RE-2Y(St)Y-fl PIMF Individually Screened Control Cable – EN 50288-7
The RE-2Y(St)Y-fl PIMF cable delivers dependable data transmission for measuring and control appliances. Constructed with bare copper conductors, PE insulation, individually screened pairs (PIMF), a static aluminum tape screen, galvanized steel wire armour, and a flame retardant PVC outer sheath, it offers exceptional signal integrity and mechanical protection. Because it meets EN 50288-7 standards and is RoHS compliant, it provides a safe and reliable solution for fixed installations in dry, wet, and outdoor wall environments.
Application
RE-2Y(St)Y-fl PIMF cables provide reliable data transfer for measuring and control appliances. Because of their individual and overall static screens, installers use them to protect circuits from external interfering signals. Furthermore, these cables are suitable for fixed installation in dry and wet premises, as well as for outdoor installation on the walls of buildings. Additionally, they are specifically designed for environments where the non-proliferation of flames is required.
Cable construction
This cable strictly adheres to EN 50288-7 standards. It features bare copper conductors with nominal areas of 0.5mm² and 0.75mm² (classes 2 or 5). The insulation uses a PE compound. Each wire is twisted to a pair with PIMF construction: a drain wire (0.6 mm, tinned Cu), an Al-PET foil, and a metal tape as the individual screen, with a wrapping of plastic foil. The PIMF pairs are stranded into layers. A wrapping screen of aluminum tape (coated with polyester and a tinned copper wire) and an inner sheath of PVC compound complete the core assembly. An armour of galvanized steel wire provides mechanical protection. Finally, a PVC compound flame retardant outer sheath (blue, black, or other color) protects the entire cable. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C of max. 36.8 Ω/km (0.5 mm² class 2) and 25.0 Ω/km (0.75 mm² class 2), or max. 38.2 Ω/km (0.5 mm² class 5) and 25.5 Ω/km (0.75 mm² class 5). The mutual capacitance at 800 Hz is max. 120 nF/km. The insulation resistance is min. 5 GΩ.km. The capacitance unbalance at 800 Hz (K1 max) is 250 pF/250m. The test voltage is 50 Hz, 1 min for 1200V (wire-wire) and 1500V (wire-screen). The L/R ratio is max. 25 H/Ω. The temperature range is mobile -5 °C to +50 °C and fixed -30 °C to +65 °C. The minimum bending radius is 10 x cable diameter. Furthermore, it passes the flame retardance test according to IEC 60332-3, class C.
Color coding
Clear color coding ensures safe and accurate wiring. Pair 1 uses black with sequential numbering imprint (a-wire) and white with sequential numbering imprint (b-wire). Pair 2 follows the same scheme.
Type codes
RE = Instrumental cable, 2Y = insulation of PE, (St) = static screen, Y-fl = sheath of PVC compound fire retardant, PIMF = screened pairs.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data RE – 2Y(St)Y-fl…
| Number of pairs | External diameter approx. | Copper weight | Cable weight approx. |
|---|---|---|---|
| 1x2x0,5mm² PIMF class 2, Lg | mm | kg/km | kg/km |
| 2 | 9,4 | 28 | 88 |
| 4 | 10,8 | 51 | 130 |
| 8 | 14,7 | 98 | 233 |
| 12 | 17,3 | 144 | 319 |
| 16 | 19,9 | 191 | 431 |
| 20 | 22,1 | 238 | 515 |
| 24 | 23,8 | 284 | 597 |
| 1x2x0,5mm² PIMF class 5, Lg | |||
| 2 | 9,4 | 27 | 87 |
| 4 | 10,8 | 49 | 128 |
| 8 | 14,7 | 94 | 228 |
| 12 | 17,3 | 139 | 313 |
| 16 | 19,9 | 183 | 413 |
| 20 | 22,1 | 228 | 505 |
| 24 | 23,8 | 273 | 585 |
Construction data RE – 2Y(St)Y-fl…
| Number of pairs | External diameter approx. | Copper weight | Cable weight approx. |
|---|---|---|---|
| 1x2x0,75mm² PIMF class 2, Lg | mm | kg/km | kg/km |
| 2 | 10,3 | 40 | 107 |
| 4 | 12,2 | 78 | 167 |
| 8 | 16,6 | 139 | 298 |
| 12 | 19,6 | 205 | 417 |
| 16 | 21,9 | 272 | 533 |
| 20 | 24,6 | 338 | 655 |
| 24 | 27,4 | 404 | 760 |
| 1x2x0,75mm² PIMF class 5, Lg | |||
| 2 | 10,3 | 38 | 105 |
| 4 | 12,2 | 67 | 163 |
| 8 | 16,6 | 125 | 281 |
| 12 | 19,6 | 189 | 407 |
| 16 | 21,9 | 250 | 520 |
| 20 | 24,6 | 326 | 636 |
| 24 | 27,4 | 372 | 760 |
Factory Overview
Packaging & Shipping

Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the RE-2Y(St)Y-fl PIMF cable?
A:- It is used for data transfer in measuring and control appliances, protecting circuits from external interfering signals in dry, wet, and outdoor wall installations.
Q:- What are the key features of the PIMF construction?
A:- PIMF (screened pairs) features individual pair screens made of a drain wire, Al-PET foil, and metal tape, combined with an overall static screen for superior protection against interference.
Q:- What standards does the cable construction follow?
A:- The construction adheres to EN 50288-7 standards.
Q:- What type of conductor and insulation does it use?
A:- It uses bare copper conductors with a PE compound insulation.
Q:- What is the temperature range for this cable?
A:- The fixed temperature range is -30°C to +65°C, and the mobile temperature range is -5°C to +50°C.
Q:- What is the mutual capacitance of this cable?
A:- The mutual capacitance at 800 Hz is max. 120 nF/km.
Q:- What is the test voltage for this cable?
A:- The test voltage is 50 Hz, 1 min for 1200V (wire-wire) and 1500V (wire-screen).
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter.
Q:- What do the type codes RE, 2Y, (St), Y-fl, and PIMF stand for?
A:- RE indicates an instrumental cable, 2Y indicates PE insulation, (St) indicates a static screen, Y-fl indicates a flame retardant PVC sheath, and PIMF indicates screened pairs.
Q:- What kind of mechanical protection does the cable have?
A:- It features an armour made of galvanized steel wire to provide robust mechanical protection.