U 1000 R2V 0.6/1 kV XLPE Copper Power Cable – NFC 32-321
The U 1000 R2V 0.6/1 kV cable delivers dependable power distribution for industrial installations and urban networks. Constructed with copper conductors, XLPE insulation, and a black PVC outer sheath, it offers excellent thermal and mechanical protection. Because it meets NFC 32-321 standards and is RoHS compliant, it provides a safe and reliable solution for cable ducts, tunnels, and outdoor installations under shelters.
Application
U 1000 R2V cables provide reliable power distribution and supply for consumers in industrial installations and urban networks. They operate efficiently with a nominal voltage of 0.6/1 kV and a frequency of 50 Hz. Because of their robust design, installers use them for fixed indoor assembly in cable ducts, tunnels, and conduits. Furthermore, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters. Consequently, they deliver consistent performance provided the conditions for the determined type of cable are met.
Cable construction
This cable strictly adheres to NFC 32-321 standards. It features copper wires that comply with NFC 32-321 (IEC 60228). The conductors range from class 1 for 1.5 to 18mm², class 2 for 1.5 to 500mm², and class 2 from 50 to 240mm². The insulation uses an XLPE compound for superior thermal resistance. Additionally, a tape or extrusion forms the inner sheath. Finally, a black PVC compound sheath protects the entire assembly. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to NFC 32-321. The operating temperature reaches a maximum of 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of 0.6/1 kV, while the highest system voltage is 1.2 kV. The temperature range for laying, installing, explosion, and storage is -5 °C to +60 °C, while the operating range is -25 °C to +70 °C. Installers must respect a minimum bending radius of 10 times the cable diameter.
Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are black or yellow/green. Double core cables feature blue and brown, or yellow-green and black. Multi-core configurations include specific color sequences for easy identification.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data U 1000 R2V 0.6/1 kV
| Number of conductors and nominal cross section | Shape | Outer diameter approx. | Cu weight | Cable weight approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 1×1,0 | rm | 9,2 | 9 | 147 |
| 1×1,5 | rm | 9,2 | 14 | 147 |
| 1×2,5 | rm | 9,2 | 23 | 164 |
| 1×6 | rm | 13,5 | 325 | 396 |
| 1×10 | rm | 15,0 | 460 | 559 |
| 1×16 | rm | 17,0 | 648 | 738 |
| 1×25 | rm | 19,0 | 889 | 990 |
| 1×35 | rm | 21,0 | 1120 | 1235 |
| 1×50 | rm | 23,0 | 1578 | 1755 |
| 1×70 | rm | 25,5 | 2178 | 2423 |
| 1×95 | rm | 28,5 | 2285 | 2370 |
| 1×120 | rm | 28,5 | ||
| 2×1,5 | rm | 8,7 | 28 | 110 |
| 2×2,5 | rm | 10,5 | 46 | 173 |
| 2×4 | rm | 11,5 | 75 | 223 |
| 2×6 | rm | 12,5 | 110 | 295 |
| 2×10 | rm | 15,0 | 188 | 480 |
| 2×16 | rm | 20,3 | 303 | 585 |
| 3×1,5 | rm | 10,1 | 42 | 160 |
| 3×2,5 | rm | 11,0 | 69 | 202 |
| 3×4 | rm | 12,0 | 112 | 290 |
| 3×6 | rm | 13,2 | 165 | 352 |
| 3×10 | rm | 14,9 | 275 | 498 |
| 3×16 | rm | 17,0 | 450 | 720 |
| 3×25 | rm | 21,5 | 700 | 1085 |
| 3×35 | rm | 23,5 | 959 | 1435 |
| 3×50 | rm | 27,0 | 1350 | 1930 |
| 3×70 | rm | 30,5 | 1862 | 2800 |
| 3×95 | rm | 35,5 | 2565 | 3590 |
| 3×120 | rm | 38,5 | 3274 | 4380 |
| 3×150 | rm | 42,0 | 4193 | 5440 |
| 3×185 | rm | 48,0 | 5160 | 6604 |
| 3×240 | rm | 55,0 | 6760 | 8612 |
| 3×1,5 | re | 10,1 | 42 | 160 |
| 3×2,5 | re | 11,0 | 69 | 202 |
| 3×4 | re | 13,0 | 148 | 330 |
| 3×6 | re | 13,2 | 162 | 357 |
| 3×10 | re | 15,5 | 270 | 451 |
| 3×16 | re | 17,0 | 432 | 697 |
| 3×185+35 | sm | 48,5 | 5170 | 6830 |
| 3×50+50 | sm | 28,5 | 1755 | 2380 |
| 3×150+70 | sm | 42,8 | 4151 | 5710 |
| 3×120+70 | sm | 40,0 | 3410 | 4677 |
| 3×185+95 | sm | 50,3 | 5338 | 7006 |
| 3×240+95 | sm | 51,8 | 5805 | 7086 |
| 3×240+95 | sm | 54,8 | 7605 | 9241 |
| 4×1,5 | re | 10,3 | 58 | 186 |
| 4×2,5 | re | 12,7 | 95 | 296 |
| 4×6 | re | 13,2 | 146 | 312 |
| 4×10 | re | 14,3 | 218 | 416 |
| 4×16 | re | 18,5 | 385 | 588 |
| 4×25 | re | 18,2 | 592 | 888 |
| 4×35 | re | 22,6 | 925 | 1310 |
| 4×1,5 | re | 10,8 | 55 | 182 |
| 4×2,5 | re | 11,6 | 92 | 236 |
| 4×4 | re | 13,2 | 149 | 296 |
| 4×6 | re | 14,3 | 218 | 418 |
| 4×10 | re | 16,5 | 363 | 605 |
| 4×16 | re | 19,3 | 565 | 888 |
| 4×25 | re | 22,6 | 925 | 1310 |
| 4×35 | re | 25,3 | 1303 | 1730 |
| 4×50 | re | 29,7 | 1857 | 2290 |
| 4×70 | re | 34,7 | 2601 | 3240 |
| 4×95 | re | 39,0 | 3520 | 4310 |
| 4×120 | re | 45,0 | 4467 | 5440 |
| 4×150 | re | 49,0 | 5575 | 6650 |
| 4×185 | re | 55,5 | 6860 | 8400 |
| 4×240 | re | 62,1 | 8829 | 10687 |
| 5×1,5 | re | 11,6 | 55 | 182 |
| 5×2,5 | re | 12,7 | 95 | 297 |
| 5×4 | re | 13,2 | 146 | 312 |
| 5×6 | re | 14,3 | 218 | 418 |
| 5×10 | re | 18,2 | 383 | 653 |
| 5×16 | re | 22,2 | 592 | 888 |
| 5×25 | re | 25,3 | 1165 | 1585 |
| 5×1,5 | re | 12,5 | 96 | 230 |
| 7×1,5 | re | 11,7 | 96 | 230 |
| 10×1,5 | re | 13,7 | 110 | 260 |
| 12×1,5 | re | 14,3 | 140 | 317 |
| 14×1,5 | re | 15,4 | 161 | 315 |
| 16×1,5 | re | 16,5 | 195 | 403 |
| 19×1,5 | re | 18,7 | 260 | 511 |
| 20×1,5 | re | 23,7 | 260 | 700 |
| 24×1,5 | re | 24,5 | 306 | 748 |
| 37×1,5 | re | 24,8 | 506 | 890 |
| 7×2,5 | re | 13,7 | 160 | 312 |
| 10×2,5 | re | 17,9 | 222 | 350 |
| 12×2,5 | re | 17,9 | 227 | 427 |
| 14×2,5 | re | 18,7 | 320 | 545 |
| 19×2,5 | re | 20,9 | 435 | 701 |
| 24×2,5 | re | 25,3 | 540 | 1042 |
| 30×2,5 | re | 27,5 | 685 | 1045 |
| 37×2,5 | re | 25,3 | 845 | 1247 |
Note: Other core configuration and special constructions manufactured upon request.
Factory Overview
Packaging & Shipping


Frequently asked questions and answer
Q:- What is the primary application of the U 1000 R2V cable?
A:- It is used for the distribution and supply of consumers with electrical power with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks.
Q:- Where can this cable be installed?
A:- It is suitable for fixed indoor assembly in cable ducts, tunnels and conduits, on shelves and grilles, directly underground in ditch and outdoor under shelters.
Q:- What standards does the cable construction follow?
A:- The construction adheres to NFC 32-321 standards, and the conductor complies with NFC 32-321 (IEC 60228).
Q:- What type of conductor and insulation does it use?
A:- It uses Cu wires for the conductor and XLPE compound for insulation.
Q:- What is the nominal voltage and highest system voltage?
A:- The nominal voltage Uo/U is 0.6/1 kV, and the highest system voltage is 1.2 kV.
Q:- What are the maximum continuous and short circuit temperatures?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.
Q:- What is the overload temperature capacity?
A:- It can withstand an overload temperature of 130°C for 100% per year maximum.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter (10 x D cable).
Q:- What are the temperature limits for laying and operation?
A:- The temperature range for laying and installing is -5°C to +60°C, while the operating temperature range is -25°C to +70°C.
Q:- What type of outer sheath protects the cable?
A:- A black PVC compound sheath protects the entire cable assembly.


Reviews