High-performance multicore cable designed for mains, submains, and subcircuits in domestic, commercial, and industrial installations. Features Plain Annealed Copper Class 2 conductors, XLPE-X-90 insulation (Red, Black, Green/Yellow), and a PVC-5V-90 Orange sheath. Compliant with AS/NZS 5000.2 (1.5–6mm²) and AS/NZS 5000.1 (10–300mm²). Max operating temperature: 75°C. Available in 2 Core+E (16–120mm²) and 3 Core+E (16–300mm²).
AGKABEL GRUPPE LIMITED presents the Circular Cables XLPE/PVC, engineered for dependable power distribution in a wide range of installation environments. Designed for mains, submains, and subcircuits, this cable is suitable for unenclosed installation, in conduit, buried direct, or in underground ducts. The combination of XLPE insulation and PVC sheath ensures excellent thermal performance and durability in domestic, commercial, and industrial installations where the cable is not subject to mechanical damage.
Construction & Standards
-
Standard:
-
1.5 to 6mm²: AS/NZS 5000.2
-
10 to 300mm²: AS/NZS 5000.1
-
-
Voltage: 0.6/1kV
-
Conductor: Plain annealed copper stranded to IEC 60228 Class 2
-
Insulation: XLPE-X-90 Red & Black and Green/Yellow
-
Sheath: PVC-5V-90 Orange
-
Max. Operating Temperature: 75°C
-
Sheath Marking: Manufacture name (trademark) and type, Production year/week or batch number, Metre-marked
Application
For mains, submains and subcircuits unenclosed, in conduit, buried direct or in underground ducts for domestic, commercial and industrial installations where not subject to mechanical damage.
Technical Specifications Table
| No. of Cores (mm²) | No. of strands | Insulation (mm) | Sheath (mm) | Overall Diameter (mm) | Earth Area (mm²) | Max. DC Resistance at 20°C (ohm/km) | Approximate Mass (kg/km) |
|---|---|---|---|---|---|---|---|
| 2 Core+E | |||||||
| 16 | 7/1.7 | 0.8 | 1.8 | 17.1 | 6.0 | 1.150 | 540 |
| 25 | 7/2.14 | 0.9 | 1.8 | 19.3 | 6.0 | 0.727 | 740 |
| 35 | 7/2.65 | 0.9 | 1.8 | 21.3 | 10.0 | 0.524 | 960 |
| 50 | 19/1.89 | 1.0 | 1.8 | 24 | 16.0 | 0.387 | 1280 |
| 70 | 19/2.24 | 1.1 | 1.8 | 27.6 | 25.0 | 0.268 | 1800 |
| 95 | 19/2.65 | 1.1 | 1.9 | 32.5 | 25.0 | 0.193 | 2400 |
| 120 | 19/2.94 | 1.2 | 2.0 | 37.3 | 35.0 | 0.153 | 2980 |
| 3 Core+E | |||||||
| 16 | 7/1.7 | 0.8 | 1.8 | 18.6 | 6.0 | 1.150 | 710 |
| 25 | 7/2.14 | 0.9 | 1.8 | 20.8 | 6.0 | 0.727 | 980 |
| 35 | 7/2.65 | 0.9 | 1.8 | 23.2 | 10 | 0.524 | 1320 |
| 50 | 19/1.89 | 1 | 1.8 | 26.3 | 16 | 0.387 | 1750 |
| 70 | 19/2.24 | 1.1 | 1.9 | 30.5 | 25 | 0.268 | 2490 |
| 95 | 19/2.65 | 1.1 | 2 | 35.2 | 25 | 0.193 | 3370 |
| 120 | 19/2.94 | 1.2 | 2.1 | 40.3 | 35 | 0.153 | 4170 |
| 150 | 19/3.28 | 1.4 | 2.3 | 44.3 | 50 | 0.124 | 5160 |
| 185 | 37/2.65 | 1.6 | 2.4 | 49.7 | 70 | 0.099 | 6550 |
| 240 | 37/2.94 | 1.7 | 2.6 | 56.8 | 95 | 0.075 | 8560 |
| 300 | 37/3.28 | 1.8 | 2.8 | 63.3 | 120 | 0.060 | 10660 |
Factory Overview
Packaging & Shipping
❓ Frequently Asked Questions (FAQ)
1. What are the primary applications for this cable?
It is ideal for mains, submains, and subcircuits in unenclosed installations, in conduit, buried direct, or in underground ducts for domestic, commercial, and industrial installations where not subject to mechanical damage.
2. What is the maximum operating temperature?
The maximum operating temperature is 75°C.
3. What materials are used for the conductor and insulation?
The conductor is Plain Annealed Copper stranded to IEC 60228 Class 2. The insulation is XLPE-X-90 (Red & Black and Green/Yellow) and the sheath is PVC-5V-90 Orange.
4. What is the voltage rating of this cable?
The voltage rating is 0.6/1kV.
5. What standards does this cable comply with?
-
1.5 to 6mm²: AS/NZS 5000.2
-
10 to 300mm²: AS/NZS 5000.1
6. What sizes and core configurations are available?
-
2 Core+E: 16mm² to 120mm²
-
3 Core+E: 16mm² to 300mm²
7. What is the benefit of XLPE insulation over PVC?
XLPE (Cross-linked Polyethylene) offers higher thermal resistance, better electrical properties, and greater resistance to chemicals and moisture compared to standard PVC, making it ideal for demanding installations.