3.8/6.6kV Aluminium XLPE Single-Core Light Duty Screened Power Cable – AS/NZS 1429.1

The 3.8/6.6kV aluminium XLPE single-core light duty screened power cable provides dependable electrical connections for urban power distribution networks, industrial facilities and underground medium voltage power installations. It features a compacted annealed aluminium conductor, TR-XLPE insulation, a light duty annealed copper wire screen and a PVC or PVC/HDPE outer sheath.

Furthermore, it supports a rated voltage of 3.8/6.6kV and a maximum operating temperature of 90°C. The light duty copper wire screen features a specified minimum fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, subject to applicable standard requirements.

Application

The 3.8/6.6kV aluminium XLPE single-core light duty screened power cable is designed for primary power supply applications in urban electrical distribution networks, industrial facilities and underground medium voltage power distribution systems.

Furthermore, the compacted annealed aluminium conductor provides efficient electrical conductivity, reduced conductor weight and an economical alternative to copper conductor power cables. The TR-XLPE (Tree-Retardant Cross-Linked Polyethylene) insulation provides enhanced resistance to water tree formation and electrical insulation degradation.

In addition, the light duty annealed copper wire screen provides a conductive path for earth fault currents, while the PVC or PVC/HDPE outer sheath provides protection against environmental influences.

These cables are suitable for direct burial, underground duct installations, unenclosed installations where they are not subject to mechanical damage, and installations requiring cable gland termination.

Cable Construction

  • Standard: AS/NZS 1429.1:2000.

  • Rated Voltage: 3.8/6.6kV (3800/6600V).

  • Conductor: Compacted annealed aluminium.

  • Insulation: TR-XLPE (Tree-Retardant Cross-Linked Polyethylene).

  • Core Identification: Numbered cores, as specified in the datasheet.

  • Number of Cores: Single-core (1C).

  • Screen: Light duty annealed copper wire screen.

  • Outer Sheath: PVC 5V-90 or PVC 5V-90/HDPE.

  • Maximum Operating Temperature: 90°C.

  • Screen Fault Current Rating: Minimum 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum coverage allowable under the applicable standard.

  • Sheath Marking: Manufacturer’s name (trademark) and type, production year/week or batch number, and metre markings.

  • Special Properties: Tree-retardant insulation, light duty copper wire screening, lightweight aluminium conductor and compact single-core construction.

  • Available Cross-Sections: 16 mm² to 630 mm².

  • Installation Methods: Direct burial, underground ducts and suitable unenclosed installations.

Technical Data

The 3.8/6.6kV aluminium XLPE single-core light duty screened power cable features a rated voltage of 3800/6600V and a maximum operating temperature of 90°C. Its TR-XLPE insulation provides enhanced resistance to water tree formation, supporting long-term electrical insulation performance in underground power distribution applications.

Moreover, the compacted annealed aluminium conductor provides a lightweight and economical solution for medium voltage electrical power distribution. The light duty annealed copper wire screen features a specified minimum fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum coverage according to the applicable standard.

The listed conductor cross-sections range from 16 mm² to 630 mm², while the conductor diameter ranges from 4.9 mm to 29.9 mm.

Furthermore, the overall cable diameter ranges from 17.9 mm to 48.2 mm, and the approximate cable mass ranges from 380 kg/km to 2830 kg/km.

The maximum DC conductor resistance at 20°C ranges from 0.047 Ω/km to 1.910 Ω/km.

Constructive Data Table

Cross-section (mm²) Conductor No. of Strands Conductor Dia. (mm) Minimum Overall Dia. (mm) Maximum Overall Dia. (mm) Max. DC Resistance at 20°C (Ω/km) Approximate Mass (kg/km)
16 7 4.9 17.9 20.3 1.910 380
25 7 6.1 19.2 21.5 1.200 490
35 7 7.0 20.0 22.4 0.868 540
50 19 8.1 21.1 23.5 0.641 600
70 19 9.8 22.8 25.2 0.443 690
95 19 11.6 24.6 27.0 0.320 800
120 19 12.9 26.0 28.3 0.253 890
150 19 14.3 27.4 29.7 0.206 990
185 36 16.0 29.2 31.6 0.164 1140
240 36 18.4 31.8 34.2 0.125 1350
300 36 20.8 34.9 37.3 0.100 1600
400 58 23.5 38.2 40.7 0.078 2000
500 60 26.6 42.0 44.6 0.061 2400
630 60 29.9 45.6 48.2 0.047 2830

Technical note: All numerical table values and measurement units have been retained from the supplied datasheet. Light duty refers to the copper wire screen rather than mechanical protection. No armour is specified. The conductor strand counts, PVC/HDPE sheath configuration, applicable AS/NZS 1429.1 edition and screen fault current capacity should be verified before publishing. The suitability for systems with high phase-to-earth fault currents must also be assessed against the actual screen rating.

Factory Overview


Packaging & Shipping


Frequently Asked Questions and Answers

Q:- What is the primary application of the 3.8/6.6kV aluminium XLPE single-core light duty screened cable?

A:- It is designed for primary power supply in urban electrical distribution networks, industrial power installations and underground medium voltage power distribution systems.

Q:- What standard does the 3.8/6.6kV aluminium XLPE power cable follow?

A:- The manufacturer specifies AS/NZS 1429.1:2000 in the product datasheet, an Australian and New Zealand standard for polymeric insulated medium voltage power cables.

Q:- What is the rated voltage of the aluminium XLPE single-core light duty screened cable?

A:- The rated voltage is 3.8/6.6kV (3800/6600V), suitable for compatible 6.6kV medium voltage electrical distribution systems.

Q:- What is the maximum operating temperature of the aluminium XLPE power cable?

A:- The maximum operating temperature is 90°C, as specified in the manufacturer’s datasheet.

Q:- What type of conductor does the single-core aluminium power cable use?

A:- It uses a compacted annealed aluminium conductor, providing efficient electrical conductivity, reduced conductor weight and an economical solution for medium voltage power distribution applications.

Q:- What are the advantages of TR-XLPE insulation?

A:- TR-XLPE insulation provides enhanced resistance to water tree formation, helping reduce electrical insulation degradation and improve long-term reliability in underground power distribution applications.

Q:- What is the fault current rating of the light duty copper wire screen?

A:- The manufacturer specifies a minimum screen fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum screen coverage allowable under the applicable standard.

Q:- What is the difference between light duty and heavy duty screened power cables?

A:- Light duty screened power cables generally feature a smaller copper wire screen cross-section and lower earth fault current capacity than heavy duty screened cables. They can provide reduced cable weight and material costs where the screen fault current capacity meets the electrical system requirements.

Q:- What conductor cross-section sizes are available?

A:- The listed conductor cross-section sizes are 16 mm², 25 mm², 35 mm², 50 mm², 70 mm², 95 mm², 120 mm², 150 mm², 185 mm², 240 mm², 300 mm², 400 mm², 500 mm² and 630 mm².

Q:- Can the 3.8/6.6kV aluminium XLPE single-core light duty screened cable be installed directly underground?

A:- Yes, the manufacturer specifies suitability for direct burial and underground duct installations. However, appropriate mechanical protection, screen fault current capacity and compliance with applicable electrical installation requirements must be ensured.

Reviews

There are no reviews yet.

Be the first to review “3.8/6.6kV Aluminium XLPE Single-Core Light Duty Screened Power Cable – AS/NZS 1429.1”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS