AIDC Data Center Power Cable Collection (UL Types)
For UPS, Control Cabinet & High-Density Rack Power
1. Main Power Feed (Utility → Switchgear → UPS → PDU)
| Cable Type | UL Std. | Insulation | Voltage | Temp | Application |
|---|
| XHHW-2 | UL 44 | XLPE | 600V (up to 1000V) | 90°C dry/wet | UPS input/output, generator & ATS feeds, tray/conduit |
| THHN / THWN-2 | UL 83 | PVC + nylon | 600V | 90°C dry / 75°C wet | General conduit wiring, cost-sensitive runs |
| TC-ER (XHHW-2 core) | UL 1277 | XLPE + PVC/CPE jacket | 600V | 90°C | Exposed cable tray, no conduit needed, UPS→PDU feeders |
| RHH / RHW-2 | UL 44 | XLPE | 600V | 90°C | Alternative to XHHW-2 in legacy specs |
2. AIDC High-Density / Battery / DC Bus
| Cable Type | UL Std. | Insulation | Voltage | Temp | Application |
|---|
| DCPC (Data Center Power Cable) | UL 2137 | Flexible XLPE / LSZH optional | 2000V AC/DC | 75/90/105/150°C | AI rack power, UPS↔BESS battery cabinet, 48V/240V DC bus |
| Battery Harness (fine-strand) | UL 1973 / UL 9540A | LSZH XLPO | 600–1000V DC | 125°C | UPS string interconnect, BMS sense + power combo |
| Flexible DC Feeder | UL 1650 (W-type alt.) | Rubber/XLPO | 2000V DC | — | Portable/industrial DC links (less common in fixed AIDC) |
3. Control Cabinet Internal Wiring
| Cable Type | UL Std. | Insulation | Voltage | Temp | Application |
|---|
| MTW | UL 1063 | PVC (flexible) | 600V | 60/75/90°C | Panel power wiring, flexible control circuits |
| UL 1015 (AWM) | UL 758 | PVC | 600V | 105°C | Main control loops, terminal blocks, transformer leads |
| UL 1007 (AWM) | UL 758 | PVC | 300V | 80°C | PLC signals, low-current control, door wiring |
| TC-ER Shielded | UL 1277 | XHHW-2 + Cu braid/foil | 600V | 90°C | UPS↔BMS/CT/PT signal & control in tray |
4. Plenum / Raised-Floor Special (NEC 645 / NFPA 262)
- CMP-rated power/comms cable for air-handling spaces (plenum)
- DP-type (UL 1690) for under-floor data hall power distribution (600V, low-flame)
5. Typical Bill-of-Material Template (English)
UPS INPUT FEED
XHHW-2, stranded bare copper, XLPE insulation, 600/1000V, 90°C wet/dry,
sunlight & oil resistant, VW-1, per UL 44 / NEC 310.15
3 x 350 kcmil + 1 x 175 kcmil GND
UPS TO PDU (TRAY)
TC-ER, XHHW-2 conductors, PVC/CPE jacket, 600V, 90°C,
IEEE 1202 / FT4, per UL 1277 / NEC 336
4 x 4/0 AWG + 1 x 2/0 AWG
BATTERY CABINET LINK
DCPC Type, UL 2137, fine-stranded tinned copper, LSZH optional,
2000V AC/DC, 90°C, flexible
2 x 4/0 AWG + shield
CONTROL PANEL
UL 1015 105°C 600V tinned copper, VW-1 (power)
UL 1007 80°C 300V (control/signal)
MTW per UL 1063 for flexible internal harness
6. Quick Selection Rule
- Building feeder / conduit → XHHW-2
- Open tray, fast install → TC-ER (XHHW-2)
- AI rack / battery flex / 2kV DC → DCPC (UL 2137)
- Cabinet inside → UL 1015 + MTW + 1007
- Plenum/under-floor → CMP / DP-type