2XS(F)2Y & A2XS(F)2Y 3.6/6 kV to 20/35 kV XLPE Water-Blocking Cable – IEC 60502-2

The 2XS(F)2Y and A2XS(F)2Y cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, water-blocking tapes, and a PE outer sheath, they offer excellent thermal and moisture protection for 3.6/6 kV, 8.7/15 kV, and 20/35 kV applications. Because they meet IEC 60502-2 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
2XS(F)2Y and A2XS(F)2Y medium voltage cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 3.6/6 kV, 8.7/15 kV, and 20/35 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for use in distribution installations and cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. A layer of semi-conductive water absorbing tapes forms the water resisting element. The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. The water resisting element can be either -i-option (water absorbing insulation) or -ii-option (water absorbing powder and a layer of plastic tape). The sheath uses PE compound type ST7 according to IEC 60502. The color is black. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BDS904 (IEC60228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 3.6/6, 8.7/15, and 20/35 kV, while the highest system voltage Uo/U is not more than 3.6/6, 12/20, and 24/36 kV. Test voltage is AC (+) – 5 min for 3.6/6 kV (10 kV), 8.7/15 kV (30 kV), and 20/35 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XS(F)2Y, A2XS(F)2Y 3.6/6; 8.7/15; 20/35 kV

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XS(F)2Y Mass of Cu approx. 2XS(F)2Y Mass of cable approx. A2XS(F)2Y Mass of Al approx. A2XS(F)2Y Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
3.6/6 kV
1×35 m/16 2,5 1,8 16 22,2 493 798 94 176
1×50 m/16 2,5 1,8 16 23,3 604 909 127 572
1×70 m/16 2,5 1,8 16 25,0 793 1140 183 622
1×95 m/16 2,5 1,8 16 26,7 1033 1432 251 746
1×120 m/16 2,5 1,8 16 28,3 1255 1706 321 829
1×150 m/16 2,5 1,9 16* 29,9 1537 1980 384 1042
1×185 m/25 2,6 1,9 25 31,7 1952 2841 495 1029
1×240 m/25 2,6 1,9 25 34,2 2361 3081 639 1162
1×300 m/25 2,8 1,9 25 36,7 2736 3096 695 1105
1×400 m/35 2,8 2,1 35 41,0 3895 3895 812 1226
1×500 m/35 3,0 2,2 35 43,3 4807 4560 969 1275
1×630 m/35 3,2 2,4 35 44,1 4807 5693 1374 2480
8.7/15 kV
1×35 m/16 4,5 1,8 16 26,2 493 921 94 176
1×50 m/16 4,5 1,8 16 27,3 604 994 127 768
1×70 m/16 4,5 1,8 16 29,0 793 1277 183 771
1×95 m/16 4,5 1,9 16 30,9 1033 1617 251 1000
1×120 m/16 4,5 1,9 16 32,5 1255 1946 321 1176
1×150 m/16 4,5 2,0 16* 34,2 1537 2237 384 1178
1×185 m/16 4,5 2,1 16* 36,1 1850 2180 494 1298
1×240 m/16 4,5 2,1 16* 38,5 2365 3430 649 1476
1×300 m/25 4,5 2,2 25 41,0 2815 3705 812 1723
1×400 m/35 4,5 2,4 35 44,9 3240 3921 1095 1826
1×500 m/35 4,5 2,5 35 47,9 4807 4900 1374 2476
1×630 m/35 4,5 2,5 35 48,7 4807 5873 1374 2774
20/35 kV
1×50 m/16 8,8 2,1 16 36,5 604 1478 127 1188
1×70 m/16 8,8 2,1 16 38,0 793 1751 183 1215
1×95 m/16 8,8 2,1 16 39,7 1033 2075 251 1445
1×120 m/16 8,8 2,2 16 41,4 1255 2556 321 1480
1×150 m/16 8,8 2,3 16 42,5 1537 2773 384 1636
1×185 m/25 8,8 2,4 25 44,5 1930 3178 484 1738
1×240 m/25 8,8 2,4 25 47,9 2365 2773 649 1813
1×300 m/25 8,8 2,5 25 50,2 2930 2960 812 2028
1×400 m/35 8,8 2,6 35 53,7 2920 4052 1095 2550
1×500 m/35 8,8 2,8 35 57,1 3830 6161 1374 2674
1×630 m/35 8,8 2,8 35 60,7 4807 6669 1374 3430

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XS(F)2Y and A2XS(F)2Y cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available in three nominal voltage levels: Uo/U 3.6/6 kV, 8.7/15 kV, and 20/35 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 standards, and the conductor complies with IEC 60228 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What is the function of the water resisting element?
A:- The water resisting element, which is a layer of semi-conductive water absorbing tapes, prevents water ingress along the cable, with options for water absorbing insulation or water absorbing powder and plastic tape.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.

Q:- What is the maximum force of strain during laying?
A:- The maximum force of strain is 30NS for Al cores and 50NS for Cu cores, where N is the number of cores and S is the cross-section of conductors in mm.