SAVVn/A 0.6/1 kV Aluminum Flame Retardant Power Cable – FN KI 02.001-96
The SAVVn/A 0.6/1 kV cable delivers dependable power distribution for industrial and commercial installations. Constructed with aluminum conductors, PVC insulation, a flame retardant filling, and a black flame retardant PVC outer sheath, it offers exceptional fire safety. Because it meets FN KI 02.001-96 standards, passes the BDS IEC 332-3/C2 Category A flame test, and is RoHS compliant, it provides a safe and reliable solution for environments requiring non-proliferation of flames.
Application
SAVVn/A cables provide reliable power transfer and distribution in networks with a nominal voltage of Uo/U 0.6/1 kV and a frequency of 50 Hz. Because they feature aluminum conductors and flame retardant materials, installers use them in surroundings that require non-proliferation of flames. Furthermore, they ensure safety in industrial and commercial installations where fire risk is a concern. Consequently, they deliver consistent performance and safety in demanding environments.
Cable construction
This cable strictly adheres to FN KI 02.001-96 standards. It features aluminum solid or twisted wires (class 1 or 2) that comply with BDS 904-84. The insulation uses a PVC compound according to BDS 5792-84. A filling with flame retardant properties forms the inner sheath. Finally, a black PVC flame retardant outer sheath of flame retardancy category A protects the entire assembly. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance according to BDS 904-84. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of 4 kV (alternating) and 12 kV (direct). The temperature range for laying and installing is -5 °C, while the exploitation and storage range is -30 °C to +50 °C. The operating temperature reaches +70 °C. The short circuit temperature is +160 °C for no more than 5 seconds. Installers must respect a minimum bending radius of 10 times the cable diameter. Furthermore, it passes the flame retardant test according to BDS IEC 332-3/C2, Category A.
Color coding
Clear color coding ensures safe and accurate wiring. Conductors without a yellow/green earth core feature random colors for 1 core, brown and blue for 2 cores, brown, black, and blue for 3 cores, blue, brown, black, and grey for 4 cores, and blue, brown, black, grey, and black for 5 cores. Conductors with a yellow/green earth core feature yellow/green, blue, and brown for 3 cores, yellow/green, brown, black, and grey for 4 cores, and yellow/green, blue, brown, black, and grey for 5 cores. The neutral conductor is always blue.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data SAVVn/A 0.6/1 kV
| Number of wires and nominal cross-section | Form of conductor | Cable diameter approx. | Mass of Al | Mass of cable approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 1 x 2,5 | re | 7,5 | 7 | 72 |
| 1 x 4 | re | 8,4 | 12 | 93 |
| 1 x 6 | re | 9,1 | 17 | 107 |
| 1 x 10 | re | 10,0 | 28 | 152 |
| 1 x 16 | re | 10,6 | 45 | 158 |
| 1 x 25 | re | 12,2 | 68 | 210 |
| 1 x 35 | re | 13,2 | 95 | 252 |
| 1 x 50 | re | 14,6 | 127 | 305 |
| 1 x 70 | re | 17,4 | 190 | 330 |
| 1 x 95 | re | 18,4 | 260 | 405 |
| 1 x 120 | re | 19,9 | 341 | 525 |
| 1 x 150 | re | 22,8 | 405 | 682 |
| 1 x 185 | re | 24,7 | 510 | 755 |
| 1 x 240 | re | 26,7 | 665 | 822 |
| 1 x 300 | re | 30,1 | 830 | 1332 |
| 1 x 400 | re | 33,5 | 1060 | 1742 |
| 1 x 500 | re | 37,9 | 1332 | 2148 |
| 2 x 1,5 | re | 9,9 | 14 | 92 |
| 2 x 2,5 | re | 10,9 | 23 | 118 |
| 2 x 4 | re | 11,5 | 35 | 142 |
| 2 x 6 | re | 14,9 | 56 | 293 |
| 2 x 10 | re | 16,5 | 90 | 307 |
| 2 x 16 | re | 17,4 | 157 | 457 |
| 2 x 25 | re | 22,4 | 210 | 550 |
| 2 x 35 | re | 25,4 | 290 | 683 |
| 2 x 50 | re | 25,9 | 385 | 882 |
| 2 x 70 | re | 27,8 | 510 | 1160 |
| 2 x 95 | re | 37,9 | 520 | 1995 |
| 3 x 1,5 | re | 13,5 | 21 | 240 |
| 3 x 2,5 | re | 14,1 | 35 | 274 |
| 3 x 4 | re | 15,1 | 51 | 319 |
| 3 x 6 | re | 17,0 | 90 | 383 |
| 3 x 10 | re | 18,5 | 135 | 465 |
| 3 x 16 | re | 20,2 | 210 | 582 |
| 3 x 25 | re | 25,1 | 270 | 783 |
| 3 x 35 | rm | 25,8 | 290 | 966 |
| 3 x 50 | rm | 29,2 | 385 | 1240 |
| 3 x 70 | rm | 32,0 | 560 | 1761 |
| 3 x 95 | rm | 40,4 | 720 | 2295 |
| 3 x 120 | sm | 37,7 | 1035 | 2059 |
| 3 x 150 | sm | 43,2 | 1035 | 2765 |
| 3 x 185 | sm | 45,8 | 1560 | 3107 |
| 3 x 240 | sm | 51,2 | 2035 | 3605 |
| 3 x 300 | sm | 57,5 | 2385 | 4602 |
| 3 x 4 + 4 | re/re | 17,9 | 63 | 425 |
| 3 x 10 + 6 | re/re | 19,4 | 101 | 510 |
| 3 x 16 + 10 | re/re | 21,5 | 165 | 645 |
| 3 x 25 + 16 | rm/re | 24,9 | 255 | 800 |
| 3 x 35 + 16 | rm/rm | 28,0 | 355 | 878 |
| 3 x 50 + 25 | rm/rm | 30,5 | 480 | 1374 |
| 3 x 70 + 35 | sm/rm | 32,6 | 485 | 1475 |
| 3 x 95 + 50 | sm/rm | 35,6 | 600 | 1450 |
| 3 x 120 + 70 | sm/rm | 41,9 | 860 | 1999 |
| 3 x 150 + 70 | sm/rm | 41,0 | 1060 | 2389 |
| 3 x 185 + 95 | sm/rm | 43,2 | 1275 | 2907 |
| 3 x 240 + 120 | sm/rm | 50,9 | 1740 | 3298 |
| 3 x 300 + 150 | sm/rm | 64,3 | 1625 | 4225 |
| 4 x 2,5 | re | 14,4 | 28 | 265 |
| 4 x 4 | re | 15,2 | 46 | 301 |
| 4 x 6 | re | 17,6 | 92 | 409 |
| 4 x 10 | re | 19,8 | 112 | 512 |
| 4 x 16 | rm | 24,9 | 180 | 683 |
| 4 x 25 | rm | 25,8 | 280 | 944 |
| 4 x 35 | rm | 28,2 | 320 | 1537 |
| 4 x 50 | rm | 33,0 | 520 | 2110 |
| 4 x 70 | rm | 39,1 | 760 | 2134 |
| 4 x 95 | rm | 45,5 | 1060 | 2801 |
| 4 x 120 | sm | 46,7 | 1340 | 3217 |
| 4 x 150 | sm | 47,5 | 1590 | 4183 |
| 4 x 185 | sm | 48,0 | 1682 | 4738 |
| 4 x 240 | sm | 48,1 | 2050 | 6142 |
| 4 x 300 | sm | 53,7 | 2100 | 6135 |
| 5 x 1,5 | re | 16,4 | 35 | 428 |
| 5 x 2,5 | re | 16,9 | 54 | 473 |
| 5 x 4 | re | 18,1 | 77 | 559 |
| 5 x 6 | re | 21,4 | 140 | 620 |
| 5 x 10 | re | 23,7 | 140 | 750 |
| 5 x 16 | rm | 24,0 | 225 | 795 |
| 5 x 25 | rm | 30,5 | 350 | 1657 |
| 5 x 35 | rm | 33,0 | 350 | 1952 |
| 5 x 50 | rm | 38,1 | 421 | 1983 |
| 5 x 70 | rm | 50,0 | 800 | 3265 |
| 5 x 95 | rm | 49,8 | 1345 | 3497 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the SAVVn/A cable?
A:- It is used for the transfer and distribution of electrical power in networks with a nominal voltage of 0.6/1 kV, specifically in surroundings requiring non-proliferation of flames.
Q:- What are the key fire safety features of this cable?
A:- It features a flame retardant filling and a black PVC flame retardant outer sheath (Category A), passing the BDS IEC 332-3/C2 flame test.
Q:- What standards does the cable construction follow?
A:- The construction adheres to FN KI 02.001-96 standards, and the conductor complies with BDS 904-84.
Q:- What type of conductor and insulation does it use?
A:- It uses aluminum solid or twisted wires (class 1 or 2) with a PVC compound insulation according to BDS 5792-84.
Q:- What is the temperature range for this cable?
A:- The temperature range for laying and installing is -5°C, while the exploitation and storage range is -30°C to +50°C.
Q:- What is the maximum operating and short-circuit temperature?
A:- The operating temperature is +70°C, and the short-circuit temperature is +160°C for no more than 5 seconds.
Q:- What is the test voltage for this cable?
A:- The test voltage is 4 kV (alternating) and 12 kV (direct).
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter (10 x D cable).
Q:- What is the neutral conductor color?
A:- The neutral conductor is always blue.
Q:- Is this cable RoHS compliant?
A:- Yes, the product is RoHS compliant.




Reviews
There are no reviews yet.