SHEk(vn)P / SAHEk(vn)P 3.6/6 kV to 20/35 kV Water-Resistant XLPE Insulated Copper & Aluminium Conductor Power Cable – BDS 2581-86
SHEk(vn)P and SAHEk(vn)P are water-resistant medium voltage power cables designed for reliable electrical power transmission and distribution in urban networks, transformer substations, and industrial installations. Manufactured according to BDS 2581-86 and Additional 4, these cables feature stranded and compacted copper or aluminium conductors, XLPE insulation, semiconductive conductor and insulation screens, water-absorbing tapes, concentric copper wire screening, and a protective black PE Type MDPE outer sheath. Available in voltage ratings from 3.6/6 kV to 20/35 kV, they are suitable for underground installations, cable ducts, conduits, shafts, and industrial power distribution systems.
Application
SHEk(vn)P and SAHEk(vn)P single-core cables with cross-linked polyethylene (XLPE) insulation are designed for the transfer and distribution of electrical power at nominal voltages ranging from 3.6/6 kV to 20/35 kV, with a frequency of 50 Hz.
They are mainly used in urban and district electrical networks, transformer substations, small and medium industrial plants, distribution installations, electric power stations, and industrial systems.
These cables are suitable for fixed installation in lines with unlimited differences in level, indoor installations, cable ducts, conduits, shafts, and underground installations in ditches, as well as outdoor installations under shelters.
Cable Construction
Manufactured according to BDS 2581-86 and Additional 4.
-
Conductor: Copper or aluminium stranded and compacted conductor, according to BDS 904 (IEC 60228), Class 2.
-
Inner semiconductive layer: Semiconductive XLPE compound.
-
Insulation: XLPE (Cross-Linked Polyethylene) compound.
-
Outer semiconductive layer: Semiconductive XLPE compound.
-
Water-resistant element: Layer of semiconductive water-absorbing tapes.
-
Metal screen: Copper wires concentrically laid with one contact copper tape of 0.1 mm thickness.
-
Water-resistant element (optional):
-
Option 1: Water-absorbing insulating tape.
-
Option 2: Water-absorbing powder and a layer of plastic tape.
-
-
Outer sheath: PE compound, Type MDPE.
-
Outer sheath colour: Black.
-
Compliance: RoHS compliant.
Cable Type Identification
| Cable designation | Conductor material |
|---|---|
| SHEk(vn)P | Copper |
| SAHEk(vn)P | Aluminium |
Technical Data
| Parameter | Specification |
|---|---|
| Applicable standard | BDS 2581-86 + Additional 4 |
| Conductor standard | BDS 904 (IEC 60228), Class 2 |
| Conductor material | Copper / Aluminium |
| Conductor resistance at 20°C | According to BDS 904 (IEC 60228), Class 2 |
| Continuous operating temperature | +90°C |
| Maximum overload temperature | +130°C / 100 hours per year maximum |
| Maximum short-circuit temperature | +250°C / 5 seconds maximum |
| Nominal voltage (Uo/U) | 3.6/6, 6/10, 12/20, 18/30, 20/35 kV |
| Highest system voltage (U) | 7.2, 12, 24, 36, 42 kV |
| AC test voltage | 11, 15, 18, 30, 35 kV respectively |
| AC test duration | 5 minutes |
| DC test voltage | 29, 48, 98, 144, 160 kV respectively |
| DC test duration | 15 minutes |
| Partial discharge at 2 × Uo | Maximum 5 pC |
| Minimum bending radius | 15 × D (cable diameter) |
| Minimum laying temperature | Not less than +5°C |
| Operating temperature range | -30°C to +50°C |
| Maximum pulling force during laying | Copper: 50 N/mm²; Aluminium: 30 N/mm² |
Conductor Construction Identification
| Component | Description |
|---|---|
| Conductor material | Copper or aluminium |
| Conductor construction | Stranded and compacted |
| Conductor class | Class 2 |
| Conductor screen | Semiconductive XLPE |
| Insulation | XLPE |
| Insulation screen | Semiconductive XLPE |
| Water-blocking layer | Semiconductive water-absorbing tapes |
| Metallic screen | Copper wires and 0.1 mm contact copper tape |
| Additional water protection | Water-absorbing insulating tape or powder with plastic tape |
| Outer sheath | PE Type MDPE |
| Outer sheath colour | Black |
Colour Coding
-
Outer sheath colour: Black.
-
Individual core insulation colour coding is not specified in the supplied product catalogue.
3. Construction Data Tables
All weights are in kg/km and dimensions are in mm. The catalogue provides separate construction and weight data for copper-conductor SHEk(vn)P and aluminium-conductor SAHEk(vn)P cables.
Column abbreviations:
-
Ins. = Insulation thickness
-
Sheath = Outer sheath thickness
-
Screen = Nominal screen cross-section
-
Dia. = Approximate cable diameter
-
Cu = Copper weight
-
Al = Aluminium weight
-
Cable = Approximate total cable weight
Construction Data – 3.6/6 kV
| Nominal construction (N × mm²) | Ins. | Sheath | Screen | Dia. | SHEk Cu | SHEk Cable | SAHEk Al | SAHEk Cu | SAHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 2.5 | 2.5 | 16 | 22 | 490 | 795 | 95 | 176 | 570 |
| 1×50rm/16 | 2.5 | 2.5 | 16 | 23 | 600 | 930 | 130 | 176 | 625 |
| 1×70rm/16 | 2.5 | 2.5 | 16 | 25 | 790 | 1155 | 190 | 176 | 720 |
| 1×95rm/16 | 2.5 | 2.5 | 16 | 26.5 | 1030 | 1430 | 260 | 176 | 825 |
| 1×120rm/16 | 2.5 | 2.5 | 16 | 28 | 1255 | 1690 | 330 | 176 | 935 |
| 1×150rm/16* | 2.5 | 2.5 | 16* | 29.5 | 1505 | 1980 | 405 | 176 | 1040 |
| 1×185rm/16* | 2.5 | 2.5 | 16* | 31.5 | 1840 | 2360 | 510 | 176 | 1190 |
| 1×240rm/16* | 2.5 | 2.5 | 16* | 33.5 | 2365 | 2950 | 665 | 176 | 1415 |
| 1×150rm/25 | 2.5 | 2.5 | 25 | 30 | 1595 | 2060 | 405 | 265 | 1120 |
| 1×185rm/25 | 2.5 | 2.5 | 25 | 32 | 1930 | 2440 | 510 | 265 | 1270 |
| 1×240rm/25 | 2.6 | 2.5 | 25 | 34 | 2450 | 3040 | 665 | 265 | 1500 |
Construction Data – 6/10 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEk Cu | SHEk Cable | SAHEk Al | SAHEk Cu | SAHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 3.4 | 2.5 | 16 | 24 | 490 | 905 | 95 | 176 | 670 |
| 1×50rm/16 | 3.4 | 2.5 | 16 | 25 | 600 | 1045 | 130 | 176 | 745 |
| 1×70rm/16 | 3.4 | 2.5 | 16 | 27 | 790 | 1275 | 190 | 176 | 845 |
| 1×95rm/16 | 3.4 | 2.5 | 16 | 29 | 1030 | 1560 | 260 | 176 | 950 |
| 1×120rm/16 | 3.4 | 2.5 | 16 | 31 | 1255 | 1820 | 330 | 176 | 1060 |
| 1×150rm/16* | 3.4 | 2.5 | 16* | 32 | 1505 | 2115 | 405 | 176 | 1180 |
| 1×185rm/16* | 3.4 | 2.5 | 16* | 34 | 1840 | 2490 | 510 | 176 | 1325 |
| 1×240rm/16* | 3.4 | 2.5 | 16* | 36 | 2365 | 3080 | 665 | 176 | 1540 |
| 1×150rm/25 | 3.4 | 2.5 | 25 | 32 | 1595 | 2200 | 405 | 265 | 1260 |
| 1×185rm/25 | 3.4 | 2.5 | 25 | 34 | 1930 | 2570 | 510 | 265 | 1405 |
| 1×240rm/25 | 3.4 | 2.5 | 25 | 36 | 2450 | 3160 | 665 | 265 | 1625 |
| 1×300rm/25 | 3.4 | 2.5 | 25 | 38.5 | 2980 | 3750 | 830 | 265 | 1850 |
| 1×400rm/35 | 3.4 | 2.5 | 35 | 42 | 3835 | 4680 | 1060 | 363 | 2250 |
| 1×500rm/35 | 3.4 | 2.5 | 35 | 45 | 4805 | 5720 | 1410 | 363 | 2600 |
Construction Data – 12/20 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEk Cu | SHEk Cable | SAHEk Al | SAHEk Cu | SAHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 5.5 | 2.5 | 16 | 28 | 490 | 1080 | 95 | 176 | 855 |
| 1×50rm/16 | 5.5 | 2.5 | 16 | 29 | 600 | 1225 | 130 | 176 | 925 |
| 1×70rm/16 | 5.5 | 2.5 | 16 | 31 | 790 | 1470 | 190 | 176 | 1040 |
| 1×95rm/16 | 5.5 | 2.5 | 16 | 33 | 1030 | 1760 | 260 | 176 | 1165 |
| 1×120rm/16 | 5.5 | 2.5 | 16 | 34 | 1255 | 1950 | 330 | 176 | 1195 |
| 1×150rm/16* | 5.5 | 2.5 | 16* | 36 | 1505 | 2340 | 405 | 176 | 1400 |
| 1×185rm/16* | 5.5 | 2.5 | 16* | 37.5 | 1840 | 2730 | 510 | 176 | 1560 |
| 1×240rm/16* | 5.5 | 2.5 | 16* | 40 | 2365 | 3400 | 665 | 176 | 1875 |
| 1×150rm/25 | 5.5 | 2.5 | 25 | 36 | 1595 | 2420 | 405 | 265 | 1500 |
| 1×185rm/25 | 5.5 | 2.5 | 25 | 38 | 1930 | 2810 | 510 | 265 | 1640 |
| 1×240rm/25 | 5.5 | 2.5 | 25 | 40.5 | 2450 | 3400 | 665 | 265 | 1875 |
| 1×300rm/25 | 5.5 | 2.5 | 25 | 42.5 | 2980 | 4010 | 830 | 265 | 2110 |
| 1×400rm/35 | 5.5 | 2.5 | 35 | 46 | 3835 | 4950 | 1060 | 363 | 2535 |
| 1×500rm/35 | 5.5 | 2.5 | 35 | 49 | 4805 | 6050 | 1410 | 363 | 2920 |
Construction Data – 18/30 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEk Cu | SHEk Cable | SAHEk Al | SAHEk Cu | SAHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×50rm/16 | 8.0 | 2.5 | 16 | 35.5 | 600 | 1460 | 130 | 176 | 1160 |
| 1×70rm/16 | 8.0 | 2.5 | 16 | 36.5 | 790 | 1720 | 190 | 176 | 1285 |
| 1×95rm/16 | 8.0 | 2.5 | 16 | 37.5 | 1030 | 2030 | 260 | 176 | 1425 |
| 1×120rm/16 | 8.0 | 2.5 | 16 | 39.5 | 1255 | 2305 | 330 | 176 | 1550 |
| 1×150rm/25 | 8.0 | 2.5 | 25 | 41 | 1595 | 2705 | 405 | 265 | 1770 |
| 1×185rm/25 | 8.0 | 2.5 | 25 | 43 | 1930 | 3105 | 510 | 265 | 1935 |
| 1×240rm/25 | 8.0 | 2.5 | 25 | 45 | 2450 | 3725 | 665 | 265 | 2185 |
| 1×300rm/25 | 8.0 | 2.5 | 25 | 48 | 2980 | 4360 | 830 | 265 | 2455 |
| 1×400rm/35 | 8.0 | 2.5 | 35 | 51.5 | 3835 | 5345 | 1060 | 363 | 2915 |
| 1×500rm/35 | 8.0 | 2.5 | 35 | 55 | 4805 | 6480 | 1410 | 363 | 3340 |
Construction Data – 20/35 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEk Cu | SHEk Cable | SAHEk Al | SAHEk Cu | SAHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×50rm/16 | 8.8 | 2.5 | 16 | 36.5 | 600 | 1480 | 130 | 176 | 1185 |
| 1×70rm/16 | 8.8 | 2.5 | 16 | 38 | 790 | 1750 | 190 | 176 | 1320 |
| 1×95rm/16 | 8.8 | 2.5 | 16 | 40 | 1030 | 2065 | 260 | 176 | 1460 |
| 1×120rm/16 | 8.8 | 2.5 | 16 | 42 | 1255 | 2355 | 330 | 176 | 1600 |
| 1×150rm/16* | 8.8 | 2.5 | 16* | 43 | 1505 | 2690 | 405 | 176 | 1750 |
| 1×185rm/16* | 8.8 | 2.5 | 16* | 44 | 1840 | 3080 | 510 | 176 | 1915 |
| 1×240rm/16* | 8.8 | 2.5 | 16* | 47 | 2365 | 3720 | 665 | 176 | 2175 |
| 1×150rm/25 | 8.8 | 2.5 | 25 | 43.5 | 1595 | 2770 | 405 | 265 | 1830 |
| 1×185rm/25 | 8.8 | 2.5 | 25 | 45 | 1930 | 3175 | 510 | 265 | 2000 |
| 1×240rm/25 | 8.8 | 2.5 | 25 | 47.5 | 2450 | 3815 | 665 | 265 | 2270 |
| 1×300rm/25 | 8.8 | 2.5 | 25 | 50 | 2980 | 4450 | 830 | 265 | 2500 |
| 1×400rm/35 | 8.8 | 2.6 | 35 | 53.5 | 3835 | 3830 | 1060 | 363 | 3010 |
| 1×500rm/35 | 8.8 | 2.8 | 35 | 56.5 | 4805 | 4800 | 1410 | 363 | 3430 |
Factory Overview
Packaging & Shipping

Frequently Asked Questions (FAQ)
Q:- What is the primary application of SHEk(vn)P and SAHEk(vn)P cables?
A:- These cables are designed for medium-voltage electrical power transmission and distribution in urban networks, transformer substations, industrial plants, and electrical power stations.
Q:- What is the difference between SHEk(vn)P and SAHEk(vn)P cables?
A:- SHEk(vn)P uses copper conductors, while SAHEk(vn)P uses aluminium conductors. Both feature XLPE insulation, copper wire screening, water-blocking elements, and PE outer sheathing.
Q:- What standards do these cables follow?
A:- They are manufactured according to BDS 2581-86 and Additional 4.
Q:- What type of conductor is used?
A:- Both cable variants use stranded and compacted Class 2 copper or aluminium conductors according to IEC 60228.
Q:- What insulation material is used?
A:- They use XLPE (Cross-Linked Polyethylene) insulation with inner and outer semiconductive layers.
Q:- What makes these cables water-resistant?
A:- They incorporate semiconductive water-absorbing tapes and optional additional water-blocking materials, such as water-absorbing insulating tape or water-absorbing powder with plastic tape.
Q:- What type of metallic screen is used?
A:- The cables feature concentrically laid copper wires and a contact copper tape with a thickness of 0.1 mm.
Q:- What is the maximum continuous operating temperature?
A:- The maximum continuous conductor operating temperature is +90°C.
Q:- What is the maximum short-circuit temperature?
A:- The maximum short-circuit temperature is +250°C for a maximum of 5 seconds.
Q:- What voltage ratings are available?
A:- The available voltage ratings are 3.6/6 kV, 6/10 kV, 12/20 kV, 18/30 kV, and 20/35 kV.


Reviews