1.9/3.3kV Aluminium XLPE 3-Core SWA Heavy Duty Screened Power Cable – AS/NZS 1429.1

The 1.9/3.3kV aluminium XLPE 3-core SWA heavy duty screened power cable provides dependable electrical connections for urban power distribution networks, industrial facilities and underground power installations. It features compacted annealed aluminium conductors, TR-XLPE insulation, a heavy duty annealed copper wire screen, steel wire armour and a PVC or PVC/HDPE outer sheath.

Application

The 1.9/3.3kV aluminium XLPE 3-core SWA heavy duty screened power cable is designed for primary power supply applications in urban electrical distribution networks, industrial facilities and underground power distribution systems.

Furthermore, the compacted annealed aluminium conductors provide efficient electrical conductivity and reduced conductor weight compared with equivalent copper conductor constructions. The TR-XLPE (Tree-Retardant Cross-Linked Polyethylene) insulation provides enhanced resistance to water tree formation and insulation degradation.

In addition, the heavy duty annealed copper wire screen provides a path for earth fault currents, while the steel wire armour provides additional mechanical protection. The PVC or PVC/HDPE outer sheath construction provides environmental protection for underground power installations.

These cables are suitable for direct burial, underground duct installations, unenclosed installations where they are not subject to mechanical damage, and installations requiring cable gland termination.

Cable Construction

  • Standard: AS/NZS 1429.1:2000.

  • Rated Voltage: 1.9/3.3kV (1900/3300V).

  • Conductor: Compacted annealed aluminium.

  • Insulation: TR-XLPE (Tree-Retardant Cross-Linked Polyethylene).

  • Core Identification: Numbered cores.

  • Number of Cores: 3.

  • Screen: Heavy duty annealed copper wire screen.

  • Armour: SWA (Steel Wire Armour).

  • Outer Sheath: PVC 5V-90 or PVC 5V-90/HDPE.

  • Maximum Operating Temperature: 90°C.

  • Screen Fault Current Rating: Minimum 13.1kA for 1 second, without exceeding the conductor rating.

  • Sheath Marking: Manufacturer’s name (trademark) and type, production year/week or batch number, and metre markings.

  • Special Properties: Tree-retardant insulation, heavy duty copper wire screening, lightweight aluminium conductors and armoured construction.

  • Available Cross-Sections: 16 mm² to 300 mm² per core.

  • Installation Methods: Direct burial, underground ducts and suitable unenclosed installations.

Technical Data

The 1.9/3.3kV aluminium XLPE 3-core SWA heavy duty screened power cable features a rated voltage of 1900/3300V and a maximum operating temperature of 90°C. Its TR-XLPE insulation provides enhanced resistance to water tree formation, supporting long-term electrical performance in underground power distribution applications.

Moreover, the compacted annealed aluminium conductors provide a lightweight and economical solution for electrical power distribution. The heavy duty annealed copper wire screen features a specified minimum fault current rating of 13.1kA for 1 second, without exceeding the conductor rating.

The listed conductor cross-sections range from 16 mm² to 300 mm² per core, while the conductor diameter ranges from 4.9 mm to 20.8 mm.

Furthermore, the overall cable diameter ranges from 39.0 mm to 84.6 mm, and the approximate cable mass ranges from 2310 kg/km to 9930 kg/km.

The maximum DC conductor resistance at 20°C ranges from 0.100 Ω/km to 1.910 Ω/km.

Constructive Data Table

Cross-section (mm²) Conductor No. of Strands Conductor Dia. (mm) Minimum Overall Dia. (mm) Maximum Overall Dia. (mm) Max. DC Resistance at 20°C (Ω/km) Approximate Mass (kg/km)
16 7 4.9 39.0 43.8 1.910 2310
25 7 6.1 41.9 46.7 1.200 2590
35 7 7.0 44.0 48.8 0.868 2880
50 19 8.1 47.5 52.3 0.641 3640
70 19 9.8 51.8 56.7 0.443 4320
95 19 11.6 56.1 61.0 0.320 5020
120 19 12.9 59.2 64.1 0.253 5560
150 19 14.3 62.8 67.8 0.206 6330
185 36 16.0 66.6 71.6 0.164 6940
240 36 18.4 72.2 77.2 0.125 7900
300 36 20.8 79.5 84.6 0.100 9930

Technical note: All numerical table values and measurement units remain unchanged from the original datasheet. SWA is indicated in the product title, but armour wire dimensions and bedding construction are not specified separately. The PVC 5V-90/HDPE sheath configuration, applicable AS/NZS 1429.1 edition and achievable screen fault current rating for each conductor size should be verified before publishing.

Factory Overview


Packaging & Shipping


Frequently Asked Questions and Answers

Q:- What is the primary application of the 1.9/3.3kV aluminium XLPE 3-core SWA heavy duty screened cable?

A:- It is designed for primary power supply in urban electrical distribution networks, industrial power installations and underground power distribution systems.

Q:- What standard does the 1.9/3.3kV aluminium XLPE SWA power cable follow?

A:- The manufacturer specifies AS/NZS 1429.1:2000 in the product datasheet.

Q:- What is the rated voltage of the aluminium XLPE 3-core SWA power cable?

A:- The rated voltage is 1.9/3.3kV (1900/3300V).

Q:- What is the maximum operating temperature of the aluminium XLPE power cable?

A:- The maximum operating temperature is 90°C.

Q:- What type of conductor does the 3-core aluminium SWA power cable use?

A:- It uses compacted annealed aluminium conductors, providing efficient electrical conductivity, reduced conductor weight and an economical solution for power distribution applications.

Q:- What are the advantages of TR-XLPE insulation?

A:- TR-XLPE insulation provides enhanced resistance to water tree formation, helping reduce insulation degradation and improve long-term electrical reliability in underground power cable applications.

Q:- What is the fault current rating of the heavy duty copper wire screen?

A:- The manufacturer specifies a minimum screen fault current rating of 13.1kA for 1 second, provided that it does not exceed the conductor rating. The actual rating should be confirmed for the selected conductor cross-section.

Q:- What is the purpose of steel wire armour in the aluminium XLPE power cable?

A:- Steel wire armour provides additional mechanical protection against external forces and potential mechanical damage during installation and operation.

Q:- What outer sheath materials are available for the aluminium XLPE SWA cable?

A:- The manufacturer specifies PVC 5V-90 or PVC 5V-90/HDPE sheath options. The appropriate sheath construction should be selected according to the installation environment and project requirements.

Q:- Can the 1.9/3.3kV aluminium XLPE SWA heavy duty screened cable be installed directly underground?

A:- Yes, the manufacturer specifies suitability for direct burial and underground duct installations. Installation must comply with applicable electrical regulations, mechanical protection and thermal design requirements.

Reviews

There are no reviews yet.

Be the first to review “1.9/3.3kV Aluminium XLPE 3-Core SWA Heavy Duty Screened Power Cable – AS/NZS 1429.1”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS