Building Wire PVC 0.6/1kV – Single-Core Copper Conductor V-90 PVC Insulated Cable (AS/NZS 5000.1)
The 0.6/1kV single-core PVC building wire provides dependable electrical connections for protective earthing, switchboard wiring, control panel wiring and fixed electrical installations. It features a plain annealed copper conductor and V-90 PVC insulation.
Furthermore, it supports a rated voltage of 600/1000V and a maximum operating temperature of 75°C. Manufactured according to the listed AS/NZS 5000.1 standard, this single-core building wire is available in conductor cross-sections ranging from 0.5 mm² to 300 mm².
Its compact construction makes it suitable for fixed wiring within electrical enclosures, switchboards, control panels and apparatus where the cable is not accessible without the use of tools.
Application
Single-core PVC building wires 0.6/1kV provide reliable electrical connections for fixed wiring, protective earthing, switchboards and control panel applications in industrial and commercial electrical installations.
Furthermore, the plain annealed copper conductor provides efficient electrical conductivity, while the V-90 PVC insulation provides electrical insulation and thermal protection for fixed wiring applications.
In addition, these building wires are suitable for installation within electrical enclosures and apparatus where the cable is not accessible without the use of tools. Their compact single-core construction supports convenient cable routing and termination within electrical distribution equipment.
Cable Construction
-
Standard: AS/NZS 5000.1.
-
Rated Voltage: 0.6/1kV.
-
Conductor: Plain annealed copper stranded according to IEC 60228 Class 2, as specified in the datasheet.
-
Insulation: PVC V-90 (Polyvinyl Chloride).
-
Maximum Operating Temperature: 75°C.
-
Sheath Marking: Manufacturer’s name (trademark) and type, production year/week or batch number, and metre markings.
-
Special Properties: Compact single-core construction, efficient electrical conductivity and suitability for fixed wiring installations.
-
Cable Type: Single-core PVC insulated building wire.
-
Conductor Construction: Solid and stranded copper options, according to the construction table.
-
Available Cross-Sections: 0.5 mm² to 300 mm².
-
Installation Requirement: Fixed wiring within suitable enclosures or apparatus where the cable is not accessible without the use of tools.
Technical Data
The single-core PVC building wire features a rated voltage of 0.6/1kV and a maximum operating temperature of 75°C. Its V-90 PVC insulation provides electrical insulation for protective earthing, switchboard wiring and control panel applications.
Moreover, the plain annealed copper conductor provides efficient electrical conductivity for fixed electrical installations. The listed conductor cross-sections range from 0.5 mm² to 300 mm², with solid and stranded conductor configurations.
The insulation thickness ranges from 0.8 mm to 2.4 mm, while the overall cable diameter ranges from 2.4 mm to 27.3 mm.
Furthermore, the approximate cable mass ranges from 10 kg/km to 2960 kg/km. The maximum DC conductor resistance at 20°C ranges from 0.0601 Ω/km to 44.000 Ω/km.
Constructive Data Table
| Cross-section (mm²) | Conductor No. of Strands | Insulation Thickness (mm) | Minimum Overall Dia. (mm) | Maximum Overall Dia. (mm) | Max. DC Resistance at 20°C (Ω/km) | Approximate Mass (kg/km) |
|---|---|---|---|---|---|---|
| 0.5 | 1/0.79 | 0.8 | 2.4 | 2.5 | 44.000 | 10 |
| 1 | 1/1.13 | 0.8 | 2.8 | 2.9 | 18.100 | 16 |
| 1 | 7/0.42 | 0.8 | 2.8 | 2.9 | 19.200 | 15 |
| 1.5 | 7/0.5 | 0.8 | 3.1 | 3.2 | 13.600 | 20 |
| — | — | — | — | — | 7.410 | 32 |
| 4 | 7/0.85 | 1.0 | 4.5 | 4.6 | 4.610 | 51 |
| 6 | 7/1.04 | 1.0 | 5.1 | 5.2 | 3.080 | 71 |
| 10 | 7/1.35 | 1.0 | 6.0 | 6.2 | 1.830 | 111 |
| 16 | 7/1.70 | 1.0 | 6.9 | 7.1 | 1.150 | 170 |
| 25 | 19/1.35 | 1.2 | 8.4 | 8.6 | 0.727 | 260 |
| 35 | 19/1.53 | 1.2 | 9.4 | 9.6 | 0.524 | 350 |
| 50 | 19/1.78 | 1.4 | 10.9 | 11.1 | 0.387 | 480 |
| 70 | 19/2.14 | 1.4 | 12.4 | 12.6 | 0.268 | 670 |
| 95 | 37/1.78 | 1.6 | 15.2 | 15.5 | 0.193 | 960 |
| 120 | 19/2.94 | 1.6 | 17.3 | 17.6 | 0.153 | 1180 |
| 150 | 19/3.28 | 1.8 | 18.8 | 19.1 | 0.124 | 1440 |
| 300 | 37/3.28 | 2.4 | 26.9 | 27.3 | 0.0601 | 2960 |
Technical note: All visible numerical table values and measurement units remain unchanged from the original datasheet. The row containing 7.410 Ω/km and 32 kg/km appears to correspond to a 2.5 mm² conductor, but the remaining specifications are missing. These fields have been left blank rather than estimated. Additionally, the datasheet specifies IEC 60228 Class 2, although the table includes solid conductor constructions normally associated with Class 1. These details should be verified before publishing.
Factory Overview
Packaging & Shipping
Frequently Asked Questions and Answers
Q:- What is the primary application of the 0.6/1kV single-core PVC building wire?
A:- It is designed for separate earth conductors, switchboard wiring, control panel wiring and fixed electrical installations within suitable enclosures and apparatus.
Q:- What standard does the single-core PVC building wire follow?
A:- The manufacturer specifies AS/NZS 5000.1, an Australian and New Zealand standard for polymeric insulated electrical cables.
Q:- What is the rated voltage of the PVC building wire?
A:- The rated voltage is 0.6/1kV (600/1000V).
Q:- What is the maximum operating temperature of the single-core building wire?
A:- The maximum operating temperature is 75°C, as specified in the manufacturer’s datasheet.
Q:- What type of conductor does the PVC building wire use?
A:- It uses plain annealed copper conductors. The construction table includes solid and stranded conductor options, with IEC 60228 Class 2 specified for the stranded conductor construction.
Q:- What type of insulation does the single-core building wire feature?
A:- It features V-90 PVC (Polyvinyl Chloride) insulation, providing electrical insulation and thermal protection for fixed wiring applications.
Q:- What conductor cross-section sizes are available?
A:- The listed conductor cross-sections range from 0.5 mm² to 300 mm², accommodating various fixed wiring, earthing and electrical distribution requirements.
Q:- Can the single-core PVC building wire be used for protective earthing?
A:- Yes, the manufacturer identifies separate earth conductors as a suitable application. The insulation colour and conductor size must comply with applicable protective earthing requirements.
Q:- Is the PVC building wire suitable for switchboard and control panel wiring?
A:- Yes, its compact single-core construction and PVC insulation make it suitable for fixed wiring within switchboards, control panels and compatible electrical equipment.
Q:- Can the single-core PVC building wire be installed in exposed locations?
A:- The manufacturer specifies fixed wiring within enclosures or apparatus where the cable is not accessible without the use of tools. Exposed installations must comply with applicable wiring and mechanical protection requirements.




Reviews