NYY-O & NYY-J 0.6/1 kV Low Voltage Power Cable – RoHS Compliant

The NYY-O and NYY-J 0.6/1 kV cables deliver heavy-duty power distribution for industrial and secondary network applications. Constructed with solid or multi-strand copper conductors, PVC insulation, and a black PVC outer sheath, they offer exceptional durability. Because they are RoHS and CE compliant, they provide a safe and reliable solution for outdoor, underground, and in-water installations.

Application
NYY cables provide reliable power distribution in power plants, industrial settings, and switching installations. They also excel in secondary distribution networks. Because of their robust design, installers prefer them for outdoor applications, indoor installations, open air, underground, and even in water. However, you should not use them where mechanical damage is anticipated.

Cable design
This cable strictly adheres to VDE 0276 part 603 standards. It features solid or multi-strand copper wires (class 1 or 2) that comply with VDE 0295 (IEC 60228). The insulation uses PVC type DIV4 according to VDE0276, while core identification follows VDE 0293. Additionally, a filling compound forms the inner sheath. Finally, a black PVC type DMV5 sheath (acc. VDE 0276) protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to VDE 0295 class 1 or 2 (IEC 60228). The maximum conductor temperature reaches 70 °C. During a short circuit, it can withstand 160 °C for no more than 5 seconds. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of AC – 4 kV at 50 Hz. Installers must respect a minimum bending radius of 15 times the cable diameter for multi-core cables, or 12 times for single-core cables. The temperature of operation ranges from -30 °C to +50 °C. Furthermore, it passes the flame test according to VDE 0472 part 804 class B (IEC 332 part 1).

Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are either black or yellow/green. Double core cables feature blue and brown, or yellow-green and black.

Multi-Core Color Configurations

  • 3-core: brown, black, grey, or yellow/green, blue, brown

  • 4-core: blue, brown, black, grey or yellow/green, brown, black, grey

  • 5-core: blue, brown, black, grey, black or yellow/green, blue, brown, black, grey

  • Multiple core: black with number mark on cores, or black with number mark on cores and yellow/green core in the outer cover

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information regarding the NYY-O and NYY-J constructions.

Number of conductors and nominal cross section Shape Outer diameter approx. Cu weight approx. Cable weight approx.
N x mm² mm kg/km kg/km
1 x 1,5 re 5,7 14 50
1 x 2,5 re 6,4 23 65
1 x 4,0 re 6,9 37 87
1 x 6,0 re 7,6 56 110
1 x 10,0 re 8,7 94 165
1 x 16,0 rm 10,1 153 237
2 x 1,5 re 9,3 28 140
2 x 2,5 re 10,5 46 175
2 x 4,0 re 11,9 75 235
2 x 6,0 re 12,9 112 297
2 x 10,0 re 16,2 188 487
2 x 16,0 rm 19,0 307 696
2 x 25,0 rm 22,7 485 1036
2 x 35,0 rm 25,8 673 1370
3 x 1,5 re 9,8 43 145
3 x 2,5 re 11,0 70 204
3 x 4,0 re 12,5 112 279
3 x 6,0 re 13,8 168 364
3 x 10,0 re 16,7 282 571
3 x 16,0 rm 19,9 460 849
3 x 25,0 rm 24,1 728 1270
3 x 35,0 rm 26,7 1010 1656
4 x 1,5 re 10,3 57 176
4 x 2,5 re 11,9 93 242
4 x 4,0 re 14,0 149 352
4 x 6,0 re 15,2 223 454
4 x 10,0 re 18,2 376 703
4 x 16,0 rm 21,8 614 1051
4 x 25,0 rm 26,6 970 1603
4 x 35,0 rm 29,3 1346 2059
5 x 1,5 re 10,9 71 207
5 x 2,5 re 12,6 116 287
5 x 4,0 re 15,2 187 433
5 x 6,0 re 16,5 279 541
5 x 10,0 re 19,9 470 844
5 x 16,0 rm 24,3 767 1268
5 x 25,0 rm 29,2 1213 1934
5 x 35,0 rm 32,4 1683 2536
7 x 1,5 re 11,8 100 250
7 x 2,5 re 14,0 163 366
10 x 1,5 re 14,9 142 400
12 x 1,5 re 15,3 171 458

Number of wires and nominal cross section Shape Outer diameter approx. Copper weight approx. Cable weight approx.
N x mm² mm kg/km kg/km
1 x 1,5 re 7,1 14 63
1 x 2,5 re 7,8 23 80
1 x 4,0 re 8,4 37 104
1 x 6,0 re 8,9 56 128
1 x 10,0 re 9,9 94 183
1 x 16,0 re 10,7 149 249
1 x 25,0 rm 12,7 243 359
1 x 35,0 rm 13,9 337 463
1 x 50,0 rm 15,6 480 633
1 x 70,0 rm 17,1 656 817
1 x 95,0 rm 19,4 911 1092
1 x 120,0 rm 20,9 1121 1326
1 x 150,0 rm 22,7 1415 1627
1 x 185,0 rm 25,0 1770 2013
1 x 240,0 rm 27,8 2273 2553
1 x 300,0 rm 30,7 2872 3200
1 x 400,0 rm 34,1 3892 4148
1 x 500,0 rm 38,1 4828 5132
2 x 1,5 re 11,2 28 132
2 x 2,5 re 12,9 46 155
2 x 4,0 re 14,9 75 215
2 x 6,0 re 15,9 112 236
2 x 10,0 re 17,5 188 306
2 x 16,0 rm 19,4 298 456
2 x 25,0 rm 22,5 498 676
2 x 35,0 rm 25,7 673 1301
2 x 50,0 rm 28,9 958 1690
2 x 70,0 rm 31,4 1319 2047
2 x 95,0 rm 38,0 1822 3033
3 x 1,5 re 12,1 43 201
3 x 2,5 re 12,9 70 247
3 x 4,0 re 15,0 112 350
3 x 6,0 re 16,1 168 436
3 x 10,0 re 18,0 252 556
3 x 16,0 rm 20,1 447 828
3 x 25,0 rm 24,4 728 1250
3 x 35,0 rm 26,7 986 1424
3 x 50,0 rm 30,4 1363 2139
3 x 70,0 sm 29,2 1968 2380
3 x 95,0 sm 32,9 2685 3082
3 x 120,0 sm 35,4 3460 3653
3 x 150,0 sm 39,2 4245 4687
3 x 185,0 sm 43,5 5227 5706
3 x 240,0 sm 48,1 6981 7089
3 x 300,0 sm 53,5 8681 9702
3 x 400,0 sm 59,7 11516 11752
3 x 500,0 sm 62,5 1505 2091
3 x 50,0+25 sm 29,2 1595 2091
3 x 70,0+35 sm 33,4 2300 2800
3 x 95,0+50 sm 37,9 3330 3770
3 x 120,0+70 sm 40,8 4096 4779
3 x 150,0+70 sm 44,8 5001 5685
3 x 185,0+95 sm 49,2 6353 7052
3 x 240,0+120 sm 55,3 8128 9227
3 x 300,0+150 sm 60,9 10035 11383
4 x 1,5 re 13,8 57 252
4 x 2,5 re 15,8 93 289
4 x 4,0 re 16,2 149 419
4 x 6,0 re 17,6 223 533
4 x 10,0 re 19,5 376 741
4 x 16,0 rm 21,8 595 1024
4 x 25,0 rm 27,2 970 1615
4 x 35,0 rm 30,1 1321 1893
4 x 50,0 sm 29,2 1817 2311
4 x 70,0 sm 33,4 2624 3142
4 x 95,0 sm 39,4 3587 4256
4 x 120,0 sm 44,8 4547 5292
4 x 150,0 sm 44,8 5503 6446
4 x 240,0 sm 55,3 8108 10426
4 x 300,0 sm 60,9 11548 12850
5 x 1,5 re 13,7 71 272
5 x 2,5 re 14,8 116 341
5 x 4,0 re 17,9 187 435
5 x 6,0 re 19,3 279 591
5 x 10,0 re 21,6 470 826
5 x 16,0 rm 24,1 744 1262
5 x 25,0 rm 30,0 1213 1929
5 x 35,0 rm 33,5 1683 2593
5 x 50,0 sm 35,1 2271 3435
5 x 70,0 sm 41,7 3203 4577
5 x 95,0 sm 45,1 4554 6318

Note: Other core configuration and special constructions manu-factured upon request. Cables with same construction may produced according to IEC 60502.

Factory Overview


Packaging & Shipping


FAQ

Q1: What is the difference between NYY-O and NYY-J cables?
A: The “O” designation typically refers to cables without a green/yellow earth core, while the “J” designation includes a green/yellow earth core in multi-core configurations. Both versions share the same robust construction and 0.6/1 kV voltage rating.

Q2: Where can I safely install this cable?
A: You can install NYY cables in power plants, industrial switching stations, and secondary distribution networks. They perform exceptionally well in outdoor applications, indoor installations, open air, underground, and even in water. However, do not use them where mechanical damage is anticipated.

Q3: What are the temperature and voltage limits?
A: The cable operates at a maximum continuous conductor temperature of 70 °C. During a short circuit, it withstands 160 °C for up to 5 seconds. The operational ambient temperature ranges from -30 °C to +50 °C. Furthermore, the rated voltage is 0.6/1 kV, and the AC test voltage is 4 kV at 50 Hz.

Q4: Does this cable meet safety and environmental standards?
A: Yes. The construction follows VDE 0276 part 603 standards. Additionally, it features a flame test rating according to VDE 0472 part 804 class B (IEC 332 part 1). Moreover, the product is fully RoHS and CE compliant, ensuring it meets strict environmental and safety regulations.

Q5: What materials make up the cable’s construction?
A: The cable features solid or multi-strand copper conductors (Class 1 or 2 per VDE 0295/IEC 60228) insulated with PVC type DIV4. A filling compound forms the inner sheath, and a black PVC type DMV5 outer sheath provides ultimate protection.

Q6: How do I identify the cores inside the cable?
A: Core identification follows VDE 0293 standards. Single cores are black or yellow/green. Double cores feature blue/brown or yellow-green/black. Multi-core cables use color sequences like brown, black, and grey, or they use black cores with printed number marks.

Q7: What is the minimum bending radius during installation?
A: To prevent damage, you must maintain a minimum bending radius of 15 times the cable diameter (15 x D) for multi-core cables, or 12 times the cable diameter (12 x D) for single-core cables.

Reviews

There are no reviews yet.

Be the first to review “NYY-O & NYY-J 0.6/1 kV Low Voltage Power Cable – RoHS Compliant”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS