NYIFY Flat Cable 230/400 V – VDE 0250 Part 201
The NYIFY flat cable delivers dependable power distribution for installations in dry environments. Constructed with copper conductors, PVC insulation, and a white, black, or grey PVC outer sheath, it offers a reliable solution for in and beneath plaster installations. Because it meets VDE 0250 part 201 standards and is CE/RoHS compliant, it provides a safe and effective solution for routing power in protected building environments, provided it is fully covered by plaster.
Application
NYIFY flat cables provide reliable power distribution for installations in dry environments. Because they feature a flat construction, installers use them both in and beneath plaster. Furthermore, the cables must be covered by plaster along their entire length. Installation in cavities of concrete, stone, or non-inflammable building materials is allowed. Additionally, the cables cannot be installed on inflammable building materials, immediately next to or under window frames, or similar materials. During the curing and drying phase of the plaster, installers must protect the cables by means of a cover plaster, adhesive, nails, or with insulating materials. The cables may not be bundled together.
Cable construction
This cable strictly adheres to VDE 0250 part 201 standards. It features copper wires according to VDE 0295 class 1 IEC 60228. The insulation uses a PVC compound type YI1 according to VDE 0207 part 4. Cores fit in adjacent configuration with a common covering of PVC compound. Finally, a white, black, or grey PVC compound type YM 1 sheath (according to VDE 0207 part 5) protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to VDE 0295 class 1 and IEC 60228. The maximum core temperature is 70 °C in operation. It operates at a rated voltage of 230/400 V and undergoes a test voltage of AC 50 Hz at 2000 V. The temperature range is -20 °C to +70 °C. Installers must respect a minimum bending radius of 6 times the cable diameter for fixed installation. Furthermore, it passes the flame test according to VDE 0472 test class B, according to VDE 0472 part 804 and IEC 60 332-1.
Color coding
Clear color coding ensures safe and accurate wiring. For 2 cores: blue, brown. For 3 cores: yellow/green, blue, brown. For 4 cores: yellow/green, brown, black, grey. For 5 cores: yellow/green, blue, brown, black, grey.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data NYIFY 230/400V
| Number of wires and nominal cross section | Outer dimensions | Copper weight | Approx. cable weight |
|---|---|---|---|
| mm² | mm | kg/km | kg/km |
| NYIFY – O | |||
| 3×1.5 | 4 x 11 | 27 | 69 |
| 3×2.5 | 4,8 x 12,2 | 44 | 88 |
| 3×4,0 | 5,5 x 14 | 71 | 140 |
| NYIFY – J | |||
| 3×1,5 | 4 x 16 | 40 | 100 |
| 3×2,5 | 4,6 x 19,8 | 66 | 155 |
| 3×4 | 5,5 x 23,0 | 106 | 217 |
| 3×6 | 5,8 x 26 | 155 | 273 |
| 4×1,5 | 4,6 x 27,5 | 55 | 218 |
| 5×1,5 | 4 x 32 | 68 | 188 |
| 5×2,5 | 4,6 x 35 | 110 | 265 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the NYIFY flat cable?
A:- It is used for installations in dry environments, both in and beneath plaster, provided the cables are fully covered by plaster along their entire length.
Q:- Where is installation NOT allowed?
A:- Installation is not allowed on inflammable building materials, immediately next to or under window frames, or similar materials.
Q:- What standards does the cable construction follow?
A:- The construction adheres to VDE 0250 part 201 standards, and the conductor complies with VDE 0295 class 1 IEC 60228.
Q:- What type of conductor and insulation does it use?
A:- It uses copper wires with a PVC compound type YI1 insulation.
Q:- What is the temperature range for this cable?
A:- The temperature range is -20°C to +70°C.
Q:- What is the rated voltage and test voltage?
A:- The rated voltage is 230/400 V, and the test voltage is AC 50 Hz at 2000 V.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 6 times the cable diameter for fixed installation.
Q:- What is the maximum core temperature?
A:- The maximum core temperature in operation is 70°C.
Q:- What are the color coding options available?
A:- The color coding includes combinations like blue/brown for 2 cores, yellow/green/blue/brown for 3 cores, and yellow/green/brown/black/grey for 4 cores.
Q:- Is this cable flame retardant?
A:- Yes, it passes the flame test according to VDE 0472 test class B, VDE 0472 part 804, and IEC 60 332-1.