NFA2X / SAH-VO 0.6/1 kV Self-Supporting Overhead Cable – VDE 0276-625/4F
The NFA2X and SAH-VO 0.6/1 kV cables deliver dependable power transmission and distribution for low voltage overhead networks. Constructed with aluminum conductors, XLPE insulation, and a self-supporting bundle design, they offer excellent performance for permanent suspension on facades and trees. Because they meet VDE 0276-625/4F standards, they provide a reliable solution for crossing forest areas without cutting.
Application
NFA2X and SAH-VO power cables provide reliable transmission, distribution, and supply of electrical power in low voltage networks. They operate efficiently at a nominal voltage of 0.6/1 kV. Because these self-supporting cables are designed for overhead lines, installers use them for permanent suspension on facades and trees. Furthermore, they allow crossing of forest areas without cutting and maintenance openings in the wood. Additionally, the suspension and support of the whole bundle is carried out by the phase (basic) insulated current-conductive core.
Cable construction
This cable strictly adheres to VDE 0276-625/4F, FN Kl 02.003 standards. It features Al stranded compacted or non-compacted conductors according to VDE 0276-625 for the phase (main) M and additional lighting R. The insulation uses XLPE with a minimum 2% carbon black content (type TXC-2). The cable lay-up constructions are twisted into a bundle, which includes phase (main) insulated cores (M) and one, two, or three additional reduced insulated cores (R). The color is black, and the marking is NFA2X to VDE 0276-625 and SAH-VO to FN Kl 02.003.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains an operating temperature of 80 °C. The short-circuit temperature is 130 °C. It operates at a nominal voltage Uo/U of 0.6/1 kV, while the highest system voltage AC is not more than 1.2 kV. Test voltage AC is 4 kV for 5 minutes and DC is 10 kV for 15 minutes. The minimum bending radius is 18 times the cable diameter. The minimum temperature of laying is no less than -10 °C, and the recommended installation temperature is 15 °C. Conductor resistance at 20 °C varies by size: 16-1.91 Ω/km, 25-1.20 Ω/km, 35-0.868 Ω/km, 50-0.641 Ω/km, 70-0.443 Ω/km, and 95-0.320 Ω/km. Breaking strength varies by size: 35-0.868 kN, 50-6.41 kN, 70-8.45 kN, and 95-15.58 kN.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and current carrying capacity.
Construction data NFA2X / SAH-VO 0.6/1 kV
| Number of conductors and nom. cross section | Diameter of bundle approx. | Mass approx. | Cable weight approx. | Allowed current in power supply networks | Allowed current at short-circuit |
|---|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | A | kA |
| 1×16 | 9,0 | 44 | 74 | 81 | 0,8 |
| 1×25 | 10,0 | 67 | 103 | 107 | 1,3 |
| 1×35 | 11,0 | 87 | 133 | 132 | 1,9 |
| 1×50 | 12,5 | 137 | 183 | 162 | 2,7 |
| 1×70 | 14,0 | 187 | 248 | 205 | 3,8 |
| 1×95 | 16,0 | 287 | 333 | 243 | 5,2 |
| 2×16 | 18,0 | 91 | 152 | 81 | 0,8 |
| 2×25 | 20,0 | 139 | 210 | 107 | 1,3 |
| 2×35 | 22,0 | 196 | 272 | 132 | 1,9 |
| 2×50 | 25,0 | 281 | 277 | 162 | 2,7 |
| 4×16 | 19,0 | 181 | 303 | 81 | 0,8 |
| 4×25 | 20,0 | 278 | 421 | 107 | 1,3 |
| 4×35 | 25,0 | 387 | 543 | 132 | 1,9 |
| 4×50 | 28,0 | 582 | 731 | 162 | 2,7 |
| 4×70 | 32,0 | 784 | 986 | 205 | 3,8 |
| 4×95 | 44,0 | 1091 | 1358 | 243 | 5,2 |
| 4×25+1×16 | 25,0 | 323 | 496 | 107 | 1,3 |
| 4×25+2×16 | 28,0 | 368 | 572 | 107 | 1,3 |
| 4×35+1×16 | 28,0 | 442 | 619 | 132 | 1,9 |
| 4×35+2×16 | 31,0 | 487 | 695 | 132 | 1,9 |
| 4×35+2×25 | 32,0 | 535 | 754 | 132 | 1,9 |
| 4×50+1×16 | 30,0 | 607 | 821 | 162 | 2,7 |
| 4×50+2×16 | 31,0 | 631 | 858 | 162 | 2,7 |
| 4×50+2×25 | 35,0 | 700 | 964 | 162 | 2,7 |
| 4×50+2×35 | 36,0 | 760 | 1025 | 162 | 2,7 |
| 4×70+1×16 | 35,0 | 810 | 1081 | 205 | 3,8 |
| 4×70+2×16 | 38,0 | 855 | 1137 | 205 | 3,8 |
| 4×70+2×25 | 35,0 | 834 | 1091 | 205 | 3,8 |
| 4×70+2×35 | 38,0 | 903 | 1196 | 205 | 3,8 |
| 4×95+1×16 | 40,0 | 907 | 1206 | 205 | 3,8 |
| 4×95+2×35 | 40,0 | 963 | 1257 | 205 | 3,8 |
| 4×95+1×16 | 41,0 | 1136 | 1434 | 245 | 5,2 |
| 4×95+2×16 | 44,0 | 1181 | 1510 | 245 | 5,2 |
| 4×95+1×25 | 42,0 | 1160 | 1463 | 245 | 5,2 |
| 4×95+2×25 | 44,0 | 1210 | 1518 | 245 | 5,2 |
| 4×95+1×35 | 42,0 | 1190 | 1494 | 245 | 5,2 |
| 4×95+2×35 | 46,0 | 1289 | 1630 | 245 | 5,2 |
Note: Other core configuration and special constructions manufactured upon request.
Factory Overview
Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the NFA2X / SAH-VO cable?
A:- It is used for transmission, distribution, and supply of electrical power in low voltage networks, specifically designed for overhead lines and permanent suspension on facades and trees.
Q:- What is the advantage of the self-supporting design?
A:- The design allows crossing of forest areas without cutting and maintenance openings in the wood, as the suspension and support are carried out by the phase (basic) insulated current-conductive core.
Q:- What standards does the cable construction follow?
A:- The construction adheres to VDE 0276-625/4F and FN Kl 02.003 standards.
Q:- What type of conductor and insulation does it use?
A:- It uses Al stranded compacted or non-compacted conductors (M and R) according to VDE 0276-625 and XLPE insulation with minimum 2% carbon black content (type TXC-2).
Q:- What is the nominal voltage and highest system voltage?
A:- The nominal voltage Uo/U is 0.6/1 kV, and the highest system voltage AC is not more than 1.2 kV.
Q:- What are the operating and short-circuit temperatures?
A:- The operating temperature is 80°C, and the short-circuit temperature is 130°C.
Q:- What is the test voltage for this cable?
A:- Test voltage AC is 4 kV for 5 minutes, and DC is 10 kV for 15 minutes.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 18 times the cable diameter (18x D cable).
Q:- What are the temperature limits for installation?
A:- The minimum temperature of laying is no less than -10°C, and the recommended installation temperature is 15°C.
Q:- How does the conductor resistance change with cross-section size?
A:- Conductor resistance at 20 °C varies: 16mm² is 1.91 Ω/km, 25mm² is 1.20 Ω/km, 35mm² is 0.868 Ω/km, 50mm² is 0.641 Ω/km, 70mm² is 0.443 Ω/km, and 95mm² is 0.320 Ω/km.


Reviews