2XSEY & A2XSEY 3.6/6 kV to 20/35 kV XLPE Three-Core Cable – IEC 60502-2

The 2XSEY and A2XSEY cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, and a red PVC outer sheath, they offer excellent thermal and electrical protection for 3.6/6 kV, 8.7/15 kV, and 20/35 kV applications. Because they meet IEC 60502-2 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
2XSEY and A2XSEY medium voltage three-core cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 3.6/6 kV, 8.7/15 kV, and 20/35 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for fixed assembly in lines with unlimited difference levels, indoor installations, cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm, or Cu tapes laid with overlap over each phase. The cable assembly features three insulated and screened cores twisted together with fillers and a tape separator. A PVC compound forms the inner sheath, and a PVC compound type ST2 sheath (according to IEC 60502) protects the entire assembly. The color is red. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BDS904 (IEC60228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 3.6/6, 8.7/15, and 20/35 kV, while the highest system voltage Uo/U is not more than 3.6/6, 12/20, and 24/36 kV. Test voltage is AC (+) – 5 min for 3.6/6 kV (10 kV), 8.7/15 kV (30 kV), and 20/35 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XSEY, A2XSEY 3.6/6; 8.7/15; 20/35 kV

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XSEY Mass of Cu approx. 2XSEY Mass of cable approx. A2XSEY Mass of Al approx. A2XSEY Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
3.6/6 kV
3×35 m/16 2,5 2,5 16 46,2 1010 2609 282 1833
3×50 m/16 2,5 2,5 16 48,8 1363 3070 404 2163
3×70 m/16 2,5 2,5 16 53,0 1968 3904 584 2590
3×95 m/16 2,5 2,7 16 57,1 2732 4914 809 3087
3×120 m/16 2,5 2,7 16 60,1 3425 5566 1013 3757
3×150 m/25 2,5 2,9 25 64,2 4245 6943 1257 4105
3×185 m/25 2,6 3,0 25 66,5 5311 8268 1579 4722
3×240 m/25 2,8 3,2 25 74,3 6981 10302 2071 5729
3×300 m/25 2,8 3,4 25 79,6 8861 12487 2589 6729
8.7/15 kV
3×35 m/16 4,5 2,6 16 55,5 1010 3365 288 2689
3×50 m/16 4,5 2,7 16 59,3 1363 3883 494 2972
3×70 m/16 4,5 2,9 16 63,6 1968 4646 757 3416
3×95 m/16 4,5 3,0 16 67,2 2732 6444 809 4017
3×120 m/16 4,5 3,1 16 70,6 3440 6751 1023 4456
3×150 m/25 4,5 3,2 25 74,6 4245 7637 1259 5010
3×185 m/25 4,5 3,4 25 78,6 5311 9386 1579 5840
3×240 m/25 4,5 3,5 25 84,3 6981 11302 2071 6838
3×300 m/25 4,5 3,7 25 79,6 8861 13631 2589 7863
20/35 kV
3×50 m/16 8,8 3,4 16 75,6 1363 6977 404 5165
3×70 m/16 8,8 3,5 16 79,6 1968 7083 584 5769
3×95 m/16 8,8 3,7 16 83,7 2730 8304 809 6456
3×120 m/16 8,8 3,8 16 87,3 3421 10244 1023 6784
3×150 m/25 8,8 3,9 25 91,0 4245 10724 1257 7885

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XSEY and A2XSEY cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available in three nominal voltage levels: Uo/U 3.6/6 kV, 8.7/15 kV, and 20/35 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 standards, and the conductor complies with IEC 60228 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What type of metal screen is used in the cable?
A:- The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm, or Cu tapes laid with overlap over each phase.

Q:- What is the cable assembly design?
A:- The cable assembly features three insulated and screened cores twisted together with fillers and a tape separator.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.

Reviews

There are no reviews yet.

Be the first to review “2XSEY & A2XSEY 3.6/6 kV to 20/35 kV XLPE Three-Core Cable – IEC 60502-2”

Your email address will not be published. Required fields are marked *