Bare Aluminum & ACSR Stranded Conductors – BDS EN 50182
The bare aluminum and aluminum steel reinforced (ACSR) stranded conductors deliver dependable overhead power transmission for exposed environments. Constructed with high-conductivity aluminum, and a galvanized steel core in the ACSR variants, they offer excellent tensile strength and minimal power loss. Because they comply with BDS EN 50182 standards and are available in various cross-sections, they provide a reliable solution for overhead electric power transmission systems.
Application
Bare aluminum and aluminum steel reinforced stranded conductors provide reliable overhead power transmission. Because they feature high-conductivity aluminum and, in the ACSR variants, a steel core for added strength, installers use them extensively in overhead electric power transmission networks. Furthermore, they are ideal for long spans and environments requiring high mechanical resilience. Consequently, they deliver consistent and efficient power distribution over long distances.
Cable construction
These conductors strictly adhere to BDS EN 50182 standards. The Type AL conductors are constructed from high-conductivity aluminum wires stranded together. The Type AL1/ST1A (ACSR) variants combine an aluminum outer layer with a galvanized steel core. The stranding patterns and conductor diameters are engineered to optimize both electrical conductivity and breaking load for overhead applications.
Technical Data
The conductors deliver consistent performance under specific conditions. For Type AL conductors, breaking loads range from 3.02 kN (16 mm²) to 82.47 kN (500 mm²), with electrical resistance at 20°C ranging from 1.798 Ω/km to 0.0579 Ω/km. For the ACSR conductors, breaking loads vary based on the steel core, ranging from 5.80 kN to 198.06 kN. The ACSR electrical resistance ranges from 1.876 Ω/km down to 0.0605 Ω/km. These specifications ensure optimal conductivity and mechanical resilience.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, stranding, weight, and electrical resistance information.
Construction data Type AL conductors
| Nominal cross-section | Stranding and wire diameter | Conductor diameter | Breaking load min. | Electrical resistance at 20°C, max | Weight of conductor, approx. |
|---|---|---|---|---|---|
| mm² | N x mm | mm | kN | Ω/km | kg/km |
| 16-AL1 | 7×1,70 | 5,10 | 3,02 | 1,798 | 43,2 |
| 25-AL1 | 7×2,10 | 6,30 | 4,48 | 1,181 | 66,3 |
| 35-AL1 | 7×2,50 | 7,50 | 6,01 | 0,8317 | 93,9 |
| 50-AL1 | 7×3,00 | 9,0 | 8,34 | 0,5794 | 132,9 |
| 70-AL1 | 19×2,10 | 10,5 | 11,85 | 0,4367 | 180,9 |
| 95-AL1 | 19×2,50 | 12,5 | 16,82 | 0,3068 | 256,3 |
| 120-AL1 | 19×2,80 | 14,0 | 19,89 | 0,2456 | 321,5 |
| 150-AL1 | 19×3,15 | 15,8 | 26,48 | 0,1960 | 405,7 |
| 185-AL1 | 37×2,50 | 17,5 | 30,34 | 0,1581 | 500,9 |
| 240-AL1 | 37×2,85 | 20,3 | 43,66 | 0,1193 | 671,1 |
| 300-AL1 | 61×2,50 | 22,5 | 52,40 | 0,0968 | 826,5 |
| 400-AL1 | 61×2,85 | 26,0 | 68,02 | 0,0723 | 1101,4 |
| 500-AL1 | 61×3,23 | 29,1 | 82,47 | 0,0579 | 1382,9 |
Construction data Type AL1/ST1A conductors
| Nominal cross-section | Stranding and wire diameter | Conductor diameter | Breaking load min. | Electrical resistance at 20°C, max | Weight Al | Weight St | Weight of conductor, approx. |
|---|---|---|---|---|---|---|---|
| mm² | N x mm | mm | kN | Ω/km | kg/km | kg/km | kg/km |
| 15-AL1/3-ST1A | 6×1,80+1×1,80 | 5,40 | 5,80 | 1,876 | 41,85 | 19,85 | 61,7 |
| 26-AL1/6-ST1A | 6×2,25+1×2,25 | 6,75 | 8,995 | 1,2012 | 65,39 | 31,01 | 96,4 |
| 28-AL1/6-ST1A | 6×2,50+1×2,50 | 7,50 | 11,32 | 0,9732 | 81,09 | 38,25 | 119,34 |
| 44-AL1/32-ST1A | 6×3,00+1×3,00 | 9,0 | 17,02 | 0,6794 | 121,35 | 79,25 | 200,6 |
| 48-AL1/8-ST1A | 6×3,20+1×3,20 | 9,60 | 16,24 | 0,5959 | 132,26 | 62,73 | 195 |
| 65-AL1/11-ST1A | 6×3,70+1×3,70 | 11,1 | 24,81 | 0,4224 | 192,38 | 87,05 | 279,43 |
| 70-AL1/11-ST1A | 28×1,85+7×1,44 | 11,7 | 26,27 | 0,4132 | 192,78 | 89,32 | 282,1 |
| 95-AL1/15-ST1A | 28×2,15+7×1,67 | 13,0 | 34,09 | 0,3060 | 260,35 | 120,14 | 380,49 |
| 106-AL1/17-ST1A | 14×3,10+19×2,25 | 17,5 | 105,82 | 0,2742 | 292,2 | 589,8 | 896 |
| 122-AL1/21-ST1A | 28×2,44+7×1,90 | 15,5 | 44,50 | 0,2376 | 335,32 | 155,51 | 490,83 |
| 123-AL1/7-ST1A | 28×2,44+7×1,90 | 14,3 | 32,88 | 0,2366 | 338,9 | 155,51 | 494,4 |
| 129-AL1/20-ST1A | 28×2,52+7×2,00 | 16,3 | 36,08 | 0,2230 | 353,09 | 187,37 | 540,16 |
| 144-AL1/24-ST1A | 28×2,60+7×2,10 | 17,1 | 53,67 | 0,2196 | 410,6 | 188,97 | 599,57 |
| 146-AL1/24-ST1A | 28×2,60+7×2,10 | 17,1 | 56,47 | 0,1944 | 391,4 | 206,59 | 598 |
| 166-AL1/28-ST1A | 28×2,80+7×2,25 | 19,0 | 65,27 | 0,1571 | 506,91 | 213,67 | 741,6 |
| 206-AL1/34-ST1A | 28×3,00+7×2,50 | 20,3 | 73,36 | 0,1381 | 576,75 | 269,07 | 843,84 |
| 216-AL1/34-ST1A | 28×3,20+7×2,50 | 21,0 | 78,87 | 0,1200 | 613,07 | 259,07 | 876,4 |
| 231-AL1/30-ST1A | 28×3,20+7×2,50 | 21,0 | 72,13 | 0,1290 | 636,44 | 233,87 | 870,31 |
| 243-AL1/39-ST1A | 28×3,45+7×2,68 | 21,8 | 85,12 | 0,1188 | 670,38 | 309,4 | 979,78 |
| 264-AL1/34-ST1A | 28×3,45+7×2,68 | 22,4 | 87,64 | 0,1066 | 757,29 | 255,84 | 1013,1 |
| 300-AL1/39-ST1A | 28×3,60+7×2,88 | 24,0 | 105,09 | 0,0949 | 839,19 | 287,07 | 1126,26 |
| 336-AL1/43-ST1A | 28×4,00+7×3,00 | 26,0 | 99,85 | 0,0776 | 874,41 | 325,24 | 1199,8 |
| 338-AL1/44-ST1A | 54×2,82+7×2,82 | 25,4 | 90,89 | 0,0993 | 937,4 | 388,87 | 1326,3 |
| 352-AL1/56-ST1A | 54×2,82+19×2,25 | 27,0 | 121,30 | 0,0758 | 1054,1 | 387,7 | 1441,8 |
| 380-AL1/57-ST1A | 54×2,88+7×2,88 | 25,9 | 108,02 | 0,0838 | 1028,56 | 386,74 | 1415,3 |
| 388-AL1/49-ST1A | 54×2,76+19×2,07 | 26,7 | 127,84 | 0,0675 | 967,7 | 303,7 | 1273,4 |
| 392-AL1/50-ST1A | 54×2,75+19×2,10 | 26,7 | 117,57 | 0,0731 | 1110,93 | 347,69 | 1458,5 |
| 418-AL1/45-ST1A | 54×2,80+7×2,80 | 28,2 | 126,51 | 0,0567 | 1186,38 | 399,1 | 1582,1 |
| 449-AL1/37-ST1A | 54×2,80+7×2,66 | 29,7 | 118,01 | 0,0626 | 1239,67 | 346,92 | 1586,58 |
| 490-AL1/64-ST1A | 54×2,80+7×3,40 | 28,7 | 150,81 | 0,0590 | 1353,92 | 497,38 | 1851,3 |
| 529-AL1/34-ST1A | 54×3,60+7×2,50 | 30,6 | 150,76 | 0,0608 | 1315,9 | 262,91 | 1578,8 |
| 511-AL1/45-ST1A | 54×3,60+7×2,66 | 30,7 | 131,31 | 0,0566 | 1410,47 | 354,83 | 1765,3 |
| 560-AL1/50-ST1A | 54×3,60+7×3,00 | 32,4 | 168,92 | 0,0550 | 1517,9 | 350,9 | 1670,2 |
| 570-AL1/90-ST1A | 61×3,50+19×2,50 | 33,2 | 135,36 | 0,0581 | 1618,7 | 934,4 | 2551,9 |
| 571-AL1/59-ST1A | 61×4,15+15×2,92 | 32,2 | 198,06 | 0,0506 | 1577,7 | 594,4 | 1887,3 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of these bare aluminum and ACSR stranded conductors?
A:- They are used for overhead electric power transmission systems, providing efficient and reliable power distribution over long distances.
Q:- What are the key benefits of the ACSR (steel-reinforced) conductors?
A:- The ACSR conductors combine an aluminum outer layer for high conductivity with a galvanized steel core for added mechanical strength, allowing for longer spans and higher tension.
Q:- What standard do these conductors follow?
A:- They strictly adhere to BDS EN 50182 standards.
Q:- What materials are these conductors made of?
A:- Type AL conductors are made of bare aluminum, while Type AL1/ST1A (ACSR) conductors are made of aluminum wires stranded around a galvanized steel core.
Q:- What is the smallest cross-section available for bare aluminum conductors?
A:- The smallest bare aluminum cross-section is 16 mm², with a stranding of 7×1.70 and a breaking load of 3.02 kN.
Q:- What is the largest cross-section available?
A:- The largest bare aluminum cross-section shown is 500 mm² (61×3.23), and the largest ACSR is 570 mm² (61×3.50+19×2.50).
Q:- How is the breaking load specified?
A:- The breaking load is specified in kilonewtons (kN) for each nominal cross-section, ensuring the conductor can withstand mechanical stress in overhead applications.
Q:- How does the electrical resistance change between bare aluminum and ACSR conductors?
A:- Bare aluminum resistance ranges from 1.798 Ω/km down to 0.0579 Ω/km. ACSR resistance ranges from 1.876 Ω/km down to 0.0506 Ω/km.
Q:- Is the stranding pattern consistent across all sizes?
A:- No, the number of wires and their diameter increase with the nominal cross-section to optimize breaking load and electrical conductivity.
Q:- What is the weight difference between bare aluminum and ACSR conductors?
A:- ACSR conductors are heavier due to the steel core. For example, a 500 mm² bare aluminum conductor weighs approx. 1382.9 kg/km, while a 570 mm² ACSR conductor weighs approx. 2551.9 kg/km.




Reviews