3.8/6.6kV Copper XLPE Single-Core Light Duty Screened Power Cable – AS/NZS 1429.1

The 3.8/6.6kV copper XLPE single-core light duty screened power cable provides dependable electrical connections for urban power distribution networks, industrial facilities and underground power installations. It features a compacted annealed copper conductor, natural TR-XLPE insulation, a light duty annealed copper wire screen and a PVC or PVC/HDPE outer sheath.

Furthermore, it supports a rated voltage of 3.8/6.6kV and a maximum operating temperature of 90°C. The light duty copper wire screen features a specified minimum fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, subject to applicable standard requirements.

Application

The 3.8/6.6kV copper XLPE single-core light duty screened power cable is designed for primary power supply applications in urban electrical distribution networks, industrial facilities and underground power distribution systems.

Furthermore, the compacted annealed copper conductor provides excellent electrical conductivity, while the natural TR-XLPE (Tree-Retardant Cross-Linked Polyethylene) insulation provides enhanced resistance to water tree formation and electrical insulation degradation.

In addition, the light duty annealed copper wire screen provides a path for earth fault currents, while the PVC or PVC/HDPE outer sheath provides environmental protection for underground power installations.

These cables are suitable for direct burial, underground duct installations, unenclosed installations where they are not subject to mechanical damage, and installations requiring cable gland termination.

Cable Construction

  • Standard: AS/NZS 1429.1:2000.

  • Rated Voltage: 3.8/6.6kV (3800/6600V).

  • Conductor: Compacted annealed copper.

  • Insulation: Natural TR-XLPE (Tree-Retardant Cross-Linked Polyethylene).

  • Number of Cores: Single-core (1C).

  • Screen: Light duty annealed copper wire screen.

  • Outer Sheath: PVC 5V-90 or PVC 5V-90/HDPE.

  • Maximum Operating Temperature: 90°C.

  • Screen Fault Current Rating: Minimum 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum coverage allowable under the applicable standard.

  • Sheath Marking: Manufacturer’s name (trademark) and type, production year/week or batch number, and metre markings.

  • Special Properties: Tree-retardant insulation, light duty copper wire screening, compact single-core construction and excellent electrical conductivity.

  • Available Cross-Sections: 16 mm² to 630 mm².

  • Installation Methods: Direct burial, underground ducts and suitable unenclosed installations.

Technical Data

The 3.8/6.6kV copper XLPE single-core light duty screened power cable features a rated voltage of 3800/6600V and a maximum operating temperature of 90°C. Its natural TR-XLPE insulation provides enhanced resistance to water tree formation, supporting long-term electrical performance in underground power distribution applications.

Moreover, the compacted annealed copper conductor provides excellent electrical conductivity and low conductor resistance. The light duty annealed copper wire screen features a specified minimum fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum coverage according to the applicable standard.

The listed conductor cross-sections range from 16 mm² to 630 mm², while the conductor diameter ranges from 4.9 mm to 32.7 mm.

Furthermore, the listed overall cable diameter ranges from 17.9 mm to 51.1 mm, and the approximate cable mass ranges from 530 kg/km to 6980 kg/km.

The maximum DC conductor resistance at 20°C ranges from 0.028 Ω/km to 1.150 Ω/km.

Constructive Data Table

Cross-section (mm²) Conductor No. of Strands Conductor Dia. (mm) Minimum Overall Dia. (mm) Maximum Overall Dia. (mm) Max. DC Resistance at 20°C (Ω/km) Approximate Mass (kg/km)
16 7 4.9 17.9 20.3 1.150 530
25 7 6.0 19.1 21.4 0.727 650
35 7 7.0 20.0 22.4 0.524 760
50 19 8.1 21.1 23.5 0.387 900
70 19 9.8 22.8 25.2 0.268 1100
95 19 11.4 24.4 26.8 0.193 1400
— — — — — 0.153 1600
150 19 14.3 27.4 29.7 0.124 1900
185 37 16.0 29.2 31.6 0.099 2300
240 37 18.4 31.8 34.2 0.075 2900
300 37 20.8 34.9 37.3 0.060 3500
400 59 23.5 38.2 40.7 0.047 4400
500 61 26.6 42.0 44.6 0.037 5500
630 91 32.7 48.1 51.1 0.028 6980

Technical note: All visible numerical table values and measurement units remain unchanged from the original datasheet. The row containing 0.153 Ω/km and 1600 kg/km appears to correspond to a 120 mm² copper conductor, but the remaining specifications are missing and have not been estimated. Light duty refers to the copper wire screen rather than mechanical protection. No armour is specified. The missing technical data, applicable AS/NZS 1429.1 edition and screen fault current rating should be verified before publishing.

Factory Overview


Packaging & Shipping


Frequently Asked Questions and Answers

Q:- What is the primary application of the 3.8/6.6kV copper XLPE single-core light duty screened cable?

A:- It is designed for primary power supply in urban electrical distribution networks, industrial power installations and underground power distribution systems.

Q:- What standard does the 3.8/6.6kV copper XLPE power cable follow?

A:- The manufacturer specifies AS/NZS 1429.1:2000 in the product datasheet.

Q:- What is the rated voltage of the copper XLPE single-core light duty screened cable?

A:- The rated voltage is 3.8/6.6kV (3800/6600V).

Q:- What is the maximum operating temperature of the copper XLPE power cable?

A:- The maximum operating temperature is 90°C.

Q:- What type of conductor does the single-core copper power cable use?

A:- It uses a compacted annealed copper conductor, providing excellent electrical conductivity, low conductor resistance and compact conductor construction.

Q:- What are the advantages of natural TR-XLPE insulation?

A:- TR-XLPE insulation provides enhanced resistance to water tree formation, helping reduce electrical insulation degradation and improve long-term reliability in underground power distribution applications.

Q:- What is the fault current rating of the light duty copper wire screen?

A:- The manufacturer specifies a minimum screen fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum screen coverage allowable under the applicable standard.

Q:- What is the difference between light duty and heavy duty screened power cables?

A:- Light duty screened power cables generally feature a smaller copper wire screen cross-section and lower earth fault current capacity than heavy duty screened cables. They offer reduced cable weight and material costs where the screen fault current capacity satisfies the electrical system requirements.

Q:- What outer sheath materials are available for the copper XLPE power cable?

A:- The manufacturer specifies PVC 5V-90 or PVC 5V-90/HDPE sheath options. The appropriate sheath construction should be selected according to the installation environment and project requirements.

Q:- Can the 3.8/6.6kV copper XLPE single-core light duty screened cable be installed directly underground?

A:- Yes, the manufacturer specifies suitability for direct burial and underground duct installations. However, appropriate mechanical protection and compliance with applicable electrical installation requirements must be ensured.

Reviews

There are no reviews yet.

Be the first to review “3.8/6.6kV Copper XLPE Single-Core Light Duty Screened Power Cable – AS/NZS 1429.1”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS