2XSH / (N)2XSH 0.6/1 kV Halogen-Free Flame Retardant Cable – VDE 0276-604
The 2XSH and (N)2XSH 0.6/1 kV cables deliver dependable power distribution for safety-critical environments like power stations, airports, and public buildings. Constructed with copper conductors, XLPE insulation, a copper wire or tape screen, and a black halogen-free flame retardant outer sheath, they offer exceptional fire safety with low smoke and corrosion emissions. Because they meet VDE 0276-604 and IEC 60502-1 standards and are CE/RoHS compliant, they provide a safe and reliable solution for installations indoors, in air, or in concrete.
Application
2XSH and (N)2XSH cables provide reliable power distribution with low halogen fire smoke emission and corrosion at fire conditions. Because of these critical safety features, installers use them in electrical installations for a nominal voltage of 0.6/1 kV. Furthermore, they are essential for important objects like power stations (nuclear, thermal), transformer substations, metro systems, and airports. Additionally, they are ideal for public buildings, hospitals, theaters, cinemas, and commercial centers where the safety of people and material values must be guaranteed. The cables can be laid indoors, in air, or in concrete. However, direct laying underground or in water is not allowed.
Cable construction
This cable strictly adheres to VDE 0276-604 (HD 604 S1) and IEC 60502-1 standards. It features copper wires according to IEC 60228 / VDE 0295 class 1 or 2. The insulation uses an XLPE compound 2X11 (DIX8) according to VDE 0276-604. Core identification follows VDE 0276-604 and VDE 0293. A halogen-free compound forms the inner sheath. The metal screen consists of Cu wires for the 2XSsH variant or Cu tapes for the 2XSH variant. Finally, a black halogen-free compound flame retardant type HM4 (LTS 1) sheath protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance according to VDE 0295 (IEC60228) class 1 or 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds (overload current). It operates at a nominal voltage of 0.6/1 kV, while the highest system voltage is no more than 1.2 kV. Test voltage is AC – 5 min between cores at 3.5 kV. Installers must respect a minimum bending radius of 6 times the cable diameter (6x D cable). The temperature of laying is no less than 0 °C. The temperature of explosion is -30 to 70 °C. Testing follows IEC 60502-1 and VDE 0276-604 / VDE 0472-804 / (IEC 332-3/C and B). The corrosion of combustion gases and conductivity has a pH of min. 4.3 and max. 100 S/cm. The density of smoke gases follows VDE 0472-816 (IEC 61034-1 and 2).
Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are black or yellow/green. Double core cables feature black and blue, or yellow/green and black. 3-core cables use black, blue, and brown, or yellow/green, blue, and brown. 4-core cables use black, blue, brown, and black, or yellow/green, brown, black, and grey. 5-core cables use black, blue, brown, black, and black, or yellow/green, blue, brown, black, and grey. Multiple core cables use black with number marks on cores or black with number marks on cores and a yellow/green core in the outer cover.
Constructive Data Table
The specific construction data table for 2XSH and 2XSsH is not provided in the source image. Please contact us for detailed sizing and weight specifications upon request.
Factory Overview
Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the 2XSH and (N)2XSH cables?
A:- They are used in electrical installations for a nominal voltage of 0.6/1 kV, particularly in safety-critical environments like power stations, metro systems, airports, hospitals, and public buildings.
Q:- What are the key fire safety features of this cable?
A:- It is halogen-free, flame retardant, and emits low smoke and low-corrosion gases during a fire, passing the IEC 332-3/C and B tests.
Q:- What standards does the cable construction follow?
A:- The construction adheres to VDE 0276-604 (HD 604 S1) and IEC 60502-1 standards, and the conductor complies with IEC 60228 / VDE 0295 class 1 or 2.
Q:- What type of conductor and insulation does it use?
A:- It uses copper wires with an XLPE compound 2X11 (DIX8) insulation according to VDE 0276-604.
Q:- What is the difference between the 2XSH and 2XSsH variants?
A:- The 2XSsH variant uses a metal screen of Cu wires, while the 2XSH variant uses a metal screen of Cu tapes.
Q:- Where can this cable be installed?
A:- The cables can be laid indoors, in air, or in concrete. However, direct laying underground or in water is not allowed.
Q:- What is the rated voltage and maximum conductor temperature?
A:- The rated voltage is 0.6/1 kV, and the continuous operating temperature is 90°C.
Q:- What is the short-circuit temperature limit?
A:- It can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.
Q:- What is the test voltage for this cable?
A:- The test voltage is AC – 5 min between cores at 3.5 kV.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 6 times the cable diameter (6x D cable).