2XYRYfr-O/J & A2XYRYfr-O/J 0.6/1 kV Flame Retardant Armoured Cable
The 2XYRYfr-O/J and A2XYRYfr-O/J 0.6/1 kV cables deliver dependable power distribution for industrial, domestic, and underground applications. Constructed with aluminum or copper conductors, XLPE insulation, galvanized iron wire armour, and a black flame retardant PVC outer sheath, they offer exceptional fire safety and mechanical protection. Because they meet IEC 60502-1 standards and are RoHS compliant, they provide a safe and reliable solution for power plants, switching installations, and secondary networks.
Application
2XYRYfr-O/J and A2XYRYfr-O/J cables provide reliable transfer and distribution of electrical power in networks with a nominal voltage of Uo/U 0.6/1 kV and a frequency of 50 Hz. Because they require no propagation of flames, installers use them widely in power plants, industrial and switching installations, and street lighting. Furthermore, they excel in domestic power supply connections and secondary distribution networks. Additionally, they are preferably used for underground application and as interior installation in rooms and cable ducts. Finally, they are suitable for outdoor applications where greater mechanical protection against accidental contact is required.
Cable construction
This cable strictly adheres to IEC 60502-1 standards. It features solid or multi-strand aluminum or copper wires (class 1 or 2) that comply with IEC 60228. The insulation uses an XLPE compound. The inner sheath uses a PVC flame retardant compound of degree of flame retardancy. The armour consists of galvanized iron wires twisted concentrically. Finally, a black PVC flame retardant outer sheath of degree of flame retardancy category A protects the entire assembly. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC 60228 class 1 or 2. The maximum conductor temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of Uo/U 0.6/1 kV, while the highest system voltage is 1.2 kV. Test voltage is AC – 5 min for 3.5 kV between cores and 3.5 kV between core and screen. Installers must respect a minimum bending radius of 15 times the cable diameter. The temperature of laying is no less than 0 °C. The temperature of explosion is -30 to 50 °C. Furthermore, it passes the flame retardancy test according to BDS IEC 332-3/82, Category A.
Color coding
Clear color coding ensures safe and accurate wiring. Double core cables feature light blue and brown, or yellow-green and black. 3-core cables use brown, black, and grey, or yellow/green, light blue, and brown. 4-core cables use light blue, brown, black, and grey, or yellow/green, brown, black, and grey. 5-core cables use light blue, brown, black, grey, and black, or yellow/green, light blue, brown, black, and grey. Multiple core cables use black with numbered cores laid in each cover.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data 2XYRYfr, A2XYRYfr 0.6/1 kV
| Number of conductors and nominal cross section | Thickness of insulation | Thickness of sheath | Cable diameter approx. | 2XYRYfr Mass of Cu approx. | 2XYRYfr Cable weight approx. | A2XYRYfr Mass of Al approx. | A2XYRYfr Cable weight approx. |
|---|---|---|---|---|---|---|---|
| N x mm² | mm | mm | mm | kg/km | kg/km | kg/km | kg/km |
| 2 x 2,5 m | 0,7 | 1,8 | 14,1 | 46 | 421 | 14 | 388 |
| 2 x 4 m | 0,7 | 1,8 | 15,2 | 75 | 500 | 23 | 448 |
| 2 x 6 m | 0,7 | 1,8 | 16,1 | 88 | 563 | 29 | 512 |
| 2 x 10 m | 0,7 | 1,8 | 18,8 | 188 | 868 | 56 | 723 |
| 2 x 16 m | 0,7 | 1,8 | 21,9 | 298 | 1150 | 89 | 931 |
| 2 x 25 m | 0,9 | 1,8 | 24,9 | 485 | 1584 | 140 | 1236 |
| 2 x 35 m | 0,9 | 1,9 | 26,2 | 645 | 2076 | 188 | 1730 |
| 2 x 50 m | 1,0 | 2,1 | 29,2 | 908 | 2376 | 240 | 1727 |
| 2 x 95 m | 1,1 | 2,1 | 38,2 | 1822 | 4058 | 539 | 2762 |
| 3 x 1,5 m | 0,7 | 1,8 | 16,5 | 43 | 468 | 13 | 417 |
| 3 x 2,5 m | 0,7 | 1,8 | 16,5 | 70 | 619 | 21 | 570 |
| 3 x 4 m | 0,7 | 1,8 | 17,5 | 70 | 719 | 38 | 658 |
| 3 x 6 m | 0,7 | 1,8 | 18,8 | 168 | 769 | 51 | 676 |
| 3 x 10 m | 0,7 | 1,8 | 19,8 | 282 | 987 | 85 | 785 |
| 3 x 16 m | 0,7 | 1,8 | 21,3 | 447 | 1254 | 135 | 915 |
| 3 x 25 m | 0,9 | 1,8 | 27,8 | 478 | 1830 | 210 | 1236 |
| 3 x 35 m | 0,9 | 1,8 | 27,8 | 1010 | 2300 | 290 | 1593 |
| 3 x 50 m | 1,0 | 1,9 | 33,8 | 1353 | 2801 | 385 | 1914 |
| 3 x 70 m | 1,1 | 2,1 | 35,3 | 1968 | 3330 | 517 | 2237 |
| 3 x 95 m | 1,1 | 2,1 | 40,0 | 2672 | 4015 | 720 | 2940 |
| 4 x 2,5 m | 0,7 | 1,8 | 16,6 | 93 | 509 | 26 | 467 |
| 4 x 4 m | 0,7 | 1,8 | 17,5 | 149 | 690 | 42 | 606 |
| 4 x 6 m | 0,7 | 1,8 | 18,8 | 230 | 820 | 58 | 754 |
| 4 x 10 m | 0,7 | 1,8 | 21,2 | 376 | 1578 | 112 | 1309 |
| 4 x 16 m | 0,7 | 1,8 | 23,5 | 595 | 2076 | 180 | 1832 |
| 4 x 25 m | 0,9 | 1,9 | 27,5 | 970 | 2620 | 290 | 2030 |
| 4 x 35 m | 1,0 | 2,1 | 30,3 | 1346 | 3701 | 390 | 2737 |
| 4×50 sm | 1,4 | 2,1 | 34,4 | 1817 | 3301 | 520 | 2225 |
| 4×70 sm | 1,6 | 2,1 | 38,6 | 2672 | 4015 | 720 | 2940 |
| 4×95 sm | 1,6 | 2,2 | 43,0 | 3843 | 5075 | 1050 | 3430 |
| 4×120 sm | 1,6 | 2,2 | 47,5 | 4367 | 7626 | 1340 | 4346 |
| 4×150 sm | 1,8 | 2,4 | 51,8 | 5810 | 9141 | 1690 | 5094 |
| 4×185 sm | 2,0 | 2,5 | 56,2 | 6960 | 10028 | 2050 | 5496 |
| 4×240 sm | 2,2 | 2,6 | 62,3 | 9371 | 12861 | 2720 | 7207 |
| 7 x 1,5 m | 0,7 | 1,8 | 17,0 | 100 | 980 | 49 | 789 |
| 7 x 2,5 m | 0,7 | 1,8 | 19,1 | 109 | 1167 | 49 | 762 |
| 10 x 1,5 m | 0,7 | 1,8 | 20,4 | 165 | 1193 | 51 | 717 |
| 12 x 1,5 m | 0,7 | 1,8 | 20,4 | 165 | 2277 | 51 | 1179 |
| 19 x 2,5 m | 0,7 | 1,8 | 25,6 | 435 | 2277 | 133 | 1972 |
Factory Overview
Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the 2XYRYfr-O/J and A2XYRYfr-O/J cables?
A:- They are used for power transfer and distribution in power plants, industrial and switching installations, street lighting, domestic power supply connections, and secondary distribution networks.
Q:- What are the key features of this cable’s fire safety?
A:- It features a PVC flame retardant insulation and a black PVC outer sheath with a flame retardancy category A, passing the BDS IEC 332-3/82 test.
Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-1 standards, and the conductor complies with IEC 60228 class 1 or 2.
Q:- What type of conductor and insulation does it use?
A:- It uses solid or multi-strand Al or Cu wires with XLPE insulation.
Q:- What kind of armour protects this cable?
A:- The cable features an armour made of galvanized iron wires twisted concentrically.
Q:- What is the rated voltage and maximum conductor temperature?
A:- The rated voltage is Uo/U 0.6/1 kV, and the maximum conductor temperature is 90°C continuous.
Q:- What are the short-circuit and overload temperature limits?
A:- It can withstand a short circuit temperature of 250°C for a maximum of 5 seconds and an overload temperature of 130°C for 100% per year max.
Q:- What is the test voltage for this cable?
A:- The test voltage is AC – 5 min for 3.5 kV between cores and 3.5 kV between core and screen.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).
Q:- What are the temperature limits for laying and explosion?
A:- The temperature of laying is no less than 0°C, and the temperature of explosion is -30 to 50°C.