AGKABEL UL AWM Style 2464 Multi-Conductor Cable is a flexible, PVC-insulated and PVC-jacketed control and signal cable recognized under UL 758 (AWM) and commonly certified to CSA standards. Rated at 300V and 80°C, it is available with 2 to 12+ color-coded conductors in sizes from 28 AWG to 16 AWG. Standard constructions feature stranded copper conductors and a flexible PVC jacket, with UL VW-1 / CSA FT1 flame ratings. Shielded variants (foil or braid) are available for EMI protection. Ideal for internal wiring of electronic equipment, control panels, PLC systems, and RS-232/422/485 serial communication, it is the perfect solution for protected, low-voltage signal and control circuits. Not intended for continuous flexing or outdoor exposure.
AGKABEL XLPE/PVC Three Conductor Shielded MV-90 5kV Cable
Medium Voltage power cable designed for primary power and distribution circuits, utility substations, and generating plants. Features stranded soft-drawn bare copper or aluminum conductors, XLPE insulation, a semi-conducting screen with copper tape shield, and a sunlight-resistant PVC sheath. Compliant with UL 1072 listed type MV-90. Voltage rating: 5000 Volts (100% & 133% insulation level). Temperature: 90°C continuous, 130°C emergency, 250°C short circuit. Suitable for wet/dry locations, conduit, open air, and direct burial. Available from AWG 8 to 1000 MCM.
AGKABEL GRUPPE LIMITED presents the XLPE/PVC Three Conductor Shielded MV-90 5kV Cable, engineered for reliable medium voltage power distribution in demanding environments. This cable is designed for use in raceways, aerial installations (when properly supported), industrial plants, primary power and distribution circuits, utility substations, and generating plants. It is suitable for wet or dry locations, direct burial, and installation in conduit, ducts, open trays, or open air. The Cross-Linked Polyethylene (XLPE) insulation provides superior dielectric strength and thermal performance, while the copper tape shield ensures safety and electromagnetic compatibility.
Technical Data
-
Standard: UL 1072 listed type MV-90
-
Voltage: 5000 Volts 100% & 133% insulation level
-
Conductor: Stranded soft-drawn bare copper or aluminum conductor
-
Conductor Shield: Semi-conducting compound or tape
-
Insulation: Cross-linked polyethylene (XLPE)
-
Insulation Shield: Semi-conducting screen with copper tape shield
-
Ground Wire: Stranded bare copper
-
Cabling: Suitable lay with fillers
-
Sheath: Sunlight resistant polyvinyl chloride (PVC)
-
Temperature: 90°C continuous, 130°C emergency, 250°C short circuit
-
Sheath Mark: Manufacture name (trademark) and type, Production year/week or batch number, Metre-marked
-
Application: Raceways; Aerial (when properly supported); Industrial plants; Primary power & distribution circuits; Utility substations; Generating plants; Wet or dry locations; Conduit, ducts, open tray, or open air; Direct burial; Feeders, distribution, and branch circuits.
Technical Specifications Table
| Conductor AWG/MCM | No. of strands | Ground AWG | Insulation Thick. (in) | Sheath Thick. (in) | Sheath OD (in) | Ampacity Rating | Approx. weight (Kg/km) |
|---|---|---|---|---|---|---|---|
| 8 | 7 | 8 | 0.090 | 2.04 | 1.11 | 59 | 604 |
| 6 | 7 | 6 | 0.090 | 0.080 | 1.19 | 79 | 813 |
| 4 | 7 | 6 | 0.090 | 0.080 | 1.30 | 105 | 1039 |
| 2 | 7 | 6 | 0.090 | 0.080 | 1.43 | 140 | 1387 |
| 1 | 19 | 4 | 0.090 | 0.080 | 1.51 | 160 | 1577 |
| 1/0 | 19 | 4 | 0.090 | 0.080 | 1.60 | 185 | 1899 |
| 2/0 | 19 | 4 | 0.090 | 0.080 | 1.70 | 215 | 2156 |
| 3/0 | 19 | 3 | 0.090 | 0.110 | 1.87 | 250 | 2750 |
| 4/0 | 19 | 3 | 0.090 | 0.110 | 1.99 | 285 | 3222 |
| 250 | 37 | 3 | 0.090 | 0.110 | 2.09 | 320 | 3646 |
| 300 | 37 | 2 | 0.090 | 0.110 | 2.17 | 355 | 4500 |
| 350 | 37 | 2 | 0.090 | 0.110 | 2.32 | 395 | 4852 |
| 400 | 37 | 2 | 0.090 | 0.110 | 2.49 | 420 | 5645 |
| 500 | 37 | 1 | 0.090 | 0.110 | 2.61 | 485 | 6429 |
| 600 | 61 | 1 | 0.090 | 0.140 | 2.90 | 540 | 7905 |
| 750 | 61 | 1/0 | 0.090 | 0.140 | 3.12 | 615 | 9354 |
| 1000 | 61 | 1/0 | 0.090 | 0.140 | 3.56 | 705 | 11705 |
Factory Overview
Packaging & Shipping


❓ Frequently Asked Questions (FAQ)
1. What are the primary applications for this cable?
It is designed for primary power and distribution circuits, utility substations, and generating plants. It is suitable for installation in raceways, aerial setups (when properly supported), and direct burial.
2. What does the “MV-90” designation mean?
MV-90 indicates a Medium Voltage cable rated for a continuous operating temperature of 90°C, as defined by UL 1072.
3. What is the purpose of the copper tape shield?
The copper tape shield (combined with the semi-conducting screen) provides essential safety by confining the electric field within the insulation and providing a low-impedance path for fault currents, while also protecting against electromagnetic interference.
4. What are the temperature ratings?
The cable is rated for 90°C continuous, 130°C emergency, and 250°C short circuit conditions.
5. What is the voltage rating?
The cable is rated for 5000 Volts and meets both 100% and 133% insulation level requirements.
6. What sizes and core configurations are available?
It is a three-conductor cable available in sizes ranging from AWG 8 to 1000 MCM, with a bare copper ground wire.