NYY-O & NYY-J 0.6/1 kV Low Voltage Power Cable – RoHS Compliant
The NYY-O and NYY-J 0.6/1 kV cables deliver heavy-duty power distribution for industrial and secondary network applications. Constructed with solid or multi-strand copper conductors, PVC insulation, and a black PVC outer sheath, they offer exceptional durability. Because they are RoHS and CE compliant, they provide a safe and reliable solution for outdoor, underground, and in-water installations.
Application
NYY cables provide reliable power distribution in power plants, industrial settings, and switching installations. They also excel in secondary distribution networks. Because of their robust design, installers prefer them for outdoor applications, indoor installations, open air, underground, and even in water. However, you should not use them where mechanical damage is anticipated.
Cable design
This cable strictly adheres to VDE 0276 part 603 standards. It features solid or multi-strand copper wires (class 1 or 2) that comply with VDE 0295 (IEC 60228). The insulation uses PVC type DIV4 according to VDE0276, while core identification follows VDE 0293. Additionally, a filling compound forms the inner sheath. Finally, a black PVC type DMV5 sheath (acc. VDE 0276) protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to VDE 0295 class 1 or 2 (IEC 60228). The maximum conductor temperature reaches 70 °C. During a short circuit, it can withstand 160 °C for no more than 5 seconds. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of AC – 4 kV at 50 Hz. Installers must respect a minimum bending radius of 15 times the cable diameter for multi-core cables, or 12 times for single-core cables. The temperature of operation ranges from -30 °C to +50 °C. Furthermore, it passes the flame test according to VDE 0472 part 804 class B (IEC 332 part 1).
Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are either black or yellow/green. Double core cables feature blue and brown, or yellow-green and black.
Multi-Core Color Configurations
-
3-core: brown, black, grey, or yellow/green, blue, brown
-
4-core: blue, brown, black, grey or yellow/green, brown, black, grey
-
5-core: blue, brown, black, grey, black or yellow/green, blue, brown, black, grey
-
Multiple core: black with number mark on cores, or black with number mark on cores and yellow/green core in the outer cover
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information regarding the NYY-O and NYY-J constructions.
| Number of conductors and nominal cross section | Shape | Outer diameter approx. | Cu weight approx. | Cable weight approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 1 x 1,5 | re | 5,7 | 14 | 50 |
| 1 x 2,5 | re | 6,4 | 23 | 65 |
| 1 x 4,0 | re | 6,9 | 37 | 87 |
| 1 x 6,0 | re | 7,6 | 56 | 110 |
| 1 x 10,0 | re | 8,7 | 94 | 165 |
| 1 x 16,0 | rm | 10,1 | 153 | 237 |
| 2 x 1,5 | re | 9,3 | 28 | 140 |
| 2 x 2,5 | re | 10,5 | 46 | 175 |
| 2 x 4,0 | re | 11,9 | 75 | 235 |
| 2 x 6,0 | re | 12,9 | 112 | 297 |
| 2 x 10,0 | re | 16,2 | 188 | 487 |
| 2 x 16,0 | rm | 19,0 | 307 | 696 |
| 2 x 25,0 | rm | 22,7 | 485 | 1036 |
| 2 x 35,0 | rm | 25,8 | 673 | 1370 |
| 3 x 1,5 | re | 9,8 | 43 | 145 |
| 3 x 2,5 | re | 11,0 | 70 | 204 |
| 3 x 4,0 | re | 12,5 | 112 | 279 |
| 3 x 6,0 | re | 13,8 | 168 | 364 |
| 3 x 10,0 | re | 16,7 | 282 | 571 |
| 3 x 16,0 | rm | 19,9 | 460 | 849 |
| 3 x 25,0 | rm | 24,1 | 728 | 1270 |
| 3 x 35,0 | rm | 26,7 | 1010 | 1656 |
| 4 x 1,5 | re | 10,3 | 57 | 176 |
| 4 x 2,5 | re | 11,9 | 93 | 242 |
| 4 x 4,0 | re | 14,0 | 149 | 352 |
| 4 x 6,0 | re | 15,2 | 223 | 454 |
| 4 x 10,0 | re | 18,2 | 376 | 703 |
| 4 x 16,0 | rm | 21,8 | 614 | 1051 |
| 4 x 25,0 | rm | 26,6 | 970 | 1603 |
| 4 x 35,0 | rm | 29,3 | 1346 | 2059 |
| 5 x 1,5 | re | 10,9 | 71 | 207 |
| 5 x 2,5 | re | 12,6 | 116 | 287 |
| 5 x 4,0 | re | 15,2 | 187 | 433 |
| 5 x 6,0 | re | 16,5 | 279 | 541 |
| 5 x 10,0 | re | 19,9 | 470 | 844 |
| 5 x 16,0 | rm | 24,3 | 767 | 1268 |
| 5 x 25,0 | rm | 29,2 | 1213 | 1934 |
| 5 x 35,0 | rm | 32,4 | 1683 | 2536 |
| 7 x 1,5 | re | 11,8 | 100 | 250 |
| 7 x 2,5 | re | 14,0 | 163 | 366 |
| 10 x 1,5 | re | 14,9 | 142 | 400 |
| 12 x 1,5 | re | 15,3 | 171 | 458 |
| Number of wires and nominal cross section | Shape | Outer diameter approx. | Copper weight approx. | Cable weight approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 1 x 1,5 | re | 7,1 | 14 | 63 |
| 1 x 2,5 | re | 7,8 | 23 | 80 |
| 1 x 4,0 | re | 8,4 | 37 | 104 |
| 1 x 6,0 | re | 8,9 | 56 | 128 |
| 1 x 10,0 | re | 9,9 | 94 | 183 |
| 1 x 16,0 | re | 10,7 | 149 | 249 |
| 1 x 25,0 | rm | 12,7 | 243 | 359 |
| 1 x 35,0 | rm | 13,9 | 337 | 463 |
| 1 x 50,0 | rm | 15,6 | 480 | 633 |
| 1 x 70,0 | rm | 17,1 | 656 | 817 |
| 1 x 95,0 | rm | 19,4 | 911 | 1092 |
| 1 x 120,0 | rm | 20,9 | 1121 | 1326 |
| 1 x 150,0 | rm | 22,7 | 1415 | 1627 |
| 1 x 185,0 | rm | 25,0 | 1770 | 2013 |
| 1 x 240,0 | rm | 27,8 | 2273 | 2553 |
| 1 x 300,0 | rm | 30,7 | 2872 | 3200 |
| 1 x 400,0 | rm | 34,1 | 3892 | 4148 |
| 1 x 500,0 | rm | 38,1 | 4828 | 5132 |
| 2 x 1,5 | re | 11,2 | 28 | 132 |
| 2 x 2,5 | re | 12,9 | 46 | 155 |
| 2 x 4,0 | re | 14,9 | 75 | 215 |
| 2 x 6,0 | re | 15,9 | 112 | 236 |
| 2 x 10,0 | re | 17,5 | 188 | 306 |
| 2 x 16,0 | rm | 19,4 | 298 | 456 |
| 2 x 25,0 | rm | 22,5 | 498 | 676 |
| 2 x 35,0 | rm | 25,7 | 673 | 1301 |
| 2 x 50,0 | rm | 28,9 | 958 | 1690 |
| 2 x 70,0 | rm | 31,4 | 1319 | 2047 |
| 2 x 95,0 | rm | 38,0 | 1822 | 3033 |
| 3 x 1,5 | re | 12,1 | 43 | 201 |
| 3 x 2,5 | re | 12,9 | 70 | 247 |
| 3 x 4,0 | re | 15,0 | 112 | 350 |
| 3 x 6,0 | re | 16,1 | 168 | 436 |
| 3 x 10,0 | re | 18,0 | 252 | 556 |
| 3 x 16,0 | rm | 20,1 | 447 | 828 |
| 3 x 25,0 | rm | 24,4 | 728 | 1250 |
| 3 x 35,0 | rm | 26,7 | 986 | 1424 |
| 3 x 50,0 | rm | 30,4 | 1363 | 2139 |
| 3 x 70,0 | sm | 29,2 | 1968 | 2380 |
| 3 x 95,0 | sm | 32,9 | 2685 | 3082 |
| 3 x 120,0 | sm | 35,4 | 3460 | 3653 |
| 3 x 150,0 | sm | 39,2 | 4245 | 4687 |
| 3 x 185,0 | sm | 43,5 | 5227 | 5706 |
| 3 x 240,0 | sm | 48,1 | 6981 | 7089 |
| 3 x 300,0 | sm | 53,5 | 8681 | 9702 |
| 3 x 400,0 | sm | 59,7 | 11516 | 11752 |
| 3 x 500,0 | sm | 62,5 | 1505 | 2091 |
| 3 x 50,0+25 | sm | 29,2 | 1595 | 2091 |
| 3 x 70,0+35 | sm | 33,4 | 2300 | 2800 |
| 3 x 95,0+50 | sm | 37,9 | 3330 | 3770 |
| 3 x 120,0+70 | sm | 40,8 | 4096 | 4779 |
| 3 x 150,0+70 | sm | 44,8 | 5001 | 5685 |
| 3 x 185,0+95 | sm | 49,2 | 6353 | 7052 |
| 3 x 240,0+120 | sm | 55,3 | 8128 | 9227 |
| 3 x 300,0+150 | sm | 60,9 | 10035 | 11383 |
| 4 x 1,5 | re | 13,8 | 57 | 252 |
| 4 x 2,5 | re | 15,8 | 93 | 289 |
| 4 x 4,0 | re | 16,2 | 149 | 419 |
| 4 x 6,0 | re | 17,6 | 223 | 533 |
| 4 x 10,0 | re | 19,5 | 376 | 741 |
| 4 x 16,0 | rm | 21,8 | 595 | 1024 |
| 4 x 25,0 | rm | 27,2 | 970 | 1615 |
| 4 x 35,0 | rm | 30,1 | 1321 | 1893 |
| 4 x 50,0 | sm | 29,2 | 1817 | 2311 |
| 4 x 70,0 | sm | 33,4 | 2624 | 3142 |
| 4 x 95,0 | sm | 39,4 | 3587 | 4256 |
| 4 x 120,0 | sm | 44,8 | 4547 | 5292 |
| 4 x 150,0 | sm | 44,8 | 5503 | 6446 |
| 4 x 240,0 | sm | 55,3 | 8108 | 10426 |
| 4 x 300,0 | sm | 60,9 | 11548 | 12850 |
| 5 x 1,5 | re | 13,7 | 71 | 272 |
| 5 x 2,5 | re | 14,8 | 116 | 341 |
| 5 x 4,0 | re | 17,9 | 187 | 435 |
| 5 x 6,0 | re | 19,3 | 279 | 591 |
| 5 x 10,0 | re | 21,6 | 470 | 826 |
| 5 x 16,0 | rm | 24,1 | 744 | 1262 |
| 5 x 25,0 | rm | 30,0 | 1213 | 1929 |
| 5 x 35,0 | rm | 33,5 | 1683 | 2593 |
| 5 x 50,0 | sm | 35,1 | 2271 | 3435 |
| 5 x 70,0 | sm | 41,7 | 3203 | 4577 |
| 5 x 95,0 | sm | 45,1 | 4554 | 6318 |
Note: Other core configuration and special constructions manu-factured upon request. Cables with same construction may produced according to IEC 60502.
Factory Overview
Packaging & Shipping
FAQ
Q1: What is the difference between NYY-O and NYY-J cables?
A: The “O” designation typically refers to cables without a green/yellow earth core, while the “J” designation includes a green/yellow earth core in multi-core configurations. Both versions share the same robust construction and 0.6/1 kV voltage rating.
Q2: Where can I safely install this cable?
A: You can install NYY cables in power plants, industrial switching stations, and secondary distribution networks. They perform exceptionally well in outdoor applications, indoor installations, open air, underground, and even in water. However, do not use them where mechanical damage is anticipated.
Q3: What are the temperature and voltage limits?
A: The cable operates at a maximum continuous conductor temperature of 70 °C. During a short circuit, it withstands 160 °C for up to 5 seconds. The operational ambient temperature ranges from -30 °C to +50 °C. Furthermore, the rated voltage is 0.6/1 kV, and the AC test voltage is 4 kV at 50 Hz.
Q4: Does this cable meet safety and environmental standards?
A: Yes. The construction follows VDE 0276 part 603 standards. Additionally, it features a flame test rating according to VDE 0472 part 804 class B (IEC 332 part 1). Moreover, the product is fully RoHS and CE compliant, ensuring it meets strict environmental and safety regulations.
Q5: What materials make up the cable’s construction?
A: The cable features solid or multi-strand copper conductors (Class 1 or 2 per VDE 0295/IEC 60228) insulated with PVC type DIV4. A filling compound forms the inner sheath, and a black PVC type DMV5 outer sheath provides ultimate protection.
Q6: How do I identify the cores inside the cable?
A: Core identification follows VDE 0293 standards. Single cores are black or yellow/green. Double cores feature blue/brown or yellow-green/black. Multi-core cables use color sequences like brown, black, and grey, or they use black cores with printed number marks.
Q7: What is the minimum bending radius during installation?
A: To prevent damage, you must maintain a minimum bending radius of 15 times the cable diameter (15 x D) for multi-core cables, or 12 times the cable diameter (12 x D) for single-core cables.



Reviews