SAVVn/A 0.6/1 kV Aluminum Flame Retardant Power Cable – FN KI 02.001-96

The SAVVn/A 0.6/1 kV cable delivers dependable power distribution for industrial and commercial installations. Constructed with aluminum conductors, PVC insulation, a flame retardant filling, and a black flame retardant PVC outer sheath, it offers exceptional fire safety. Because it meets FN KI 02.001-96 standards, passes the BDS IEC 332-3/C2 Category A flame test, and is RoHS compliant, it provides a safe and reliable solution for environments requiring non-proliferation of flames.

Application
SAVVn/A cables provide reliable power transfer and distribution in networks with a nominal voltage of Uo/U 0.6/1 kV and a frequency of 50 Hz. Because they feature aluminum conductors and flame retardant materials, installers use them in surroundings that require non-proliferation of flames. Furthermore, they ensure safety in industrial and commercial installations where fire risk is a concern. Consequently, they deliver consistent performance and safety in demanding environments.

Cable construction
This cable strictly adheres to FN KI 02.001-96 standards. It features aluminum solid or twisted wires (class 1 or 2) that comply with BDS 904-84. The insulation uses a PVC compound according to BDS 5792-84. A filling with flame retardant properties forms the inner sheath. Finally, a black PVC flame retardant outer sheath of flame retardancy category A protects the entire assembly. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance according to BDS 904-84. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of 4 kV (alternating) and 12 kV (direct). The temperature range for laying and installing is -5 °C, while the exploitation and storage range is -30 °C to +50 °C. The operating temperature reaches +70 °C. The short circuit temperature is +160 °C for no more than 5 seconds. Installers must respect a minimum bending radius of 10 times the cable diameter. Furthermore, it passes the flame retardant test according to BDS IEC 332-3/C2, Category A.

Color coding
Clear color coding ensures safe and accurate wiring. Conductors without a yellow/green earth core feature random colors for 1 core, brown and blue for 2 cores, brown, black, and blue for 3 cores, blue, brown, black, and grey for 4 cores, and blue, brown, black, grey, and black for 5 cores. Conductors with a yellow/green earth core feature yellow/green, blue, and brown for 3 cores, yellow/green, brown, black, and grey for 4 cores, and yellow/green, blue, brown, black, and grey for 5 cores. The neutral conductor is always blue.

Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data SAVVn/A 0.6/1 kV

Number of wires and nominal cross-section Form of conductor Cable diameter approx. Mass of Al Mass of cable approx.
N x mm² mm kg/km kg/km
1 x 2,5 re 7,5 7 72
1 x 4 re 8,4 12 93
1 x 6 re 9,1 17 107
1 x 10 re 10,0 28 152
1 x 16 re 10,6 45 158
1 x 25 re 12,2 68 210
1 x 35 re 13,2 95 252
1 x 50 re 14,6 127 305
1 x 70 re 17,4 190 330
1 x 95 re 18,4 260 405
1 x 120 re 19,9 341 525
1 x 150 re 22,8 405 682
1 x 185 re 24,7 510 755
1 x 240 re 26,7 665 822
1 x 300 re 30,1 830 1332
1 x 400 re 33,5 1060 1742
1 x 500 re 37,9 1332 2148
2 x 1,5 re 9,9 14 92
2 x 2,5 re 10,9 23 118
2 x 4 re 11,5 35 142
2 x 6 re 14,9 56 293
2 x 10 re 16,5 90 307
2 x 16 re 17,4 157 457
2 x 25 re 22,4 210 550
2 x 35 re 25,4 290 683
2 x 50 re 25,9 385 882
2 x 70 re 27,8 510 1160
2 x 95 re 37,9 520 1995
3 x 1,5 re 13,5 21 240
3 x 2,5 re 14,1 35 274
3 x 4 re 15,1 51 319
3 x 6 re 17,0 90 383
3 x 10 re 18,5 135 465
3 x 16 re 20,2 210 582
3 x 25 re 25,1 270 783
3 x 35 rm 25,8 290 966
3 x 50 rm 29,2 385 1240
3 x 70 rm 32,0 560 1761
3 x 95 rm 40,4 720 2295
3 x 120 sm 37,7 1035 2059
3 x 150 sm 43,2 1035 2765
3 x 185 sm 45,8 1560 3107
3 x 240 sm 51,2 2035 3605
3 x 300 sm 57,5 2385 4602
3 x 4 + 4 re/re 17,9 63 425
3 x 10 + 6 re/re 19,4 101 510
3 x 16 + 10 re/re 21,5 165 645
3 x 25 + 16 rm/re 24,9 255 800
3 x 35 + 16 rm/rm 28,0 355 878
3 x 50 + 25 rm/rm 30,5 480 1374
3 x 70 + 35 sm/rm 32,6 485 1475
3 x 95 + 50 sm/rm 35,6 600 1450
3 x 120 + 70 sm/rm 41,9 860 1999
3 x 150 + 70 sm/rm 41,0 1060 2389
3 x 185 + 95 sm/rm 43,2 1275 2907
3 x 240 + 120 sm/rm 50,9 1740 3298
3 x 300 + 150 sm/rm 64,3 1625 4225
4 x 2,5 re 14,4 28 265
4 x 4 re 15,2 46 301
4 x 6 re 17,6 92 409
4 x 10 re 19,8 112 512
4 x 16 rm 24,9 180 683
4 x 25 rm 25,8 280 944
4 x 35 rm 28,2 320 1537
4 x 50 rm 33,0 520 2110
4 x 70 rm 39,1 760 2134
4 x 95 rm 45,5 1060 2801
4 x 120 sm 46,7 1340 3217
4 x 150 sm 47,5 1590 4183
4 x 185 sm 48,0 1682 4738
4 x 240 sm 48,1 2050 6142
4 x 300 sm 53,7 2100 6135
5 x 1,5 re 16,4 35 428
5 x 2,5 re 16,9 54 473
5 x 4 re 18,1 77 559
5 x 6 re 21,4 140 620
5 x 10 re 23,7 140 750
5 x 16 rm 24,0 225 795
5 x 25 rm 30,5 350 1657
5 x 35 rm 33,0 350 1952
5 x 50 rm 38,1 421 1983
5 x 70 rm 50,0 800 3265
5 x 95 rm 49,8 1345 3497

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the SAVVn/A cable?
A:- It is used for the transfer and distribution of electrical power in networks with a nominal voltage of 0.6/1 kV, specifically in surroundings requiring non-proliferation of flames.

Q:- What are the key fire safety features of this cable?
A:- It features a flame retardant filling and a black PVC flame retardant outer sheath (Category A), passing the BDS IEC 332-3/C2 flame test.

Q:- What standards does the cable construction follow?
A:- The construction adheres to FN KI 02.001-96 standards, and the conductor complies with BDS 904-84.

Q:- What type of conductor and insulation does it use?
A:- It uses aluminum solid or twisted wires (class 1 or 2) with a PVC compound insulation according to BDS 5792-84.

Q:- What is the temperature range for this cable?
A:- The temperature range for laying and installing is -5°C, while the exploitation and storage range is -30°C to +50°C.

Q:- What is the maximum operating and short-circuit temperature?
A:- The operating temperature is +70°C, and the short-circuit temperature is +160°C for no more than 5 seconds.

Q:- What is the test voltage for this cable?
A:- The test voltage is 4 kV (alternating) and 12 kV (direct).

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter (10 x D cable).

Q:- What is the neutral conductor color?
A:- The neutral conductor is always blue.

Q:- Is this cable RoHS compliant?
A:- Yes, the product is RoHS compliant.

Reviews

There are no reviews yet.

Be the first to review “SAVVn/A 0.6/1 kV Aluminum Flame Retardant Power Cable – FN KI 02.001-96”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS