AGKABEL Middle Voltage Power Cables – EXeCVB / EAXeCVB (8.7/15 kV, 12/20 kV, 20.8/36 kV)

Single-core cables with XLPE insulation and longitudinal water-blocking elements, designed for power transfer and distribution in urban and district networks. Features Cu or Al compacted conductors, a copper wire screen, and a red PVC sheath. Compliant with NBN C 33-323 and RoHS. Operating temperature: 90°C continuous. Suitable for transformer substations, power stations, and industrial systems. Available from 25mm² to 400mm².

AGKABEL GRUPPE LIMITED presents the Middle Voltage Power Cables (EXeCVB and EAXeCVB), engineered for reliable power transfer and distribution. These single-core cables feature XLPE insulation and longitudinal water-blocking elements, ensuring high performance and safety even in wet environments. Designed for nominal voltages Uo/U 8.7/15 kV, 12/20 kV, and 20.8/36 kV at 50 Hz, they are ideal for urban and district electrical networks, transformer substations, and small to medium industrial plants. Suitable for distribution installations, electric power stations, and industrial systems, they are built for fixed assembly in lines with unlimited difference levels, indoor installations, cable ducts, conduits, shafts, over shelves/grills, directly underground in ditches, and outdoor shelters.

Technical Data

  • Standard: According to NBN C 33-323

  • Conductors: Cu and Al stranded compacted, according to IEC 60228 cl.2 (NBN C 30-228)

  • Insulation: XLPE compound

  • Water resisting element: Layer of semi-conductive water absorbing tapes + water absorbing insulating tape

  • Metal screen: Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm

  • Sheath: PVC compound type ST2 (Red)

  • Conductor resistance at 20°C: According to IEC 60228 class 2 (NBN C 30-228)

  • Operating temperature: 90°C continuous operation

  • Overload temperature: 120°C / 100h per year max.

  • Short circuit temperature: 250°C / 5 s max.

  • Nominal voltage Uo/U: 8.7/15; 12/20; 20.8/36 kV

  • Highest system voltage Uo/U: 8.7/15; 12/20; 20.8/36 kV (17.5 kV; 24 kV; 41.5 kV)

  • Test voltage: AC (~) – 5 min (8.7/15: 35 kV; 12/20: 48 kV; 20.8/36: 83 kV)

  • Level of partial discharge: max. 5 pC at 2*Uo

  • Bending radius, min: 15x D cable

  • Temperature of laying: no less than -15°C

  • Temperature of exploitation: -30 to 50°C

  • Application: Designed for transfer and distribution of electrical power with nominal voltage Uo/U 8.7/15kV, 12/20kV, n 20.8/36 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer’s substations, small and medium industrial plants. Suitable for use in distribution installations, electric power stations and industrial systems.

Technical Specifications Table

Number of conductors and nominal cross section N x mm² Thickness of insulation (mm) Thickness of sheath (mm) Nominal cross-section of screen (mm²) Cable diameter approx. (mm) Mass of Cu approx. (kg/km) Mass of cable approx. (kg/km) Mass of Al approx. (kg/km) Mass of cable approx. (kg/km)
8.7/15 kV (EXeCVB)
1×25 rm /16 4,5 2,6 16 26,8 490 1048 68 890
1×50 rm /16 4,5 2,6 16 29,0 690 1319 130 1024
1×95 rm /25 4,5 2,6 25 32,5 1120 1858 260 1263
1×150 rm /25 4,5 2,9 25 35,9 1595 2473 405 1548
1×240 rm /25 4,5 3,1 25 40,0 2661 3510 665 1985
1x400rm /35 4,5 3,3 35 47,3 4344 5204 1060 2792
12/20 kV (EXeCVB)
1×50 rm /16 5,5 2,6 16 31,4 690 1414 130 1119
1×95 rm /25 5,5 2,7 25 35,0 1120 1979 260 1384
1×150 rm /25 5,5 3,0 25 38,4 1595 2607 405 1682
1×240 rm /25 5,5 3,1 25 42,7 2661 3641 665 2116
1x400rm /35 5,5 3,3 35 49,6 4344 5348 1060 2936
20.8/36 kV (EXeCVB)
1×120 rm /25 8,8 3,0 25 43,5 1345 2772 330 2022
1×150 rm /25 8,8 3,2 25 45,3 1595 3136 405 2211
1×240 rm /25 8,8 3,4 25 49,8 2455 4252 665 2727
1×400 rm /35 8,8 3,6 35 56,9 3835 6047 1060 3635

 

(Note: The table above lists EXeCVB data. EAXeCVB data follows the same structure with Aluminium conductors. Further dimensions available on request.)

 

Factory Overview


Packaging & Shipping


Fly

 

❓ Frequently Asked Questions (FAQ)

1. What are the primary applications for these cables?
They are designed for transfer and distribution of electrical power in urban and district electrical networks, as well as for the electrical supply of transformer’s substations, small and medium industrial plants, and distribution installations, power stations, and industrial systems.

2. What is the significance of the water-blocking elements?
The longitudinal water-blocking elements (water-absorbing tapes) prevent water from propagating along the cable in case of damage, significantly enhancing the cable’s reliability and lifespan, especially in underground or wet installations.

3. What are the voltage ratings of these cables?
They are available in 8.7/15 kV, 12/20 kV, and 20.8/36 kV ratings.

4. What is the maximum operating temperature?
The continuous operating temperature is 90°C, with a maximum overload temperature of 120°C (100h/year max) and a short-circuit temperature of 250°C (5s max).

5. What standards do these cables comply with?
They comply with NBN C 33-323 and are RoHS compliant. Conductor resistance is according to IEC 60228 class 2.

6. What is the difference between EXeCVB and EAXeCVB?

  • EXeCVB: Features Copper (Cu) conductors.

  • EAXeCVB: Features Aluminium (Al) conductors, offering a lighter and more cost-effective alternative.

7. What sizes and core configurations are available?
Available in single-core configurations, with conductor sizes ranging from 25mm² to 400mm².

Reviews

There are no reviews yet.

Be the first to review “AGKABEL Middle Voltage Power Cables – EXeCVB / EAXeCVB (8.7/15 kV, 12/20 kV, 20.8/36 kV)”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS