150 | rm | 25.1 | 1378 | 1890 |
| 1 × 185 | rm | 27.7 | 1703 | 2307 |
| 1 × 240 | rm | 30.6 | 2208 | 2935 |
| 2 × 2.5 | re | 12.7 | 46 | 281 |
| 2 × 4 | re | 14.6 | 75 | 346 |
| 2 × 6 | re | 15.7 | 110 | 415 |
| 2 × 10 | re | 17.3 | 182 | 538 |
| 2 × 16 | re | 19.3 | 303 | 711 |
| 2 × 25 | rm | 23.7 | 470 | 1038 |
| 2 × 35 | rm | 25.9 | 652 | 1315 |
| 2 × 50 | rm | 29.4 | 928 | 1706 |
| 3 × 1.5 | re | 12.4 | 42 | 252 |
| 3 × 2.5 | re | 13.2 | 69 | 297 |
| 3 × 4 | re | 15.4 | 110 | 410 |
| 3 × 6 | re | 16.4 | 165 | 490 |
| 3 × 10 | re | 18.3 | 275 | 660 |
| 3 × 16 | re | 20.3 | 450 | 880 |
| 3 × 25 | rm | 25.0 | 700 | 1326 |
| 3 × 35 | rm | 27.5 | 980 | 1685 |
| 3 × 50 | rm | 31.3 | 1390 | 2210 |
| 3 × 70 | sm | 32.2 | 1950 | 2754 |
| 3 × 95 | sm | 36.7 | 2650 | 3670 |
| 3 × 120 | sm | 39.5 | 3350 | 4452 |
| 3 × 150 | sm | 43.1 | 4185 | 5388 |
| 3 × 185 | sm | 47.6 | 5160 | 6835 |
| 3 × 240 | sm | 53.4 | 6720 | 8501 |
| 3 × 2.5 + 1.5 | re/re | 13.7 | 82 | 295 |
| 3 × 4 + 2.5 | re/re | 16.0 | 132 | 450 |
| 3 × 6 + 4 | re/re | 17.1 | 202 | 545 |
| 3 × 10 + 6 | re/re | 19.1 | 330 | 736 |
| 3 × 16 + 10 | re/re | 21.2 | 540 | 996 |
| 3 × 25 + 16 | rm/re | 26.3 | 850 | 1514 |
| 3 × 35 + 16 | rm/re | 29.1 | 1130 | 1890 |
| 3 × 50 + 25 | rm+rm | 33.0 | 1630 | 2499 |
| 3 × 70 + 35 | sm/rm | 35.4 | 2280 | 3212 |
| 3 × 95 + 50 | sm/rm | 40.2 | 3120 | 4180 |
| 3 × 120 + 70 | sm/rm | 43.7 | 4010 | 5260 |
| 3 × 150 + 70 | sm/rm | 48.1 | 4850 | 6220 |
| 3 × 185 + 95 | sm/rm | 53.3 | 6070 | 7786 |
Construction Data – SVBT 0.6/1 kV (Table 2)
| Nominal cross-section (N × mm²) | Shape | Outer diameter (mm) | Cu weight (kg/km) | Cable weight (kg/km) |
|---|---|---|---|---|
| 3 × 240 + 120 | sm/rm | 59.6 | 7840 | 9910 |
| 4 × 1.5 | re | 13.2 | 55 | 286 |
| 4 × 2.5 | re | 14.1 | 92 | 350 |
| 4 × 4 | re | 16.5 | 146 | 480 |
| 4 × 6 | re | 17.6 | 218 | 580 |
| 4 × 10 | re | 19.8 | 363 | 800 |
| 4 × 16 | re | 22.0 | 582 | 1080 |
| 4 × 25 | rm | 27.4 | 925 | 1642 |
| 4 × 35 | rm | 30.4 | 1303 | 2175 |
| 4 × 50 | rm | 34.4 | 1857 | 2762 |
| 4 × 70 | sm | 36.6 | 2601 | 3478 |
| 4 × 95 | sm | 42.0 | 3540 | 4791 |
| 4 × 120 | sm | 45.4 | 4460 | 5800 |
| 4 × 150 | sm | 50.0 | 5575 | 7975 |
| 4 × 185 | sm | 55.2 | 6880 | 8117 |
| 4 × 240 | sm | 62.2 | 8928 | 10080 |
| 5 × 1.5 | re | 14.0 | 69 | 331 |
| 5 × 2.5 | re | 15.2 | 114 | 413 |
| 5 × 4 | re | 17.7 | 182 | 567 |
| 5 × 6 | re | 19.2 | 275 | 708 |
| 5 × 10 | re | 21.4 | 455 | 970 |
| 5 × 16 | re | 24.0 | 745 | 1324 |
| 5 × 25 | rm | 30.7 | 1165 | 2048 |
| 5 × 35 | rm | 33.4 | 1640 | 2758 |
| 5 × 50 | rm | 38.7 | 2330 | 3840 |
| 5 × 70 | rm | 43.7 | 3260 | 5128 |
| 7 × 1.5 | re | 15.2 | 96 | 421 |
| 8 × 1.5 | re | 16.2 | 110 | 465 |
| 10 × 1.5 | re | 18.3 | 140 | 571 |
| 12 × 1.5 | re | 18.8 | 165 | 610 |
| 14 × 1.5 | re | 19.5 | 195 | 675 |
| 16 × 1.5 | re | 20.5 | 220 | 740 |
| 19 × 1.5 | re | 21.3 | 260 | 814 |
| 24 × 1.5 | re | 24.5 | 330 | 1042 |
| 30 × 1.5 | re | 25.7 | 410 | 1180 |
| 37 × 1.5 | re | 27.7 | 506 | 1370 |
| 7 × 2.5 | re | 16.3 | 160 | 508 |
| 8 × 2.5 | re | 17.3 | 182 | 570 |
| 10 × 2.5 | re | 19.9 | 228 | 719 |
| 12 × 2.5 | re | 20.4 | 275 | 778 |
| 14 × 2.5 | re | 21.4 | 320 | 838 |
| 16 × 2.5 | re | 22.6 | 365 | 941 |
| 19 × 2.5 | re | 23.5 | 435 | 1050 |
| 24 × 2.5 | re | 27.0 | 546 | 1354 |
| 30 × 2.5 | re | 28.4 | 685 | 1551 |
| 37 × 2.5 | re | 30.8 | 845 | 1820 |
Note: The supplied specification permits simultaneous laying of the inner and outer sheath during extrusion.
Factory Overview
Packaging & Shipping
Frequently Asked Questions (FAQ)
Q:- What is the primary application of SVBT cable?
A:- SVBT cables are used for electrical power transmission and distribution in switching and static installations, including indoor, outdoor, open-air, duct, tunnel, canal, and shaft installations.
Q:- What standards does SVBT cable follow?
A:- The cable construction follows BDS 16291-85, while the copper conductor complies with BDS 904-84 (IEC 60228).
Q:- What type of conductor is used in SVBT cable?
A:- It uses solid or stranded copper conductors, available in circular solid, circular stranded, and sector stranded configurations.
Q:- What materials are used in SVBT cable construction?
A:- The cable consists of copper conductors, PVC insulation, a PVC inner sheath, steel tape armour, and a PVC outer sheath.
Q:- What is the purpose of steel tape armour?
A:- Steel tape armour provides additional mechanical protection against external damage, making the cable suitable for installations where mechanical protection is required.
Q:- What is the rated voltage of SVBT cable?
A:- The rated voltage is 0.6/1 kV.
Q:- What is the maximum operating temperature?
A:- The maximum conductor operating temperature is +70°C, while the maximum short-circuit temperature is +160°C for no more than 5 seconds.
Q:- What is the operating temperature range of SVBT cable?
A:- The specified temperature range is -30°C to +50°C, with a minimum laying temperature of -5°C.
Q:- What is the minimum bending radius?
A:- The minimum bending radius is 15 times the cable diameter (15 × D).
Q:- Is SVBT cable flame tested and RoHS compliant?
A:- Yes. According to the supplied product specification, it passes the flame test according to BDS IEC 332-1 and is RoHS compliant.




Reviews