SvHEk(v)P / SAvHEk(v)P 6/10 kV to 12/20 kV Water-Resistant XLPE Insulated Copper & Aluminium Conductor Power Cable – BDS 2581-86
SvHEk(v)P and SAvHEk(v)P are water-resistant medium voltage power cables designed for reliable electrical power transmission and distribution in urban networks, transformer substations, and industrial installations. Manufactured according to BDS 2581-86 and Additional 4, these cables feature stranded and compacted copper or aluminium conductors, XLPE insulation, semiconductive conductor and insulation screens, longitudinal water-blocking elements, concentric copper wire screening, and an aluminium foil radial moisture barrier with a copolymer layer. Finished with a protective black PE Type MDPE outer sheath, they are suitable for underground installations, cable ducts, conduits, and industrial power distribution systems.
Application
SvHEk(v)P and SAvHEk(v)P single-core cables with cross-linked polyethylene (XLPE) insulation and longitudinal water-blocking elements are designed for the transfer and distribution of electrical power at nominal voltages of 6/10 kV and 12/20 kV, with a frequency of 50 Hz.
They are mainly used in urban and district electrical networks, transformer substations, small and medium industrial plants, distribution installations, electric power stations, and industrial systems.
These cables are suitable for fixed installation in lines with unlimited differences in level, indoor installations, cable ducts, conduits, shafts, and underground installations in ditches, as well as outdoor installations under shelters.
Cable Construction
Manufactured according to BDS 2581-86 and Additional 4.
-
Conductor: Copper or aluminium stranded and compacted conductor, according to BDS 904 (IEC 60228), Class 2.
-
Water-resistant element: Water-absorbing powder.
-
Inner semiconductive layer: Semiconductive XLPE compound.
-
Insulation: XLPE (Cross-Linked Polyethylene) compound.
-
Outer semiconductive layer: Semiconductive XLPE compound.
-
Water-resistant element: Layer of semiconductive water-absorbing tapes.
-
Metal screen: Copper wires concentrically laid with one contact copper tape of 0.1 mm thickness.
-
Additional water-resistant element: Water-absorbing powder.
-
Radial protection from moisture ingress: Aluminium foil with copolymer layer.
-
Outer sheath: PE compound, Type MDPE.
-
Outer sheath colour: Black.
-
Compliance: RoHS compliant.
Cable Type Identification
| Cable designation | Conductor material |
|---|---|
| SvHEk(v)P | Copper |
| SAvHEk(v)P | Aluminium |
Technical Data
| Parameter | Specification |
|---|---|
| Applicable standard | BDS 2581-86 + Additional 4 |
| Conductor standard | BDS 904 (IEC 60228), Class 2 |
| Conductor material | Copper / Aluminium |
| Conductor resistance at 20°C | According to BDS 904 (IEC 60228), Class 2 |
| Continuous operating temperature | +90°C |
| Maximum overload temperature | +130°C / 100 hours per year maximum |
| Maximum short-circuit temperature | +250°C / 5 seconds maximum |
| Nominal voltage (Uo/U) | 6/10 kV; 12/20 kV |
| Highest system voltage (U) | 12 kV; 24 kV |
| AC test voltage | 15 kV; 30 kV |
| AC test duration | 5 minutes |
| DC test voltage | 48 kV; 98 kV |
| DC test duration | 15 minutes |
| Partial discharge at 2 × Uo | Maximum 5 pC |
| Minimum bending radius | 15 × D (cable diameter) |
| Minimum laying temperature | Not less than -20°C |
| Operating temperature range | -30°C to +50°C |
| Maximum pulling force during laying | Aluminium: 30 N/mm²; Copper: 50 N/mm² |
| Water penetration test | IEC 60502-2 Annex D |
Conductor Construction Identification
| Component | Description |
|---|---|
| Conductor material | Copper or aluminium |
| Conductor construction | Stranded and compacted |
| Conductor class | Class 2 |
| Inner conductor screen | Semiconductive XLPE |
| Insulation | XLPE |
| Outer insulation screen | Semiconductive XLPE |
| Water-blocking layer | Water-absorbing powder and semiconductive water-absorbing tapes |
| Metallic screen | Copper wires and 0.1 mm contact copper tape |
| Radial moisture barrier | Aluminium foil with copolymer layer |
| Outer sheath | PE Type MDPE |
| Outer sheath colour | Black |
Colour Coding
-
Outer sheath colour: Black.
-
Individual core insulation colour coding is not specified in the supplied product catalogue.
3. Construction Data Tables
All dimensions are in mm and all material and cable weights are in kg/km.
Column identification:
-
Ins. = Insulation thickness
-
Sheath = Outer sheath thickness
-
Screen = Nominal copper screen cross-section
-
Dia. = Approximate cable diameter
-
Cu = Copper weight
-
Al = Aluminium weight
-
Cable = Approximate total cable weight
Construction Data – 3.6/6 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SvHEk Cu | SvHEk Cable | SAvHEk Al | SAvHEk Cu | SAvHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 2.5 | 2.5 | 16 | 22 | 490 | 795 | 95 | 176 | 570 |
| 1×50rm/16 | 2.5 | 2.5 | 16 | 23 | 600 | 930 | 130 | 176 | 625 |
| 1×70rm/16 | 2.5 | 2.5 | 16 | 25 | 790 | 1155 | 190 | 176 | 720 |
| 1×95rm/16 | 2.5 | 2.5 | 16 | 26.5 | 1030 | 1430 | 260 | 176 | 825 |
| 1×120rm/16 | 2.5 | 2.5 | 16 | 28 | 1255 | 1690 | 330 | 176 | 935 |
| 1×150rm/16* | 2.5 | 2.5 | 16* | 29.5 | 1505 | 1980 | 405 | 176 | 1040 |
| 1×185rm/16* | 2.5 | 2.5 | 16* | 31.5 | 1840 | 2360 | 510 | 176 | 1190 |
| 1×240rm/16* | 2.5 | 2.5 | 16* | 33.5 | 2365 | 2950 | 665 | 176 | 1415 |
| 1×150rm/25 | 2.5 | 2.5 | 25 | 30 | 1595 | 2060 | 405 | 265 | 1120 |
| 1×185rm/25 | 2.5 | 2.5 | 25 | 32 | 1930 | 2440 | 510 | 265 | 1270 |
| 1×240rm/25 | 2.6 | 2.5 | 25 | 34 | 2450 | 3040 | 665 | 265 | 1500 |
| 1×300rm/25 | 2.8 | 2.5 | 25 | 37 | 2980 | 3650 | 830 | 265 | 1745 |
| 1×400rm/35 | 3.0 | 2.5 | 35 | 41 | 3835 | 4610 | 1060 | 363 | 2180 |
| 1×500rm/35 | 3.2 | 2.5 | 35 | 45 | 4805 | 5990 | 1410 | 363 | 2560 |
Construction Data – 6/10 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SvHEk Cu | SvHEk Cable | SAvHEk Al | SAvHEk Cu | SAvHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 3.4 | 2.5 | 16 | 24 | 490 | 905 | 95 | 176 | 670 |
| 1×50rm/16 | 3.4 | 2.5 | 16 | 25 | 600 | 1045 | 130 | 176 | 745 |
| 1×70rm/16 | 3.4 | 2.5 | 16 | 27 | 790 | 1275 | 190 | 176 | 845 |
| 1×95rm/16 | 3.4 | 2.5 | 16 | 29 | 1030 | 1560 | 260 | 176 | 950 |
| 1×120rm/16 | 3.4 | 2.5 | 16 | 31 | 1255 | 1820 | 330 | 176 | 1080 |
| 1×150rm/16* | 3.4 | 2.5 | 16* | 32 | 1505 | 2115 | 405 | 176 | 1180 |
| 1×185rm/16* | 3.4 | 2.5 | 16* | 34 | 1840 | 2490 | 510 | 176 | 1325 |
| 1×240rm/16* | 3.4 | 2.5 | 16* | 36 | 2365 | 3080 | 665 | 176 | 1540 |
| 1×150rm/25 | 3.4 | 2.5 | 25 | 32 | 1595 | 2200 | 405 | 265 | 1260 |
| 1×185rm/25 | 3.4 | 2.5 | 25 | 34 | 1930 | 2570 | 510 | 265 | 1405 |
| 1×240rm/25 | 3.4 | 2.5 | 25 | 36 | 2450 | 3160 | 665 | 265 | 1625 |
| 1×300rm/25 | 3.4 | 2.5 | 25 | 38.5 | 2980 | 3750 | 830 | 265 | 1850 |
| 1×400rm/35 | 3.4 | 2.5 | 35 | 42 | 3835 | 4680 | 1060 | 363 | 2250 |
| 1×500rm/35 | 3.4 | 2.5 | 35 | 45 | 4805 | 5720 | 1410 | 363 | 2600 |
Construction Data – 12/20 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SvHEk Cu | SvHEk Cable | SAvHEk Al | SAvHEk Cu | SAvHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×35rm/16 | 5.5 | 2.5 | 16 | 28 | 490 | 1080 | 95 | 176 | 855 |
| 1×50rm/16 | 5.5 | 2.5 | 16 | 29 | 600 | 1225 | 130 | 176 | 925 |
| 1×70rm/16 | 5.5 | 2.5 | 16 | 31 | 790 | 1470 | 190 | 176 | 1040 |
| 1×95rm/16 | 5.5 | 2.5 | 16 | 33 | 1030 | 1760 | 260 | 176 | 1165 |
| 1×120rm/16 | 5.5 | 2.5 | 16 | 34 | 1255 | 1950 | 330 | 176 | 1195 |
| 1×150rm/16* | 5.5 | 2.5 | 16* | 36 | 1505 | 2340 | 405 | 176 | 1400 |
| 1×185rm/16* | 5.5 | 2.5 | 16* | 37.5 | 1840 | 2730 | 510 | 176 | 1560 |
| 1×240rm/16* | 5.5 | 2.5 | 16* | 40 | 2365 | 3400 | 665 | 176 | 1875 |
| 1×150rm/25 | 5.5 | 2.5 | 25 | 36 | 1595 | 2420 | 405 | 265 | 1500 |
| 1×185rm/25 | 5.5 | 2.5 | 25 | 38 | 1930 | 2810 | 510 | 265 | 1640 |
| 1×240rm/25 | 5.5 | 2.5 | 25 | 40.5 | 2450 | 3400 | 665 | 265 | 1875 |
| 1×300rm/25 | 5.5 | 2.5 | 25 | 42.5 | 2980 | 4010 | 830 | 265 | 2110 |
| 1×400rm/35 | 5.5 | 2.5 | 35 | 46 | 3835 | 4950 | 1060 | 363 | 2535 |
| 1×500rm/35 | 5.5 | 2.5 | 35 | 49 | 4805 | 6050 | 1410 | 363 | 2920 |
Construction Data – 18/30 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SvHEk Cu | SvHEk Cable | SAvHEk Al | SAvHEk Cu | SAvHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×50rm/16 | 8.0 | 2.5 | 16 | 35.5 | 600 | 1460 | 130 | 176 | 1160 |
| 1×70rm/16 | 8.0 | 2.5 | 16 | 36.5 | 790 | 1720 | 190 | 176 | 1285 |
| 1×95rm/16 | 8.0 | 2.5 | 16 | 37.5 | 1030 | 2030 | 260 | 176 | 1425 |
| 1×120rm/16 | 8.0 | 2.5 | 16 | 39.5 | 1255 | 2305 | 330 | 176 | 1550 |
| 1×150rm/25 | 8.0 | 2.5 | 25 | 41 | 1595 | 2705 | 405 | 265 | 1770 |
| 1×185rm/25 | 8.0 | 2.5 | 25 | 43 | 1930 | 3105 | 510 | 265 | 1935 |
| 1×240rm/25 | 8.0 | 2.5 | 25 | 45 | 2450 | 3725 | 665 | 265 | 2185 |
| 1×300rm/25 | 8.0 | 2.5 | 25 | 48 | 2980 | 4360 | 830 | 265 | 2455 |
| 1×400rm/35 | 8.0 | 2.5 | 35 | 51.5 | 3835 | 5345 | 1060 | 363 | 2915 |
| 1×500rm/35 | 8.0 | 2.5 | 35 | 55 | 4805 | 6480 | 1410 | 363 | 3340 |
Construction Data – 20/35 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SvHEk Cu | SvHEk Cable | SAvHEk Al | SAvHEk Cu | SAvHEk Cable |
|---|---|---|---|---|---|---|---|---|---|
| 1×50rm/16 | 8.8 | 2.5 | 16 | 36.5 | 600 | 1480 | 130 | 176 | 1185 |
| 1×70rm/16 | 8.8 | 2.5 | 16 | 38 | 790 | 1750 | 190 | 176 | 1320 |
| 1×95rm/16 | 8.8 | 2.5 | 16 | 40 | 1030 | 2065 | 260 | 176 | 1460 |
| 1×120rm/16 | 8.8 | 2.5 | 16 | 42 | 1255 | 2355 | 330 | 176 | 1600 |
| 1×150rm/16* | 8.8 | 2.5 | 16* | 43 | 1505 | 2690 | 405 | 176 | 1750 |
| 1×185rm/16* | 8.8 | 2.5 | 16* | 44 | 1840 | 3080 | 510 | 176 | 1915 |
| 1×240rm/16* | 8.8 | 2.5 | 16* | 47 | 2365 | 3720 | 665 | 176 | 2175 |
| 1×150rm/25 | 8.8 | 2.5 | 25 | 43.5 | 1595 | 2770 | 405 | 265 | 1830 |
| 1×185rm/25 | 8.8 | 2.5 | 25 | 45 | 1930 | 3175 | 510 | 265 | 2000 |
| 1×240rm/25 | 8.8 | 2.5 | 25 | 47.5 | 2450 | 3815 | 665 | 265 | 2270 |
| 1×300rm/25 | 8.8 | 2.5 | 25 | 50 | 2980 | 4450 | 830 | 265 | 2500 |
| 1×400rm/35 | 8.8 | 2.6 | 35 | 53.5 | 3835 | 3830 | 1060 | 363 | 3010 |
| 1×500rm/35 | 8.8 | 2.8 | 35 | 56.5 | 4805 | 4800 | 1410 | 363 | 3430 |
Factory Overview
Packaging & Shipping
Frequently Asked Questions (FAQ)
Q:- What is the primary application of SvHEk(v)P and SAvHEk(v)P cables?
A:- These cables are designed for medium-voltage electrical power transmission and distribution in urban networks, transformer substations, industrial plants, and electrical power stations.
Q:- What is the difference between SvHEk(v)P and SAvHEk(v)P cables?
A:- SvHEk(v)P uses copper conductors, while SAvHEk(v)P uses aluminium conductors. Both feature XLPE insulation, copper wire screening, longitudinal water-blocking elements, and PE outer sheathing.
Q:- What standards do these cables follow?
A:- They are manufactured according to BDS 2581-86 and Additional 4.
Q:- What type of conductor is used?
A:- Both cable variants use stranded and compacted Class 2 copper or aluminium conductors according to IEC 60228.
Q:- What insulation material is used?
A:- They use XLPE (Cross-Linked Polyethylene) insulation with inner and outer semiconductive layers.
Q:- What makes these cables water-resistant?
A:- They incorporate water-absorbing powder, semiconductive water-absorbing tapes, and an aluminium foil radial moisture barrier with a copolymer layer.
Q:- What type of metallic screen is used?
A:- The cables feature concentrically laid copper wires and a contact copper tape with a thickness of 0.1 mm.
Q:- What is the maximum continuous operating temperature?
A:- The maximum continuous conductor operating temperature is +90°C.
Q:- What is the maximum short-circuit temperature?
A:- The maximum short-circuit temperature is +250°C for a maximum of 5 seconds.
Q:- What voltage ratings are available?
A:- The product header specifies 6/10 kV and 12/20 kV. The construction tables additionally list 3.6/6 kV, 18/30 kV, and 20/35 kV configurations.
Q:- Is this cable tested for water penetration?
A:- Yes. The catalogue specifies a water penetration test in the region of the metallic screen according to IEC 60502-2 Annex D.




Reviews