PVC/OSCR/PVC/SWA/PVC Armoured Screened Control Cable – ESI 09-6
The PVC/OSCR/PVC/SWA/PVC cable delivers dependable communication and control connections for industrial and infrastructure applications. Constructed with solid copper conductors, PVC insulation, twisted pairs, an aluminum tape screen, steel wire armour, and a black PVC outer sheath, it offers exceptional mechanical protection and signal integrity. Because it meets ESI 09-6 standards and is RoHS compliant, it provides a safe and reliable solution for electrical instrument circuits in outdoor and underground installations.
Application
PVC/OSCR/PVC/SWA/PVC cables provide reliable communication and control connections for industrial and infrastructure applications. Because of their steel wire armour and overall screen, installers use them in electrical instrument circuits to provide communication services. Consequently, they deliver consistent performance and signal integrity in physically demanding environments.
Cable construction
This cable adheres to ESI 09-6, issue 6 standards. It features a solid copper conductor with a diameter of 0.8 mm. The insulation uses a PVC type TI1 compound (according to BS 6746). Each pair is twisted, with pairs stranded into units or layers, incorporating a minimum of 1 layer of plastic tape. A screen of aluminum tape (one side coated with polyester and 1 solid tinned copper wire with a diameter of 0.8mm) provides overall shielding. A PVC compound type TM1 forms the inner sheath. A single layer of galvanized steel wires (according to BS 1442) provides the armour. The outer sheath uses a PVC compound type TM1 (according to BS 6746) in black color. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C of max. 36.8 MΩ/km. The insulation resistance is min. 80 MΩ.km. The mutual capacitance at 800 Hz is max. 150 nF/km. The capacitance unbalance at 800 Hz is max. 400 pF/500m. The test voltage is 50 Hz, 1 min for 500V (wire-wire) and 2000V (wire-screen). The operating voltage peak value is 150V. The temperature range is mobile -5 °C to +50 °C and fixed -20 °C to +70 °C. The minimum bending radius is 15 x cable diameter.
Cable core construction
The pairs are arranged in layers, with specific units (10×2) for larger pair counts. Each unit is lapped with colored tape for identification: Unit 1 – Blue, Unit 2 – Orange, Unit 3 – Green, Unit 4 – Brown, Unit 5 – Grey.
Color coding
Clear color coding ensures safe and accurate wiring. The 2-pair (quad cables) use white, red, blue, and orange. For multi-pair cables, the a-wire colors include white, black, red, etc., and the b-wire colors include blue, orange, green, etc.
Type codes
PVC = insulation or sheath of PVC, SWA = galvanized steel wires armour, OSCR = screen of aluminum tape.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data PVC/PVC/SWA/PVC… x2x1/0.8
| Number of pairs | Diameter of armour wire | External diameter approx. | Copper weight | Cable weight approx. |
|---|---|---|---|---|
| mm | mm | kg/km | kg/km | |
| 2x2x0.8 | 0,90 | 10,3 | 24 | 227 |
| 5x2x0.8 | 0,90 | 13,7 | 51 | 362 |
| 10x2x0.8 | 1,25 | 17,0 | 98 | 617 |
| 15x2x0.8 | 1,25 | 18,6 | 144 | 741 |
| 20x2x0.8 | 1,25 | 20,8 | 191 | 898 |
| 30x2x0.8 | 1,25 | 23,6 | 284 | 1123 |
| 40x2x0.8 | 1,60 | 26,8 | 377 | 1521 |
| 50x2x0.8 | 1,60 | 28,8 | 470 | 1742 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the PVC/OSCR/PVC/SWA/PVC cable?
A:- It is used in electrical instrument circuits to provide communication services, particularly in outdoor and underground applications where mechanical damage is not anticipated.
Q:- What are the key shielding and protection features of this cable?
A:- It features an aluminum tape screen (OSCR) for signal protection and a single layer of galvanized steel wires (SWA) for robust mechanical protection.
Q:- What standards does the cable construction follow?
A:- The construction adheres to ESI 09-6, issue 6 standards.
Q:- What type of conductor and insulation does it use?
A:- It uses a solid copper conductor with a PVC type TI1 insulation according to BS 6746.
Q:- What is the temperature range for this cable?
A:- The fixed temperature range is -20°C to +70°C, and the mobile temperature range is -5°C to +50°C.
Q:- What is the mutual capacitance of this cable?
A:- The mutual capacitance at 800 Hz is max. 150 nF/km.
Q:- What is the test voltage for this cable?
A:- The test voltage is 50 Hz, 1 min for 500V (wire-wire) and 2000V (wire-screen).
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter.
Q:- What is the conductor resistance at 20°C?
A:- The conductor resistance at 20°C is max. 36.8 MΩ/km.
Q:- How are the units identified in larger multi-pair cables?
A:- Each 10-pair unit is lapped with colored tape for identification: Unit 1 (Blue), Unit 2 (Orange), Unit 3 (Green), Unit 4 (Brown), and Unit 5 (Grey).




Reviews
There are no reviews yet.