Unscreened Fire Alarm Cable 12/80V – V-90HT PVC Insulated and Sheathed Cable (AS/NZS Standards)

The unscreened fire alarm cable provides dependable electrical connections for compatible fire alarm systems, detection circuits and low-voltage signalling applications. It features plain annealed stranded copper conductors, V-90HT PVC insulation and an easy-peel V-90HT PVC outer sheath.

Furthermore, it features a manufacturer-specified voltage rating of 12/80V and a maximum operating temperature of 105°C. Available in conductor cross-sections of 0.75 mm², 1.0 mm² and 1.5 mm², this fire alarm cable offers round and flat construction options for convenient installation.

Its easy-peel sheath makes it suitable for general wiring, conduit installations and commercial and industrial applications where the cable is protected against mechanical damage.

Application

Unscreened fire alarm cables provide reliable electrical connections for fire alarm systems, detection circuits, signalling equipment and low-voltage general wiring applications in commercial and industrial buildings.

Furthermore, the stranded plain annealed copper conductors provide efficient electrical conductivity. The V-90HT PVC insulation and outer sheath provide thermal and electrical protection for compatible low-voltage installations.

In addition, the easy-peel sheath design simplifies cable preparation, termination and installation. These cables are suitable for unenclosed wiring and conduit installations in commercial and industrial environments where they are not subject to mechanical damage.

Cable Construction

  • Standards: AS/NZS 5000, AS/NZS 1125, IEC 60228, IEC 60332-1, AS/NZS 3808.

  • Rated Voltage: 12/80V.

  • Conductor: Plain annealed copper stranded according to IEC 60228 Class 2, as specified in the datasheet.

  • Insulation: V-90HT PVC (Polyvinyl Chloride).

  • Sheath: V-90HT PVC.

  • Screening: Unscreened.

  • Maximum Operating Temperature: 105°C, as specified in the datasheet.

  • Sheath Marking: Manufacturer’s name (trademark) and type, production year/week or batch number, and metre markings.

  • Special Properties: Easy-peel outer sheath and convenient cable termination.

  • Cable Type: Unscreened low-voltage fire alarm cable.

  • Available Constructions: Round and flat cable designs.

  • Installation Requirement: Suitable for installations where the cable is not subject to mechanical damage.

Technical Data

The unscreened fire alarm cable features a manufacturer-specified voltage rating of 12/80V and a maximum operating temperature of 105°C. Its V-90HT PVC insulation and outer sheath provide electrical insulation and protection for low-voltage wiring applications.

Moreover, the listed conductor cross-sections range from 0.75 mm² to 1.5 mm². The insulation thickness ranges from 0.6 mm to 0.7 mm, while the outer sheath thickness ranges from 0.8 mm to 1.0 mm.

The round cable diameters range from 6.2 mm to 7.0 mm, while the flat cable dimensions range from 3.4 × 5.5 mm to 4.6 × 7.3 mm.

Furthermore, the approximate cable weight ranges from 40 kg/km to 100 kg/km. The maximum DC conductor resistance at 20°C ranges from 13.6 Ω/km to 26.0 Ω/km.

Constructive Data Table

Cross-section (mm²) Conductor No. of Strands Insulation Thickness (mm) Sheath Thickness (mm) Overall Diameter / Dimensions (mm) Max. DC Resistance at 20°C (Ω/km) Shielding Approx. Weight (kg/km)
1.0 7/0.4 0.6 0.9 6.2 21.2 / 50
1.5 7/0.5 0.7 1.0 7.0 13.6 / 70
0.75 24/0.2 0.6 0.8 3.7 × 6.0 26.0 / 40
0.75 24/0.2 0.6 0.8 3.4 × 5.5 26.0 / 40
1.0 7/0.4 0.6 0.9 4.3 × 6.7 21.2 / 60
1.5 7/0.5 0.7 1.0 4.6 × 7.3 13.6 / 100

Technical note: All numerical table values and measurement units remain unchanged from the original datasheet. The 12/80V voltage designation, 105°C operating temperature against the V-90HT material designation, and IEC 60228 Class 2 conductor classification for the 24/0.2 mm construction should be verified with the manufacturer. IEC 60332-1 relates to flame propagation testing and does not establish fire resistance or circuit integrity during a fire.

Factory Overview



Packaging & Shipping


Frequently Asked Questions and Answers

Q:- What is the primary application of the unscreened fire alarm cable?

A:- It is intended for compatible fire alarm systems, detection circuits, signalling equipment and low-voltage general wiring in commercial and industrial installations.

Q:- What standards does the unscreened fire alarm cable follow?

A:- The manufacturer lists AS/NZS 5000, AS/NZS 1125, IEC 60228, IEC 60332-1 and AS/NZS 3808 in the product datasheet.

Q:- What is the rated voltage of the unscreened fire alarm cable?

A:- The manufacturer specifies a voltage rating of 12/80V. The precise voltage designation should be confirmed with the manufacturer.

Q:- What is the maximum operating temperature of the fire alarm cable?

A:- The manufacturer specifies a maximum operating temperature of 105°C, subject to verification of the applicable material and operating conditions.

Q:- What type of conductor does the unscreened fire alarm cable use?

A:- It uses plain annealed stranded copper conductors, with IEC 60228 Class 2 specified in the product datasheet.

Q:- What type of insulation and outer sheath does the fire alarm cable feature?

A:- It features V-90HT PVC insulation and a V-90HT PVC outer sheath.

Q:- What are the advantages of the easy-peel outer sheath?

A:- The easy-peel outer sheath simplifies cable stripping, conductor preparation and termination, helping improve installation efficiency.

Q:- What conductor cross-section sizes are available?

A:- The listed conductor cross-section sizes are 0.75 mm², 1.0 mm² and 1.5 mm², with round and flat cable constructions available.

Q:- Is the unscreened fire alarm cable suitable for conduit installation?

A:- Yes, the manufacturer specifies suitability for unenclosed wiring and conduit installations in commercial and industrial environments where the cable is not subject to mechanical damage.

Q:- Is the unscreened fire alarm cable fire-resistant?

A:- The manufacturer lists IEC 60332-1, which relates to vertical flame propagation testing of a single insulated wire or cable. However, the supplied datasheet does not specify fire-resistance or circuit-integrity test compliance. Suitability for fire alarm circuits requiring continued operation during a fire must be verified separately.

Reviews

There are no reviews yet.

Be the first to review “Unscreened Fire Alarm Cable 12/80V – V-90HT PVC Insulated and Sheathed Cable (AS/NZS Standards)”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS