H05Z-U, H07Z-U/R, H05Z-K, H07Z-K Halogen-Free Single Core Cables
These halogen-free single core cables are engineered for fire- and flame-resistant internal wiring of tools and appliances. They feature a bare copper conductor with a halogen-free compound insulation, available in sizes from 0.5 mm² to 400 mm². Designed for installation in conduits and pipes, they operate effectively within a temperature range of -40°C to +90°C. The H05Z types are rated for 300/500 V, while the H07Z types are rated for 450/750 V, ensuring safety with low smoke and zero halogen emissions.
These halogen-free single core cables are specifically designed as fire- and flame-resistant, halogen-free installation wires for internal wiring of tools and appliances, as well as for installation in conduits and pipes, in and under plaster. Because they are manufactured without halogenated materials, they are exceptionally safe for use in environments where smoke and toxic gas emissions must be minimized during a fire. Furthermore, the cables offer excellent electrical and mechanical properties, making them highly versatile for a wide range of wiring applications.
The cable structure features a bare copper conductor, insulated with a halogen-free compound, and available in various cross-sections from 0.5 mm² up to 3×240 mm² for the larger sizes. The H05Z-U and H05Z-K types are rated for 300/500 V, while the H07Z-U/R and H07Z-K types are rated for 450/750 V.
Technical Data & Construction Overview:
-
Temperature range: -40°C to +90°C
-
Nominal voltage: H05… = 300/500 V; H07… = 450/750 V
Construction Data (Part Numbers & Specifications)
| Part N° | N° of cores x cross-sec mm² | Outer diameter ca. mm | Copper weight kg/km | Weight ca. kg/km |
|---|---|---|---|---|
| H05Z-U | ||||
| 11617001 | 0,5 | 2,6 | 5,00 | 9,00 |
| 11617002 | 0,75 | 2,8 | 7,50 | 11,00 |
| 11617003 | 1 | 3,0 | 10,00 | 13,00 |
| H07Z-U/R | ||||
| 11617030 | 1,5 | 3,3 | 15,00 | 18,00 |
| 11617035 | 2,5 | 3,7 | 25,00 | 27,00 |
| 11617006 | 4 | 4,2 | 40,00 | 45,00 |
| 11617007 | 6 | 4,7 | 60,00 | 65,00 |
| 11617008 | 10 | 5,8 | 100,00 | 103,00 |
| 11617009 | 16 | 7,4 | 160,00 | 162,00 |
| 11617010 | 25 | 9,2 | 250,00 | 245,00 |
| 11617011 | 35 | 10,4 | 350,00 | 310,00 |
| 11617012 | 50 | 12,2 | 500,00 | 450,00 |
| 11617013 | 70 | 14,4 | 700,00 | 640,00 |
| 11617014 | 95 | 16,0 | 950,00 | 880,00 |
| 11617015 | 120 | 18,2 | 1.200,00 | 1.185,00 |
| 11617016 | 150 | 20,2 | 1.500,00 | 1.350,00 |
| 11617017 | 185 | 22,7 | 1.850,00 | 1.670,00 |
| 11617018 | 240 | 25,5 | 2.400,00 | 2.270,00 |
| 11617019 | 300 | 28,3 | 2.800,00 | 3.200,00 |
| 11617020 | 400 | 32,3 | 3.840,00 | 4.200,00 |
| H05Z-K | ||||
| 11618114 | 0,5 | 2,6 | 4,80 | 9,00 |
| 11618105 | 0,75 | 2,8 | 7,20 | 11,00 |
| 11618011 | 1 | 2,9 | 9,60 | 14,00 |
| H07Z-K | ||||
| 11618014 | 1,5 | 3,5 | 14,40 | 20,00 |
| 11618019 | 2,5 | 4,0 | 24,00 | 30,00 |
| 11618029 | 4 | 4,6 | 38,00 | 45,00 |
| 11618033 | 6 | 4,6 | 58,00 | 45,00 |
| 11618061 | 10 | 6,8 | 96,00 | 110,00 |
| 11618042 | 16 | 8,2 | 154,00 | 170,00 |
| 11618113 | 25 | 10,4 | 240,00 | 260,00 |
| 11618011 | 35 | 11,9 | 336,00 | 360,00 |
| 11618051 | 50 | 13,7 | 480,00 | 500,00 |
| 11618060 | 70 | 16,4 | 672,00 | 700,00 |
| 11618053 | 95 | 18,2 | 912,00 | 950,00 |
| 11618065 | 120 | 20,2 | 1.152,00 | 1.200,00 |
| 11618111 | 150 | 22,7 | 1.440,00 | 1.500,00 |
| 11618067 | 185 | 25,2 | 1.776,00 | 1.850,00 |
| 11618068 | 240 | 28,5 | 2.304,00 | 2.400,00 |
Further dimensions available on request. All technical information in this catalogue is supplied without liability.
Factory Overview
Packaging & Shipping
Frequently asked questions and answer (Q:- A:-)
Q:- What is the primary application of these halogen-free cables?
A:- They are used for internal wiring of tools and appliances, as well as for installation in conduits, pipes, in and under plaster.
Q:- Are these cables fire-resistant?
A:- Yes, they are designed as fire- and flame-resistant installation wires.
Q:- What is the temperature range for these cables?
A:- The temperature range is -40°C to +90°C.
Q:- What is the nominal voltage for the H05Z types?
A:- The nominal voltage for H05Z types is 300/500 V.
Q:- What is the nominal voltage for the H07Z types?
A:- The nominal voltage for H07Z types is 450/750 V.
Q:- What is the difference between the U and K types?
A:- The U types are single core cables for general installation, while the K types are flexible single core cables for appliance wiring.
Q:- What is the outer diameter of the H05Z-U 0.5 mm² cable?
A:- The outer diameter is 2.6 mm.
Q:- What is the copper weight for the H07Z-K 240 mm² cable?
A:- The copper weight is 2,304.00 kg/km.
Q:- Do these cables emit toxic smoke during a fire?
A:- No, they are halogen-free, meaning they emit low smoke and no toxic halogen gases.
Q:- Are further dimensions available?
A:- Yes, further dimensions are available on request.



Reviews
There are no reviews yet.