RE-2Y(St)YSWAY-fl Armoured Instrumentation and Control Cable – EN 50288-7
The RE-2Y(St)YSWAY-fl cable delivers dependable data transmission for measuring and control appliances. Constructed with bare copper conductors, PE insulation, a static aluminum tape screen, galvanized steel wire armour, and a flame retardant PVC outer sheath, it offers exceptional signal integrity and mechanical protection. Because it meets EN 50288-7 standards and is RoHS compliant, it provides a safe and reliable solution for fixed installations in dry, wet, and outdoor wall environments.
Application
RE-2Y(St)YSWAY-fl cables provide reliable data transfer for measuring and control appliances. Because of their static screen, installers use them to protect circuits from external interfering signals. Furthermore, these cables are suitable for fixed installation in dry and wet premises, as well as for outdoor installation on the walls of buildings. Additionally, they are specifically designed for environments where the non-proliferation of flames is required.
Cable construction
This cable strictly adheres to EN 50288-7 standards. It features bare copper conductors with nominal areas of 0.5mm² and 0.75mm² (classes 2 or 5). The insulation uses a PE compound. Each pair is twisted, with pairs stranded into layers of polyester tapes. A wrapping screen of aluminum tape (coated with polyester and one tinned copper wire 0.5mm²) forms the static screen. An inner sheath of PVC compound provides bedding. The armour consists of galvanized steel wire for mechanical protection. Finally, a PVC compound flame retardant outer sheath protects the entire assembly. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C of max. 36.8 Ω/km (0.5 mm² class 2) and 25.0 Ω/km (0.75 mm² class 2), or max. 38.2 Ω/km (0.5 mm² class 5) and 25.5 Ω/km (0.75 mm² class 5). The mutual capacitance at 800 Hz is max. 100 nF/km. The insulation resistance is min. 5 GΩ.km. The capacitance unbalance at 800 Hz (K1 max) is 250 pF/250m. The test voltage is 50 Hz, 1 min for 1000V (wire-wire) and 1500V (wire-screen). The L/R ratio is max. 25 H/Ω. The temperature range is mobile -5 °C to +50 °C and fixed -30 °C to +65 °C. The minimum bending radius is 10 x cable diameter. Furthermore, it passes the flame retardance test according to IEC 60332-3, class C.
Cable core construction
The pairs are arranged in layers: 1 pair (1st layer), 2 pairs (2nd layer), 4 pairs (3rd layer), 8 pairs (4th layer), 12 pairs (2nd layer), 16 pairs (3rd layer), 20 pairs (4th layer), and 24 pairs (4th layer).
Color coding
Clear color coding ensures safe and accurate wiring. Pair 1 uses black with sequential numbering imprint (a-wire) and white with sequential numbering imprint (b-wire). Pair 2 follows the same scheme.
Type codes
RE = instrumental cable, 2Y = insulation of PE, (St) = static screen, Y = sheath of PVC, SWA = galvanized steel wire.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data RE-2Y(St)YSWAY-fl…
| Number of pairs | External diameter approx. | Copper weight | Cable weight approx. |
|---|---|---|---|
| 1x2x0,5mm² class 2 | mm | kg/km | kg/km |
| 1 | 10,3 | 23 | 236 |
| 2 | 12,6 | 34 | 307 |
| 4 | 13,8 | 42 | 367 |
| 8 | 18,4 | 80 | 508 |
| 12 | 18,7 | 117 | 628 |
| 16 | 21,3 | 155 | 867 |
| 20 | 22,7 | 192 | 1005 |
| 24 | 24,5 | 230 | 1101 |
| 1x2x0,5mm² class 5 | |||
| 1 | 10,3 | 22 | 235 |
| 2 | 12,6 | 33 | 306 |
| 4 | 13,8 | 40 | 365 |
| 8 | 18,4 | 75 | 503 |
| 12 | 18,7 | 111 | 623 |
| 16 | 21,3 | 147 | 859 |
| 20 | 22,7 | 182 | 992 |
| 24 | 24,5 | 218 | 1080 |
Construction data RE-2Y(St)YSWAY-fl…
| Number of pairs | External diameter approx. | Copper weight | Cable weight approx. |
|---|---|---|---|
| 1x2x0,75mm² class 2 | mm | kg/km | kg/km |
| 1 | 10,2 | 18 | 224 |
| 2 | 13,1 | 32 | 331 |
| 4 | 14,5 | 60 | 409 |
| 8 | 17,4 | 111 | 473 |
| 12 | 20,0 | 171 | 731 |
| 16 | 22,7 | 227 | 1005 |
| 20 | 24,8 | 285 | 1168 |
| 24 | 26,4 | 341 | 1304 |
| 1x2x0,75mm² class 5 | |||
| 1 | 10,2 | 17 | 223 |
| 2 | 13,1 | 30 | 329 |
| 4 | 14,5 | 56 | 406 |
| 8 | 17,4 | 104 | 466 |
| 12 | 20,0 | 161 | 721 |
| 16 | 22,7 | 213 | 992 |
| 20 | 24,8 | 268 | 1149 |
| 24 | 26,4 | 321 | 1284 |
Factory Overview
Packaging & Shipping

Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the RE-2Y(St)YSWAY-fl cable?
A:- It is used for data transfer in measuring and control appliances, protecting circuits from external interfering signals in dry, wet, and outdoor wall installations.
Q:- What are the key mechanical protection features of this cable?
A:- It features a galvanized steel wire armour (SWA) that provides robust mechanical protection, making it suitable for harsh environments.
Q:- What standards does the cable construction follow?
A:- The construction adheres to EN 50288-7 standards.
Q:- What type of conductor and insulation does it use?
A:- It uses bare copper conductors with a PE compound insulation.
Q:- What is the temperature range for this cable?
A:- The fixed temperature range is -30°C to +65°C, and the mobile temperature range is -5°C to +50°C.
Q:- What is the mutual capacitance of this cable?
A:- The mutual capacitance at 800 Hz is max. 100 nF/km.
Q:- What is the test voltage for this cable?
A:- The test voltage is 50 Hz, 1 min for 1000V (wire-wire) and 1500V (wire-screen).
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter.
Q:- What do the type codes RE, 2Y, (St), Y, and SWA stand for?
A:- RE indicates an instrumental cable, 2Y indicates PE insulation, (St) indicates a static screen, Y indicates a PVC sheath, and SWA indicates galvanized steel wire armour.
Q:- How is the static screen constructed?
A:- The static screen consists of a wrapping of aluminum tape coated with polyester and one tinned copper wire.


Reviews
There are no reviews yet.