2XSEY-FR & A2XSEY-FR 6/10 kV Flame Retardant Three-Core Cable – IEC 60502-2

The 2XSEY-FR and A2XSEY-FR 6/10 kV cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, and flame retardant PVC sheaths, they offer exceptional fire safety and mechanical protection. Because they meet IEC 60502-2 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
2XSEY-FR and A2XSEY-FR medium voltage three-core cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with a nominal voltage of Uo/U 6/10 kV and a frequency of 50 Hz. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for fixed assembly in distribution installations, cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles. However, installers should not lay them directly underground or in water, and they should not be laid near reactor stations.

Cable construction
This cable strictly adheres to IEC 60502-2 and IEC 60332-3 standards. It features copper and aluminum stranded compacted wires according to IEC 60228. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. The metal screen can be either -i-option (Cu tapes laid with overlap over each phase) or -ii-option (Cu wires laid concentrically). The cable assembly features three insulated and screened phases twisted with fillers and a tape support. The inner sheath uses an extruded PVC compound flame retardant. The sheath can be either -i-option (fillings and tapes – tool B and C, flame retardant PVC) or -ii-option (fillings, tapes, and metal screen – tool A, flame retardant black PVC). Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC 60228. The maximum conductor temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of Uo/U 6/10 kV, while the highest system voltage is 6/10 kV and 12 kV. Test voltage is AC – 5 min for 6/10 kV (21 kV), or DC (-) – 15 min (6/10 kV). The minimum bending radius is 15 times the cable diameter. The temperature of laying is no less than -5 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502. Furthermore, it passes the flame retardancy test according to EC 332-3, Category A.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XSEY-FR, A2XSEY-FR 6/10 kV

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XSEY-FR Mass of Cu approx. 2XSEY-FR Cable weight approx. A2XSEY-FR Mass of Al approx. A2XSEY-FR Cable weight approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
6/10 kV
3×35 m/16 3,4 2,5 16 47,6 1010 3276 298 2223
3×50 m/16 3,4 2,6 16 50,3 1363 3834 404 2668
3×70 m/16 3,4 2,8 16 54,8 1968 4770 584 3100
3×95 m/16 3,4 2,8 16 58,4 2730 5681 809 3575
3×120 m/16 3,4 2,9 16 61,6 3440 6953 1023 4023
3×150 m/25 3,4 3,0 25 64,4 4245 8627 1257 4679
3×185 m/25 3,4 3,1 25 68,6 5310 10102 1575 5373
3×240 m/25 3,4 3,4 25 74,3 6981 11963 2071 7331

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XSEY-FR and A2XSEY-FR cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available at a nominal voltage level of Uo/U 6/10 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 and IEC 60332-3 standards, and the conductor complies with IEC 60228.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What are the key fire safety features of this cable?
A:- It features a flame retardant PVC inner sheath and a flame retardant PVC outer sheath, passing the EC 332-3 Category A flame test.

Q:- What are the installation restrictions for this cable?
A:- It should not be laid directly underground or in water, and it should not be laid near reactor stations.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the test voltage for this cable?
A:- Test voltage is AC – 5 min for 6/10 kV (21 kV), or DC (-) – 15 min.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The temperature of laying is no less than -5°C, and the temperature of explosion is -30 to 50°C.