SVVn/C 0.6/1 kV Flame Retardant Power Cable – FN KI 02.001-2006
The SVVn/C 0.6/1 kV cable delivers dependable power distribution for industrial and commercial installations. Constructed with copper conductors, PVC insulation, and a black flame retardant PVC outer sheath, it offers exceptional fire safety. Because it meets FN KI 02.001-96 standards, passes the BDS IEC 332-3/C2 Category C flame test, and is RoHS compliant, it provides a safe and reliable solution for environments requiring non-proliferation of flames.
Application
SVVn/C cables provide reliable power transfer and distribution in networks with a nominal voltage of Uo/U 0.6/1 kV and a frequency of 50 Hz. Because they feature flame retardant materials, installers use them in surroundings that require non-proliferation of flames. Furthermore, they ensure safety in industrial and commercial installations where fire risk is a concern. Consequently, they deliver consistent performance and safety in demanding environments.
Cable construction
This cable strictly adheres to FN KI 02.001-96 standards. It features copper solid or twisted wires (class 1 or 2) that comply with BDS 904-84 (IEC 60228). The insulation uses a PVC compound according to BDS 5782-84. Finally, a black PVC flame retardant outer sheath of flame retardancy category C protects the entire assembly. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance according to BDS 904-84. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of 4 kV (alternating) and 12 kV (direct). The temperature range for laying and installing is -5 °C, while the exploitation and storage range is -30 °C to +50 °C. The operating temperature reaches +70 °C. The short circuit temperature is +160 °C for no more than 5 seconds. Installers must respect a minimum bending radius of 10 times the cable diameter. Furthermore, it passes the flame retardant test according to BDS IEC 332-3/C2, Category C.
Color coding
Clear color coding ensures safe and accurate wiring. Conductors without a yellow/green earth core feature random colors for 1 core, light blue and brown for 2 cores, brown, black, and grey for 3 cores, and blue, brown, black, and grey for 4 cores. Conductors with a yellow/green earth core feature yellow/green, blue, and brown for 3 cores, and yellow/green, brown, black, and grey for 4 cores. The neutral conductor is always blue.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data SVVn/C 0.6/1 kV
| Number of wires and nominal cross-section | Form of conductor | Cable diameter approx. | Mass of Cu | Mass of cable approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 1 x 1,5 | re | 7,2 | 14 | 69 |
| 1 x 2,5 | re | 7,6 | 23 | 82 |
| 1 x 4 | re | 8,0 | 37 | 102 |
| 1 x 6 | re | 8,7 | 55 | 128 |
| 1 x 10 | re | 9,3 | 93 | 178 |
| 1 x 16 | re | 10,8 | 148 | 253 |
| 1 x 25 | rm | 11,9 | 229 | 350 |
| 1 x 35 | rm | 13,0 | 322 | 462 |
| 1 x 50 | rm | 15,0 | 456 | 608 |
| 1 x 70 | rm | 16,7 | 648 | 810 |
| 1 x 95 | rm | 18,4 | 885 | 1100 |
| 1 x 120 | rm | 19,9 | 1120 | 1325 |
| 1 x 150 | rm | 21,9 | 1378 | 1610 |
| 1 x 185 | rm | 24,3 | 1703 | 2010 |
| 1 x 240 | rm | 27,2 | 2208 | 2565 |
| 1 x 300 | rm | 30,3 | 2765 | 3200 |
| 1 x 400 | rm | 37,9 | 4600 | 5180 |
| 2 x 1,5 | re | 9,3 | 28 | 100 |
| 2 x 2,5 | re | 10,0 | 46 | 130 |
| 2 x 4 | re | 10,6 | 75 | 150 |
| 2 x 6 | re | 12,1 | 112 | 210 |
| 2 x 10 | re | 15,2 | 182 | 370 |
| 2 x 16 | rm | 17,8 | 303 | 500 |
| 2 x 25 | rm | 23,8 | 485 | 1057 |
| 2 x 35 | rm | 27,9 | 652 | 1408 |
| 2 x 70 | rm | 27,0 | 928 | 1406 |
| 3 x 1,5 | re | 10,2 | 42 | 122 |
| 3 x 2,5 | re | 11,0 | 69 | 154 |
| 3 x 4 | re | 12,8 | 110 | 210 |
| 3 x 6 | re | 14,0 | 165 | 260 |
| 3 x 10 | re | 16,0 | 275 | 480 |
| 3 x 16 | rm | 18,9 | 450 | 682 |
| 3 x 25 | rm | 22,8 | 700 | 1070 |
| 3 x 35 | rm | 25,3 | 980 | 1298 |
| 3 x 50 | rm | 28,9 | 1390 | 1895 |
| 3 x 70 | sm | 28,8 | 1850 | 2400 |
| 3 x 95 | sm | 33,1 | 2650 | 3255 |
| 3 x 120 | sm | 35,9 | 3350 | 4010 |
| 3 x 150 | sm | 39,3 | 4185 | 4830 |
| 3 x 185 | sm | 43,3 | 5160 | 6035 |
| 3 x 1,5 + 1,5 | re/re | 11,2 | 56 | 140 |
| 3 x 2,5 + 1,5 | re/re | 13,2 | 76 | 205 |
| 3 x 4,0 + 2,5 | re/re | 13,4 | 132 | 293 |
| 3 x 6,0 + 4,0 | re/re | 14,4 | 202 | 380 |
| 3 x 10 + 6,0 | re/re | 16,7 | 330 | 545 |
| 3 x 16 + 10 | rm/re | 19,9 | 580 | 810 |
| 3 x 25 + 16 | rm/re | 24,5 | 850 | 1245 |
| 3 x 35 + 16 | rm/rm | 27,1 | 1130 | 1590 |
| 3 x 50 + 25 | sm/rm | 30,8 | 1680 | 2175 |
| 3 x 70 + 35 | sm/rm | 34,9 | 2280 | 2785 |
| 3 x 95 + 50 | sm/rm | 36,8 | 3120 | 3680 |
| 3 x 120 + 70 | sm/rm | 41,9 | 4060 | 5090 |
| 3 x 150 + 70 | sm/rm | 44,3 | 4850 | 5620 |
| 3 x 185 + 95 | sm/rm | 49,3 | 6070 | 7090 |
| 3 x 240 + 120 | sm/rm | 55,4 | 7840 | 9150 |
| 4 x 1,5 | re | 11,0 | 55 | 165 |
| 4 x 2,5 | re | 11,9 | 92 | 215 |
| 4 x 4 | re | 13,6 | 146 | 218 |
| 4 x 6 | re | 15,1 | 216 | 375 |
| 4 x 10 | re | 18,4 | 363 | 583 |
| 4 x 16 | rm | 20,5 | 595 | 951 |
| 4 x 25 | rm | 25,0 | 970 | 1385 |
| 4 x 35 | rm | 28,0 | 1325 | 1737 |
| 4 x 50 | sm | 32,0 | 1857 | 2007 |
| 4 x 70 | sm | 33,0 | 2307 | 3101 |
| 4 x 95 | sm | 41,2 | 4460 | 5210 |
| 4 x 120 | sm | 45,2 | 5575 | 6385 |
| 4 x 150 | sm | 45,2 | 5855 | 7620 |
| 4 x 185 | sm | 55,6 | 6790 | 9800 |
| 4 x 240 | sm | 56,4 | 8928 | 10310 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the SVVn/C cable?
A:- It is used for the transfer and distribution of electrical power in networks with a nominal voltage of 0.6/1 kV, specifically in surroundings requiring non-proliferation of flames.
Q:- What are the key fire safety features of this cable?
A:- It features a black PVC flame retardant outer sheath (Category C), passing the BDS IEC 332-3/C2 flame test.
Q:- What standards does the cable construction follow?
A:- The construction adheres to FN KI 02.001-96 standards, and the conductor complies with BDS 904-84 (IEC 60228).
Q:- What type of conductor and insulation does it use?
A:- It uses copper solid or twisted wires (class 1 or 2) with a PVC compound insulation according to BDS 5782-84.
Q:- What is the temperature range for this cable?
A:- The temperature range for laying and installing is -5°C, while the exploitation and storage range is -30°C to +50°C.
Q:- What is the maximum operating and short-circuit temperature?
A:- The operating temperature is +70°C, and the short-circuit temperature is +160°C for no more than 5 seconds.
Q:- What is the test voltage for this cable?
A:- The test voltage is 4 kV (alternating) and 12 kV (direct).
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter (10 x D cable).
Q:- What is the neutral conductor color?
A:- The neutral conductor is always blue.
Q:- Is this cable RoHS compliant?
A:- Yes, the product is RoHS compliant.




Reviews