3.8/6.6kV Copper XLPE 3-Core SWA Light Duty Screened Power Cable – AS/NZS 1429.1

The 3.8/6.6kV copper XLPE 3-core SWA light duty screened power cable provides dependable electrical connections for urban power distribution networks, industrial facilities and underground medium voltage power installations. It features compacted annealed copper conductors, TR-XLPE insulation, a light duty annealed copper wire screen, steel wire armour and a PVC or HDPE outer sheath.

Furthermore, it supports a rated voltage of 3.8/6.6kV and a maximum operating temperature of 90°C. The light duty copper wire screen features a specified minimum fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, subject to applicable standard requirements.

Application

The 3.8/6.6kV copper XLPE 3-core SWA light duty screened power cable is designed for primary power supply applications in urban electrical distribution networks, industrial facilities and underground medium voltage power distribution systems.

Furthermore, the compacted annealed copper conductors provide excellent electrical conductivity and low conductor resistance. The TR-XLPE (Tree-Retardant Cross-Linked Polyethylene) insulation provides enhanced resistance to water tree formation and electrical insulation degradation.

In addition, the light duty annealed copper wire screen provides a conductive path for earth fault currents, while the steel wire armour (SWA) provides additional mechanical protection against external forces. The PVC or HDPE outer sheath provides protection against environmental influences.

These cables are suitable for direct burial, underground duct installations, suitable unenclosed installations and installations requiring cable gland termination.

Cable Construction

  • Standard: AS/NZS 1429.1:2000.

  • Rated Voltage: 3.8/6.6kV (3800/6600V).

  • Conductor: Compacted annealed copper.

  • Insulation: TR-XLPE (Tree-Retardant Cross-Linked Polyethylene).

  • Core Identification: Numbered cores.

  • Number of Cores: 3-Core (3C).

  • Screen: Light duty annealed copper wire screen.

  • Armour: SWA (Steel Wire Armour).

  • Outer Sheath: PVC 5V-90 or HDPE.

  • Maximum Operating Temperature: 90°C.

  • Screen Fault Current Rating: Minimum 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum coverage allowable under the applicable standard.

  • Sheath Marking: Manufacturer’s name (trademark) and type, production year/week or batch number, and metre markings.

  • Special Properties: Tree-retardant insulation, light duty copper wire screening, steel wire armour, excellent electrical conductivity and additional mechanical protection.

  • Available Cross-Sections: 16 mm² to 300 mm² per core.

  • Installation Methods: Direct burial, underground ducts and suitable unenclosed installations.

Technical Data

The 3.8/6.6kV copper XLPE 3-core SWA light duty screened power cable features a rated voltage of 3800/6600V and a maximum operating temperature of 90°C. Its TR-XLPE insulation provides enhanced resistance to water tree formation, supporting long-term electrical insulation performance in underground power distribution applications.

Moreover, the compacted annealed copper conductors provide excellent electrical conductivity and low conductor resistance. The light duty annealed copper wire screen features a manufacturer-specified minimum fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum coverage according to the applicable standard.

In addition, the steel wire armour provides additional mechanical protection, making the cable suitable for demanding underground and industrial power distribution applications, subject to installation requirements.

The listed conductor cross-sections range from 16 mm² to 300 mm² per core, while the conductor diameter ranges from 4.9 mm to 20.8 mm.

Furthermore, the overall cable diameter ranges from 41.4 mm to 88.7 mm, and the approximate cable mass ranges from 2790 kg/km to 15910 kg/km, excluding the anomalous 50 mm² mass entry requiring confirmation.

The maximum DC conductor resistance at 20°C ranges from 0.0601 Ω/km to 1.150 Ω/km.

Constructive Data Table

Cross-section (mm²) Conductor No. of Strands Conductor Dia. (mm) Minimum Overall Dia. (mm) Maximum Overall Dia. (mm) Max. DC Resistance at 20°C (Ω/km) Approximate Mass (kg/km)
16 7 4.9 41.4 46.4 1.150 2790
25 7 6.0 44.1 49.1 0.727 3260
35 7 7.0 46.1 51.1 0.524 3690
50 19 8.1 50.3 55.4 0.387 4.71*
70 19 9.8 54.1 59.3 0.268 5630
95 19 11.4 57.8 63.0 0.193 6670
120 19 12.9 61.8 66.9 0.153 7750
150 19 14.3 65.0 70.2 0.124 8770
185 36 16.0 70.2 75.5 0.0991 11000
240 36 18.4 76.1 81.4 0.0754 13250
300 36 20.8 83.2 88.7 0.0601 15910

Technical note: All numerical table values and measurement units have been retained from the supplied datasheet. The approximate mass of the 50 mm² cable is listed as 4.71 kg/km, which appears to be a typographical or unit conversion error, possibly intended as 4710 kg/km. This value requires confirmation before publication. The armour wire diameter, bedding construction, screen cross-section and applicable AS/NZS 1429.1 edition should also be verified.

Factory Overview


Packaging & Shipping


Frequently Asked Questions and Answers

Q:- What is the primary application of the 3.8/6.6kV copper XLPE 3-core SWA light duty screened cable?

A:- It is designed for primary power supply in urban electrical distribution networks, industrial power installations and underground medium voltage distribution systems requiring additional mechanical protection.

Q:- What standard does the 3.8/6.6kV copper XLPE SWA power cable follow?

A:- The manufacturer specifies AS/NZS 1429.1:2000, an Australian and New Zealand standard for polymeric insulated medium voltage power cables.

Q:- What is the rated voltage of the copper XLPE 3-core SWA light duty screened cable?

A:- The rated voltage is 3.8/6.6kV (3800/6600V), suitable for compatible 6.6kV medium voltage electrical distribution systems.

Q:- What is the maximum operating temperature of the copper XLPE SWA power cable?

A:- The maximum operating temperature is 90°C, as specified in the manufacturer’s datasheet.

Q:- What type of conductor does the 3-core copper SWA power cable use?

A:- It uses compacted annealed copper conductors, providing excellent electrical conductivity, low conductor resistance and compact conductor construction.

Q:- What are the advantages of TR-XLPE insulation?

A:- TR-XLPE insulation provides enhanced resistance to water tree formation, helping reduce electrical insulation degradation and improve long-term reliability in underground power distribution applications.

Q:- What is the fault current rating of the light duty copper wire screen?

A:- The manufacturer specifies a minimum screen fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum screen coverage allowable under the applicable standard.

Q:- What is the purpose of steel wire armour in medium voltage power cables?

A:- Steel wire armour provides additional mechanical protection against external impact, compression and other mechanical stresses during installation and operation.

Q:- What is the difference between light duty and heavy duty screened SWA power cables?

A:- Light duty screened cables generally feature a smaller copper wire screen cross-section and lower earth fault current capacity than heavy duty screened cables. Both can incorporate steel wire armour for mechanical protection. The appropriate screen configuration depends on the electrical system’s fault current requirements.

Q:- Can the 3.8/6.6kV copper XLPE 3-core SWA light duty screened cable be installed directly underground?

A:- Yes, the manufacturer specifies suitability for direct burial and underground duct installations. The steel wire armour provides additional mechanical protection, subject to applicable electrical installation requirements and environmental conditions.