SHEkT / SAHEkT 3.6/6 kV to 20/35 kV XLPE Insulated Copper & Aluminium Conductor Screened Power Cable – BDS 2581-86
SHEkT and SAHEkT medium voltage power cables are designed for reliable electrical power transmission and distribution in urban networks, transformer substations, and industrial installations. Manufactured according to BDS 2581-86, these cables feature stranded and compacted copper or aluminium conductors, XLPE insulation, semiconductive conductor and insulation screens, concentrically laid copper wire screening, and a protective red PVC Type P-5 outer sheath. Available in voltage ratings from 3.6/6 kV to 20/35 kV, they are suitable for underground installations, cable ducts, tunnels, conduits, and industrial power distribution systems.
Application
SHEkT and SAHEkT single-core cables with cross-linked polyethylene (XLPE) insulation are designed for the transfer and distribution of electrical power with nominal voltages ranging from 3.6/6 kV to 20/35 kV. They are mainly used for power supply in urban and district electrical networks and for electrical supply to transformer substations, small and medium industrial plants.
These cables are suitable for fixed installation in electrical power stations and industrial systems. They are also suitable for underground installations within ditches, cable ducts, conduits, and shafts, as well as over shelves and grids directly under shelters and in outdoor areas.
Cable Construction
The SHEkT / SAHEkT cables are manufactured according to BDS 2581-86.
-
Conductor: Copper or aluminium, stranded and compacted, according to BDS 904 (IEC 60228), Class 2.
-
Inner semiconductive layer: Semiconductive XLPE compound.
-
Insulation: XLPE (Cross-Linked Polyethylene) compound.
-
Outer semiconductive layer: Semiconductive XLPE compound.
-
Metal screen: Copper wires concentrically laid and one contact copper tape with a thickness of 0.1 mm.
-
Separating layer: Layer of plastic tape.
-
Outer sheath: PVC compound, Type P-5.
-
Outer sheath colour: Red.
-
Compliance: RoHS compliant.
Cable Type Identification
| Cable designation | Conductor material |
|---|---|
| SHEkT | Copper |
| SAHEkT | Aluminium |
Technical Data
| Parameter | Specification |
|---|---|
| Applicable standard | BDS 2581-86 |
| Conductor standard | BDS 904 (IEC 60228), Class 2 |
| Conductor material | Copper / Aluminium |
| Conductor resistance at 20°C | According to BDS 904 (IEC 60228), Class 2 |
| Continuous operating temperature | +90°C |
| Maximum overload temperature | +130°C, 100 hours per year maximum |
| Maximum short-circuit temperature | +250°C / 5 seconds maximum |
| Nominal voltage | 3.6/6, 6/10, 12/20, 18/30, 20/35 kV |
| Highest system voltage (U) | 7.2, 12, 24, 36, 42 kV |
| Test voltage AC, 5 minutes | 18, 30, 42, 63, 70 kV |
| Test voltage DC, 15 minutes | 29, 48, 66, 98, 110 kV |
| Minimum bending radius | 15 × D (cable diameter) |
| Minimum laying temperature | Not less than +5°C |
| Operating temperature range | -30°C to +50°C |
| Maximum pulling force during laying | According to conductor material and cross-section, as specified in the product datasheet |
Conductor Construction Identification
| Component | Description |
|---|---|
| Conductor | Stranded and compacted |
| Conductor class | Class 2 |
| Conductor materials | Copper or aluminium |
| Conductor screen | Semiconductive XLPE |
| Insulation | XLPE |
| Insulation screen | Semiconductive XLPE |
| Metallic screen | Copper wires and contact copper tape |
| Separating layer | Plastic tape |
| Outer sheath | PVC Type P-5 |
Colour Coding
-
Outer sheath colour: Red.
-
Individual core colour coding is not specified in the supplied product datasheet.
3. Construction Data Tables
The following data is transcribed from the supplied SHEkT / SAHEkT product catalogue.
Column identification:
-
Insulation thickness: mm
-
Sheath thickness: mm
-
Nominal cross-section of screen: mm²
-
Cable diameter: mm
-
Copper, aluminium and cable weights: kg/km
Construction Data – 3.6/6 kV
| Nominal construction | Insulation (mm) | Sheath (mm) | Screen (mm²) | Diameter (mm) | SHEkT Cu weight | SHEkT cable weight | SAHEkT Al weight | SAHEkT Cu weight | SAHEkT cable weight |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 2.5 | 2.5 | 16 | 21.5 | 490 | 805 | 95 | 176 | 580 |
| 1×50rm/16 | 2.5 | 2.5 | 16 | 22.5 | 600 | 940 | 130 | 176 | 640 |
| 1×70rm/16 | 2.5 | 2.5 | 16 | 24.5 | 790 | 1170 | 190 | 176 | 735 |
| 1×95rm/16 | 2.5 | 2.5 | 16 | 26.0 | 1030 | 1445 | 260 | 176 | 840 |
| 1×120rm/16 | 2.5 | 2.5 | 16 | 27.5 | 1255 | 1695 | 330 | 176 | 940 |
| 1×150rm/16* | 2.5 | 2.5 | 16* | 29.0 | 1505 | 1995 | 405 | 176 | 1060 |
| 1×185rm/16* | 2.5 | 2.5 | 16* | 30.5 | 1840 | 2365 | 510 | 176 | 1200 |
| 1×240rm/16* | 2.5 | 2.5 | 16* | 33.0 | 2365 | 2970 | 665 | 176 | 1430 |
Construction Data – 6/10 kV
| Nominal construction | Insulation (mm) | Sheath (mm) | Screen (mm²) | Diameter (mm) | SHEkT Cu weight | SHEkT cable weight | SAHEkT Al weight | SAHEkT Cu weight | SAHEkT cable weight |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 3.4 | 2.5 | 16 | 23 | 490 | 930 | 95 | 176 | 700 |
| 1×50rm/16 | 3.4 | 2.5 | 16 | 24 | 600 | 1075 | 130 | 176 | 770 |
| 1×70rm/16 | 3.4 | 2.5 | 16 | 26 | 790 | 1310 | 190 | 176 | 875 |
| 1×95rm/16 | 3.4 | 2.5 | 16 | 27 | 1030 | 1590 | 260 | 176 | 990 |
| 1×120rm/16 | 3.4 | 2.5 | 16 | 29 | 1255 | 1855 | 330 | 176 | 1100 |
| 1×150rm/16* | 3.4 | 2.5 | 16* | 30 | 1505 | 2150 | 405 | 176 | 1210 |
| 1×185rm/16* | 3.4 | 2.5 | 16* | 32 | 1840 | 2530 | 510 | 176 | 1380 |
| 1×240rm/16* | 3.4 | 2.5 | 16* | 34 | 2365 | 3120 | 665 | 176 | 1580 |
| 1×150rm/25 | 3.4 | 2.5 | 25 | 30.5 | 1595 | 2240 | 405 | 265 | 1300 |
| 1×185rm/25 | 3.4 | 2.5 | 25 | 32.5 | 1930 | 2620 | 510 | 265 | 1450 |
| 1×240rm/25 | 3.4 | 2.5 | 25 | 34.5 | 2450 | 3210 | 665 | 265 | 1670 |
| 1×300rm/25 | 3.4 | 2.5 | 25 | 37 | 2980 | 3800 | 830 | 265 | 1890 |
| 1×400rm/35 | 3.4 | 2.5 | 35 | 40 | 3835 | 4730 | 1060 | 363 | 2300 |
| 1×500rm/35 | 3.4 | 2.5 | 35 | 43 | 4805 | 5740 | 1410 | 363 | 2650 |
Construction Data – 12/20 kV
| Nominal construction | Insulation (mm) | Sheath (mm) | Screen (mm²) | Diameter (mm) | SHEkT Cu weight | SHEkT cable weight | SAHEkT Al weight | SAHEkT Cu weight | SAHEkT cable weight |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 5.5 | 2.5 | 16 | 27 | 490 | 1115 | 95 | 176 | 870 |
| 1×50rm/16 | 5.5 | 2.5 | 16 | 28 | 600 | 1260 | 130 | 176 | 940 |
| 1×70rm/16 | 5.5 | 2.5 | 16 | 30 | 790 | 1510 | 190 | 176 | 1070 |
| 1×95rm/16 | 5.5 | 2.5 | 16 | 32 | 1030 | 1805 | 260 | 176 | 1190 |
| 1×120rm/16 | 5.5 | 2.5 | 16 | 33.5 | 1255 | 1995 | 330 | 176 | 1230 |
| 1×150rm/16* | 5.5 | 2.5 | 16* | 35 | 1505 | 2385 | 405 | 176 | 1440 |
| 1×185rm/16* | 5.5 | 2.5 | 16* | 37 | 1840 | 2775 | 510 | 176 | 1600 |
| 1×240rm/16* | 5.5 | 2.5 | 16* | 39.5 | 2365 | 3370 | 665 | 176 | 1840 |
| 1×150rm/25 | 5.5 | 2.5 | 25 | 35.5 | 1595 | 2465 | 405 | 265 | 1530 |
| 1×185rm/25 | 5.5 | 2.5 | 25 | 37.5 | 1930 | 2880 | 510 | 265 | 1690 |
| 1×240rm/25 | 5.5 | 2.5 | 25 | 40 | 2450 | 3465 | 665 | 265 | 1920 |
| 1×300rm/25 | 5.5 | 2.5 | 25 | 42 | 2980 | 4070 | 830 | 265 | 2150 |
| 1×400rm/35 | 5.5 | 2.5 | 35 | 45 | 3835 | 5025 | 1060 | 363 | 2580 |
| 1×500rm/35 | 5.5 | 2.5 | 35 | 48 | 4805 | 6125 | 1410 | 363 | 2970 |
Construction Data – 18/30 kV
| Nominal construction | Insulation (mm) | Sheath (mm) | Screen (mm²) | Diameter (mm) | SHEkT Cu weight | SHEkT cable weight | SAHEkT Al weight | SAHEkT Cu weight | SAHEkT cable weight |
|---|---|---|---|---|---|---|---|---|---|
| 1×50rm/16 | 8.0 | 2.5 | 16 | 35 | 600 | 1505 | 130 | 176 | 1205 |
| 1×70rm/16 | 8.0 | 2.5 | 16 | 36 | 790 | 1765 | 190 | 176 | 1330 |
| 1×95rm/16 | 8.0 | 2.5 | 16 | 37 | 1030 | 2078 | 260 | 176 | 1475 |
| 1×120rm/16 | 8.0 | 2.5 | 16 | 39 | 1255 | 2358 | 330 | 176 | 1600 |
| 1×150rm/16* | 8.0 | 2.5 | 16* | 40 | 1505 | 1515 | 405 | 176 | 1740 |
| 1×185rm/16* | 8.0 | 2.5 | 16* | 42 | 1840 | 1845 | 510 | 176 | 1905 |
| 1×240rm/16* | 8.0 | 2.5 | 16* | 44 | 2365 | 2355 | 665 | 176 | 2150 |
| 1×150rm/25 | 8.0 | 2.5 | 25 | 40.5 | 1595 | 1595 | 405 | 265 | 1820 |
| 1×185rm/25 | 8.0 | 2.5 | 25 | 42.5 | 1930 | 1930 | 510 | 265 | 1990 |
| 1×240rm/25 | 8.0 | 2.5 | 25 | 44.5 | 2450 | 2450 | 665 | 265 | 2245 |
| 1×300rm/25 | 8.0 | 2.5 | 25 | 47 | 2980 | 2980 | 830 | 265 | 2520 |
| 1×400rm/35 | 8.0 | 2.6 | 35 | 50.5 | 3835 | 3835 | 1060 | 363 | 2995 |
| 1×500rm/35 | 8.0 | 2.7 | 35 | 54 | 4805 | 4805 | 1410 | 363 | 3415 |
Construction Data – 20/35 kV
| Nominal construction | Insulation (mm) | Sheath (mm) | Screen (mm²) | Diameter (mm) | SHEkT Cu weight | SHEkT cable weight | SAHEkT Al weight | SAHEkT Cu weight | SAHEkT cable weight |
|---|---|---|---|---|---|---|---|---|---|
| 1×50rm/16 | 8.8 | 2.5 | 16 | 35.5 | 600 | 1515 | 130 | 176 | 1215 |
| 1×70rm/16 | 8.8 | 2.5 | 16 | 37 | 790 | 1775 | 190 | 176 | 1340 |
| 1×95rm/16 | 8.8 | 2.5 | 16 | 39 | 1030 | 2100 | 260 | 176 | 1500 |
| 1×120rm/16 | 8.8 | 2.5 | 16 | 41 | 1255 | 2400 | 330 | 176 | 1640 |
| 1×150rm/16* | 8.8 | 2.5 | 16* | 41.5 | 1505 | 2720 | 405 | 176 | 1785 |
| 1×185rm/16* | 8.8 | 2.5 | 16* | 43.5 | 1840 | 3140 | 510 | 176 | 1970 |
| 1×240rm/16* | 8.8 | 2.5 | 16* | 46 | 2365 | 3775 | 665 | 176 | 2240 |
| 1×150rm/25 | 8.8 | 2.5 | 25 | 42 | 1595 | 2800 | 405 | 265 | 1885 |
| 1×185rm/25 | 8.8 | 2.5 | 25 | 44 | 1930 | 3225 | 510 | 265 | 2055 |
| 1×240rm/25 | 8.8 | 2.5 | 25 | 46.5 | 2450 | 3870 | 665 | 265 | 2335 |
| 1×300rm/25 | 8.8 | 2.5 | 25 | 48.5 | 2980 | 4500 | 830 | 265 | 2595 |
| 1×400rm/35 | 8.8 | 2.6 | 35 | 52 | 3835 | 5500 | 1060 | 363 | 3070 |
| 1×500rm/35 | 8.8 | 2.7 | 35 | 55.5 | 4805 | 6660 | 1410 | 363 | 3520 |
Factory Overview
Packaging & Shipping
Frequently Asked Questions (FAQ)
Q:- What is the primary application of SHEkT and SAHEkT cables?
A:- These cables are designed for medium-voltage power transmission and distribution in urban and district electrical networks, transformer substations, and industrial plants.
Q:- What is the difference between SHEkT and SAHEkT cables?
A:- SHEkT uses copper conductors, while SAHEkT uses aluminium conductors. Both have XLPE insulation, copper wire screening, and PVC outer sheathing.
Q:- What standard do these cables follow?
A:- Both cable types are manufactured according to BDS 2581-86.
Q:- What type of conductor is used?
A:- They use stranded and compacted copper or aluminium conductors, Class 2, according to IEC 60228.
Q:- What insulation material is used?
A:- Both cables use XLPE (Cross-Linked Polyethylene) insulation with inner and outer semiconductive layers.
Q:- What type of metallic screen is used?
A:- The cables use concentrically laid copper wires and a contact copper tape with a thickness of 0.1 mm.
Q:- What is the maximum continuous operating temperature?
A:- The maximum continuous conductor operating temperature is +90°C.
Q:- What is the maximum short-circuit temperature?
A:- The maximum short-circuit temperature is +250°C for a maximum of 5 seconds.
Q:- What voltage ratings are available?
A:- The available voltage ratings are 3.6/6 kV, 6/10 kV, 12/20 kV, 18/30 kV, and 20/35 kV.
Q:- What is the minimum bending radius?
A:- The specified minimum bending radius is 15 times the cable diameter (15 × D).




Reviews
There are no reviews yet.