1.9/3.3kV Copper XLPE 3-Core SWA Light Duty Screened Power Cable – AS/NZS 1429.1
The 1.9/3.3kV copper XLPE 3-core SWA light duty screened power cable provides dependable electrical connections for urban power distribution networks, industrial facilities and underground power installations. It features compacted annealed copper conductors, TR-XLPE insulation, a light duty annealed copper wire screen, steel wire armour and a PVC or HDPE outer sheath.
Application
The 1.9/3.3kV copper XLPE 3-core SWA light duty screened power cable is designed for primary power supply applications in urban electrical distribution networks, industrial facilities and underground power transmission systems.
Furthermore, the compacted annealed copper conductors provide efficient electrical conductivity, while the TR-XLPE (Tree-Retardant Cross-Linked Polyethylene) insulation provides enhanced resistance to water tree formation and electrical insulation degradation.
In addition, the light duty annealed copper wire screen provides a path for earth fault currents, while the steel wire armour provides additional mechanical protection. The PVC or HDPE outer sheath protects the cable against environmental influences.
These cables are suitable for direct burial, installation in underground ducts, unenclosed installations where they are not subject to mechanical damage, and installations requiring cable gland termination.
Cable Construction
-
Standard: AS/NZS 1429.1:2000.
-
Rated Voltage: 1.9/3.3kV (1900/3300V).
-
Conductor: Compacted annealed copper.
-
Insulation: TR-XLPE (Tree-Retardant Cross-Linked Polyethylene).
-
Core Identification: Numbered cores.
-
Number of Cores: 3.
-
Screen: Light duty annealed copper wire screen.
-
Armour: SWA (Steel Wire Armour), as indicated in the product title.
-
Outer Sheath: PVC 5V-90 or HDPE (High-Density Polyethylene).
-
Maximum Operating Temperature: 90°C.
-
Screen Fault Current Rating: Minimum 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum coverage as specified in the applicable standard.
-
Sheath Marking: Manufacturer’s name (trademark) and type, production year/week or batch number, and metre markings.
-
Special Properties: Tree-retardant insulation, light duty copper wire screening and armoured construction.
-
Available Cross-Sections: 16 mm² to 300 mm² per core.
-
Installation Methods: Direct burial, underground ducts and suitable unenclosed installations.
Technical Data
The 1.9/3.3kV copper XLPE 3-core SWA light duty screened power cable features a rated voltage of 1900/3300V and a maximum operating temperature of 90°C. Its TR-XLPE insulation provides enhanced resistance to water tree formation, supporting long-term electrical performance in underground power distribution applications.
Moreover, the compacted annealed copper conductors provide efficient electrical conductivity and a compact conductor construction. The light duty copper wire screen has a specified minimum fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, subject to the applicable standard requirements.
The listed conductor cross-sections range from 16 mm² to 300 mm² per core, while the conductor diameter ranges from 4.9 mm to 20.8 mm.
Furthermore, the overall cable diameter ranges from 39.0 mm to 84.0 mm, and the approximate cable mass ranges from 2610 kg/km to 15120 kg/km. The maximum DC conductor resistance at 20°C ranges from 0.0601 Ω/km to 1.150 Ω/km.
Constructive Data Table
| Cross-section (mm²) | Conductor No. of Strands | Conductor Dia. (mm) | Minimum Overall Dia. (mm) | Maximum Overall Dia. (mm) | Max. DC Resistance at 20°C (Ω/km) | Approximate Mass (kg/km) |
|---|---|---|---|---|---|---|
| 16 | 7 | 4.9 | 39.0 | 43.8 | 1.150 | 2610 |
| 25 | 7 | 6.0 | 41.7 | 46.5 | 0.727 | 3070 |
| 35 | 7 | 7.0 | 44.0 | 48.8 | 0.524 | 3500 |
| 50 | 19 | 8.1 | 49.5 | 51.3 | 0.387 | 4020 |
| 70 | 19 | 9.8 | 51.8 | 56.7 | 0.268 | 5390 |
| 95 | 19 | 11.4 | 55.5 | 60.4 | 0.193 | 6420 |
| 120 | 19 | 12.9 | 59.0 | 63.9 | 0.153 | 7410 |
| 150 | 19 | 14.3 | 62.6 | 67.6 | 0.124 | 8510 |
| 185 | 36 | 16.0 | 66.6 | 71.6 | 0.0991 | 9880 |
| 240 | 36 | 18.4 | 72.2 | 77.2 | 0.0754 | 12040 |
| 300 | 36 | 20.8 | 78.9 | 84.0 | 0.0601 | 15120 |
Technical note: All visible numerical table values have been retained from the original datasheet. SWA is indicated in the product title, but the armour construction, bedding material and armour wire dimensions are not specified separately. The applicable AS/NZS 1429.1 edition, sheath material designation and screen fault current rating should be confirmed before publishing.
Factory Overview
Packaging & Shipping
Frequently Asked Questions and Answers
Q:- What is the primary application of the 1.9/3.3kV copper XLPE 3-core SWA light duty screened cable?
A:- It is designed for primary power supply in urban electrical distribution networks, industrial power installations and underground power distribution systems.
Q:- What standard does the 1.9/3.3kV copper XLPE SWA power cable follow?
A:- The manufacturer specifies AS/NZS 1429.1:2000 in the product datasheet.
Q:- What is the rated voltage of the copper XLPE 3-core SWA power cable?
A:- The rated voltage is 1.9/3.3kV (1900/3300V).
Q:- What is the maximum operating temperature of the 1.9/3.3kV XLPE power cable?
A:- The maximum operating temperature is 90°C.
Q:- What type of conductor does the 3-core SWA power cable use?
A:- It uses compacted annealed copper conductors, providing efficient electrical conductivity and a compact conductor construction.
Q:- What are the advantages of TR-XLPE insulation?
A:- TR-XLPE insulation provides enhanced resistance to water tree formation, helping reduce insulation degradation and improve long-term electrical reliability in underground power cable applications.
Q:- What is the fault current rating of the light duty copper wire screen?
A:- The manufacturer specifies a minimum screen fault current rating of 13.1kA for 0.04 seconds or 2.6kA for 1 second, or minimum screen coverage according to the applicable standard.
Q:- What is the purpose of steel wire armour in the 1.9/3.3kV power cable?
A:- Steel wire armour provides additional mechanical protection against external forces and potential mechanical damage during installation and operation.
Q:- What outer sheath materials are available for the copper XLPE SWA cable?
A:- The manufacturer specifies PVC 5V-90 or HDPE outer sheath options. The appropriate sheath material should be selected according to the installation environment and project requirements.
Q:- Can the 1.9/3.3kV copper XLPE SWA cable be installed directly underground?
A:- Yes, the manufacturer specifies suitability for direct burial and underground duct installations. Installation must comply with applicable electrical regulations, mechanical protection and thermal design requirements.




Reviews
There are no reviews yet.