3.8/6.6kV Copper XLPE Single-Core Heavy Duty Screened Power Cable – AS/NZS 1429.1
The 3.8/6.6kV copper XLPE single-core heavy duty screened power cable provides dependable electrical connections for urban power distribution networks, industrial facilities and underground medium voltage power installations. It features a compacted annealed copper conductor, natural TR-XLPE insulation, a heavy duty annealed copper wire screen and a PVC or PVC/HDPE outer sheath.
Application
The 3.8/6.6kV copper XLPE single-core heavy duty screened power cable is designed for primary power supply applications in urban electrical distribution networks, industrial facilities and underground medium voltage power distribution systems, particularly in systems with high phase-to-earth fault current levels.
Furthermore, the compacted annealed copper conductor provides excellent electrical conductivity and low conductor resistance. The natural TR-XLPE (Tree-Retardant Cross-Linked Polyethylene) insulation provides enhanced resistance to water tree formation and electrical insulation degradation.
In addition, the heavy duty annealed copper wire screen provides a conductive path for earth fault currents, while the PVC or PVC/HDPE outer sheath provides protection against environmental influences.
These cables are suitable for direct burial, underground duct installations, unenclosed installations where they are not subject to mechanical damage, and installations requiring cable gland termination.
Cable Construction
-
Standard: AS/NZS 1429.1:2000.
-
Rated Voltage: 3.8/6.6kV (3800/6600V).
-
Conductor: Compacted annealed copper.
-
Insulation: Natural TR-XLPE (Tree-Retardant Cross-Linked Polyethylene).
-
Number of Cores: Single-Core (1C).
-
Screen: Heavy duty annealed copper wire screen.
-
Outer Sheath: PVC 5V-90 or PVC 5V-90/HDPE.
-
Maximum Operating Temperature: 90°C.
-
Screen Fault Current Rating: Minimum 13.1kA for 1 second, without exceeding the conductor rating.
-
Sheath Marking: Manufacturer’s name (trademark) and type, production year/week or batch number, and metre markings.
-
Special Properties: Tree-retardant insulation, heavy duty copper wire screening, excellent electrical conductivity and compact single-core construction.
-
Available Cross-Sections: 16 mm² to 630 mm².
-
Installation Methods: Direct burial, underground ducts and suitable unenclosed installations.
Technical Data
The 3.8/6.6kV copper XLPE single-core heavy duty screened power cable features a rated voltage of 3800/6600V and a maximum operating temperature of 90°C. Its natural TR-XLPE insulation provides enhanced resistance to water tree formation, supporting long-term electrical insulation performance in underground power distribution applications.
Moreover, the compacted annealed copper conductor provides excellent electrical conductivity and low conductor resistance. The heavy duty annealed copper wire screen features a manufacturer-specified minimum fault current rating of 13.1kA for 1 second, without exceeding the conductor rating.
The listed conductor cross-sections range from 16 mm² to 630 mm², while the conductor diameter ranges from 4.9 mm to 32.7 mm.
Furthermore, the overall cable diameter ranges from 17.9 mm to 52.5 mm, and the approximate cable mass ranges from 530 kg/km to 7700 kg/km.
The maximum DC conductor resistance at 20°C ranges from 0.028 Ω/km to 1.150 Ω/km.
Constructive Data Table
| Cross-section (mm²) | Conductor No. of Strands | Conductor Dia. (mm) | Minimum Overall Dia. (mm) | Maximum Overall Dia. (mm) | Max. DC Resistance at 20°C (Ω/km) | Approximate Mass (kg/km) |
|---|---|---|---|---|---|---|
| 16 | 7 | 4.9 | 17.9 | 20.3 | 1.150 | 530 |
| 25 | 7 | 6.0 | 19.1 | 21.4 | 0.727 | 710 |
| 35 | 7 | 7.0 | 20.4 | 22.7 | 0.524 | 1000 |
| 50 | 19 | 8.1 | 22.5 | 24.8 | 0.387 | 1200 |
| 70 | 19 | 9.8 | 24.2 | 26.5 | 0.268 | 1600 |
| 95 | 19 | 11.4 | 26.5 | 28.9 | 0.193 | 2100 |
| 120 | 19 | 12.9 | 28.0 | 30.4 | 0.153 | 2300 |
| 150 | 19 | 14.3 | 28.7 | 31.1 | 0.124 | 2600 |
| 185 | 37 | 16.0 | 30.6 | 32.9 | 0.099 | 3000 |
| 240 | 37 | 18.4 | 33.4 | 35.8 | 0.075 | 3600 |
| 300 | 37 | 20.8 | 36.4 | 38.9 | 0.060 | 4200 |
| 400 | 59 | 23.5 | 39.7 | 42.3 | 0.047 | 5100 |
| 500 | 61 | 26.6 | 43.4 | 46.0 | 0.037 | 6100 |
| 630 | 91 | 32.7 | 49.5 | 52.5 | 0.028 | 7700 |
Technical note: All numerical table values and measurement units have been retained from the supplied datasheet. Heavy duty refers to the copper wire screen rather than mechanical protection or steel wire armour. No armour is specified. The applicable AS/NZS 1429.1 edition, screen cross-section, sheath configuration and actual screen fault current capacity for each conductor size should be verified before publication.
Factory Overview
Packaging & Shipping
Frequently Asked Questions and Answers
Q:- What is the primary application of the 3.8/6.6kV copper XLPE single-core heavy duty screened cable?
A:- It is designed for primary power supply in urban electrical distribution networks, industrial power installations and underground medium voltage distribution systems, particularly systems with high phase-to-earth fault current requirements.
Q:- What standard does the 3.8/6.6kV copper XLPE power cable follow?
A:- The manufacturer specifies AS/NZS 1429.1:2000 in the product datasheet, an Australian and New Zealand standard for polymeric insulated medium voltage power cables.
Q:- What is the rated voltage of the copper XLPE single-core heavy duty screened cable?
A:- The rated voltage is 3.8/6.6kV (3800/6600V), suitable for compatible 6.6kV medium voltage electrical distribution systems.
Q:- What is the maximum operating temperature of the copper XLPE power cable?
A:- The maximum operating temperature is 90°C, as specified in the manufacturer’s datasheet.
Q:- What type of conductor does the single-core copper power cable use?
A:- It uses a compacted annealed copper conductor, providing excellent electrical conductivity, low conductor resistance and compact conductor construction.
Q:- What are the advantages of natural TR-XLPE insulation?
A:- Natural TR-XLPE insulation provides enhanced resistance to water tree formation, helping reduce electrical insulation degradation and improve long-term reliability in underground power distribution applications.
Q:- What is the fault current rating of the heavy duty copper wire screen?
A:- The manufacturer specifies a minimum screen fault current rating of 13.1kA for 1 second, provided that it does not exceed the conductor rating. The actual fault current capacity must be confirmed for the selected cable construction.
Q:- What is the difference between heavy duty and light duty screened power cables?
A:- Heavy duty screened power cables generally feature a larger copper wire screen cross-section and higher earth fault current capacity than light duty screened cables, making them suitable for electrical systems with higher phase-to-earth fault current requirements.
Q:- What conductor cross-section sizes are available?
A:- The listed conductor cross-section sizes are 16 mm², 25 mm², 35 mm², 50 mm², 70 mm², 95 mm², 120 mm², 150 mm², 185 mm², 240 mm², 300 mm², 400 mm², 500 mm² and 630 mm².
Q:- Can the 3.8/6.6kV copper XLPE single-core heavy duty screened cable be installed directly underground?
A:- Yes, the manufacturer specifies suitability for direct burial and underground duct installations. However, appropriate mechanical protection, screen fault current capacity and compliance with applicable electrical installation requirements must be ensured.




Reviews