SVT-s 0.6/1 kV UV-Steady Power Cable – BDS 16291-85
The SVT-s 0.6/1 kV cable delivers dependable power distribution for outdoor installations and switching applications. Constructed with solid or twisted copper conductors, PVC insulation, and a UV-steady black PVC outer sheath, it offers excellent durability against atmospheric influences and sunlight. Because it meets BDS 16291-85 standards and is RoHS compliant, it provides a safe and reliable solution for exposed environments.
Application
SVT-s cables provide reliable power transfer and distribution for switching installations. Because they are constructed to withstand atmospheric influences and sunlight, installers use them for outdoor installations. Furthermore, they operate efficiently at a rated voltage of Uo/U 0.6/1 kV and a frequency of 50 Hz. Consequently, they deliver consistent performance in exposed environments where UV stability is crucial.
Cable construction
This cable strictly adheres to BDS 16291-85 standards. It features solid or twisted copper wires (class 1 or 2) that comply with BDS 904-84 (IEC 60228). The insulation uses a PVC compound. Finally, a black PVC compound outer sheath protects the entire assembly. Notably, this sheath is UV steady, and the cable is produced without or with joint filling. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BDS 904-84. The maximum conductor temperature is +70 °C. During a short circuit, it can withstand +160 °C for no more than 5 seconds. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of AC – 4 kV 50 Hz and DC – 12 kV. Installers must respect a minimum bending radius of 10 times the cable diameter. The temperature of laying is -5 °C, and the temperature range is -30 °C to +50 °C. Furthermore, it passes the flame test according to BDS IEC 332-1.
Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are black, brown, blue, yellow/green, or other colors upon request. Double core cables feature blue and black. Multi-core configurations include specific color sequences. For instance, 3-core uses brown, black, and grey, or yellow/green, blue, and brown. 4-core uses blue, brown, black, and grey, or yellow/green, brown, black, and grey. 5-core uses blue, brown, black, grey, and black, or yellow/green, blue, brown, black, and grey. Multiple core uses black with number marks on cores or black with number marks on cores and a yellow/green core in the outer cover.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data SVT-s 0.6/1 kV
| Number of wires and nominal cross-section | Shape | Outer diameter approx. | Cu weight | Cable weight approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 1 x 1,5 | re | 7,2 | 14 | 69 |
| 1 x 2,5 | re | 7,6 | 23 | 82 |
| 1 x 4,0 | re | 8,0 | 37 | 102 |
| 1 x 6,0 | re | 8,7 | 55 | 128 |
| 1 x 10 | re | 9,3 | 93 | 178 |
| 1 x 16 | re | 10,8 | 148 | 253 |
| 1 x 25 | rm | 11,9 | 229 | 350 |
| 1 x 35 | rm | 13,0 | 322 | 458 |
| 1 x 50 | rm | 15,0 | 456 | 608 |
| 1 x 70 | rm | 16,7 | 648 | 810 |
| 1 x 95 | rm | 18,4 | 885 | 1100 |
| 1 x 120 | rm | 19,9 | 1120 | 1325 |
| 1 x 150 | rm | 21,9 | 1378 | 1610 |
| 1 x 185 | rm | 24,1 | 1703 | 2010 |
| 1 x 240 | rm | 27,2 | 2208 | 2565 |
| 1 x 300 | rm | 30,3 | 2765 | 3200 |
| 1 x 400 | rm | 33,7 | 3690 | 4010 |
| 1 x 500 | rm | 37,9 | 4600 | 5180 |
| 2 x 1,5 | re | 9,3 | 28 | 100 |
| 2 x 2,5 | re | 10,0 | 46 | 130 |
| 2 x 4,0 | re | 10,6 | 75 | 150 |
| 2 x 6,0 | re | 12,1 | 112 | 210 |
| 2 x 10 | re | 15,2 | 182 | 370 |
| 2 x 16 | rm | 17,8 | 303 | 500 |
| 2 x 25 | rm | 23,8 | 485 | 1057 |
| 2 x 35 | rm | 25,9 | 652 | 1237 |
| 2 x 50 | rm | 27,9 | 928 | 1408 |
| 3 x 1,5 | re | 10,2 | 42 | 122 |
| 3 x 2,5 | re | 11,0 | 69 | 154 |
| 3 x 4,0 | re | 12,8 | 110 | 210 |
| 3 x 6,0 | re | 14,0 | 165 | 260 |
| 3 x 10 | re | 16,0 | 275 | 480 |
| 3 x 16 | rm | 18,9 | 450 | 682 |
| 3 x 25 | rm | 22,8 | 700 | 1070 |
| 3 x 35 | rm | 25,9 | 1000 | 1336 |
| 3 x 50 | rm | 28,9 | 1390 | 1895 |
| 3 x 70 | sm | 28,9 | 1850 | 2400 |
| 3 x 95 | sm | 33,1 | 2650 | 3255 |
| 3 x 120 | sm | 35,9 | 3350 | 4010 |
| 3 x 150 | sm | 39,3 | 4185 | 4830 |
| 3 x 185 | sm | 43,4 | 5160 | 6055 |
| 3 x 240 | sm | 48,9 | 6720 | 7810 |
| 3 x 1,5 + 1,5 | re/re | 11,2 | 56 | 140 |
| 3 x 2,5 + 1,5 | re/re | 13,2 | 76 | 205 |
| 3 x 4,0 + 4,0 | re/re | 14,4 | 202 | 380 |
| 3 x 10 + 6,0 | re/re | 16,7 | 330 | 545 |
| 3 x 16 + 10 | rm/re | 20,6 | 580 | 845 |
| 3 x 25 + 16 | rm/re | 24,5 | 580 | 1245 |
| 3 x 35 + 16 | rm/rm | 27,3 | 1130 | 1590 |
| 3 x 50 + 25 | sm/rm | 30,8 | 1630 | 2175 |
| 3 x 70 + 35 | sm/rm | 34,9 | 2280 | 2785 |
| 3 x 95 + 50 | sm/rm | 36,8 | 3120 | 3680 |
| 3 x 120 + 70 | sm/rm | 40,1 | 4010 | 4780 |
| 3 x 150 + 70 | sm/rm | 44,3 | 4830 | 5620 |
Construction data SVT-s 0.6/1 kV
| Number of wires and nominal cross-section | Shape | Outer diameter approx. | Cu weight | Cable weight approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 3 x 185 + 95 | sm/rm | 48,3 | 6070 | 7480 |
| 3 x 240 + 120 | sm/rm | 55,4 | 7840 | 9150 |
| 4 x 1,0 | re | 10,4 | 37 | 140 |
| 4 x 1,5 | re | 11,0 | 55 | 165 |
| 4 x 2,5 | re | 11,9 | 92 | 216 |
| 4 x 4,0 | re | 13,9 | 146 | 298 |
| 4 x 6,0 | re | 16,8 | 218 | 375 |
| 4 x 10 | re | 18,3 | 363 | 583 |
| 4 x 16 | rm | 20,3 | 595 | 925 |
| 4 x 25 | rm | 25,0 | 970 | 1285 |
| 4 x 35 | rm | 28,0 | 1305 | 1778 |
| 4 x 50 | sm | 33,0 | 2301 | 3101 |
| 4 x 70 | sm | 37,3 | 2601 | 4100 |
| 4 x 95 | sm | 41,3 | 4540 | 5250 |
| 4 x 120 | sm | 45,2 | 5575 | 6350 |
| 4 x 150 | sm | 49,5 | 5855 | 7590 |
| 4 x 185 | sm | 54,4 | 6790 | 9780 |
| 5 x 1,0 | re | 11,2 | 45 | 160 |
| 5 x 1,5 | re | 11,8 | 69 | 195 |
| 5 x 2,5 | re | 13,8 | 116 | 275 |
| 5 x 4,0 | re | 15,5 | 182 | 380 |
| 5 x 6,0 | re | 16,8 | 275 | 500 |
| 5 x 10 | re | 23,2 | 745 | 1150 |
| 5 x 16 | rm | 23,2 | 745 | 1150 |
| 5 x 25 | rm | 27,9 | 1165 | 1700 |
| 5 x 35 | rm | 30,9 | 1690 | 2110 |
| 5 x 50 | sm | 36,9 | 2330 | 3130 |
| 5 x 70 | sm | 42,0 | 3230 | 4230 |
| 7 x 1,5 | re | 12,0 | 96 | 230 |
| 10 x 1,5 | re | 14,7 | 140 | 315 |
| 12 x 1,5 | re | 14,7 | 140 | 315 |
| 14 x 1,5 | re | 16,1 | 195 | 410 |
| 16 x 1,5 | re | 17,1 | 220 | 470 |
| 19 x 1,5 | re | 17,1 | 220 | 550 |
| 21 x 1,5 | re | 18,3 | 270 | 600 |
| 24 x 1,5 | re | 22,6 | 410 | 840 |
| 30 x 1,5 | re | 26,5 | 506 | 1110 |
| 37 x 1,5 | re | 26,5 | 506 | 1110 |
| 8 x 2,5 | re | 14,1 | 182 | 365 |
| 10 x 2,5 | re | 18,2 | 225 | 445 |
| 12 x 2,5 | re | 18,2 | 279 | 485 |
| 14 x 2,5 | re | 18,2 | 330 | 550 |
| 16 x 2,5 | re | 18,2 | 330 | 570 |
| 19 x 2,5 | re | 24,5 | 546 | 695 |
| 21 x 2,5 | re | 24,5 | 546 | 695 |
| 24 x 2,5 | re | 25,3 | 552 | 1210 |
| 30 x 2,5 | re | 25,3 | 685 | 1210 |
| 37 x 2,5 | re | 28,6 | 845 | 1480 |
| 7 x 4,0 | re | 19,3 | 255 | 470 |
| 7 x 6,0 | re | 20,0 | 384 | 630 |
| 7 x 10 | re | 17,3 | 384 | 640 |
Note: Cable may be produced without joint filling.
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the SVT-s cable?
A:- It is used for transferring and distributing electrical power in switching installations and outdoor installations, specifically designed to withstand atmospheric influences and sunlight.
Q:- What are the key features of this cable’s outer sheath?
A:- The black PVC outer sheath is UV steady, providing excellent protection against sunlight and weather conditions for outdoor applications.
Q:- What standards does the cable construction follow?
A:- The construction adheres to BDS 16291-85 standards, and the conductor complies with BDS 904-84 (IEC 60228).
Q:- What type of conductor and insulation does it use?
A:- It uses solid or twisted copper wires (class 1 or 2) with PVC insulation.
Q:- What is the temperature range for this cable?
A:- The temperature of laying is -5°C, and the operating temperature range is -30°C to +50°C.
Q:- What is the maximum conductor temperature and short-circuit limit?
A:- The maximum conductor temperature is +70°C. During a short circuit, it can withstand +160°C for no more than 5 seconds.
Q:- What is the test voltage for this cable?
A:- The test voltage is AC – 4 kV 50 Hz and DC – 12 kV.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter (10 x D cable).
Q:- Is this cable flame retardant?
A:- Yes, it passes the flame test according to BDS IEC 332-1.
Q:- Is this cable RoHS compliant?
A:- Yes, the product is RoHS compliant.




Reviews
There are no reviews yet.