FRT-XIOL & FRT-XIOSL Flame Retardant Multi-Pair Instrumentation Cables
The FRT-XIOL and FRT-XIOSL multi-pair cables deliver dependable signal transmission for complex industrial and infrastructure instrumentation systems. Constructed with plain annealed copper conductors, XLPE insulation, individual and overall screens, and LSZH sheathing, they offer excellent fire safety and interference protection. Because they meet BS 5308 and IEC 60332-3 standards and are RoHS compliant, they provide a safe and reliable solution for critical data circuits and process control applications.
Application
FRT-XIOL and FRT-XIOSL multi-pair cables provide reliable signal transmission for complex industrial and infrastructure instrumentation systems. Because they feature individual and overall screening along with flame retardant construction, installers use them to protect critical data circuits from electromagnetic interference and prevent fire propagation. Furthermore, these cables are designed to maintain signal integrity in demanding environments. Consequently, they deliver consistent and safe performance for process control and monitoring applications.
Cable construction
These cables are manufactured to rigorous standards including BS 5308, BS 7211, BS 6724, and IEC 60332-3. They feature plain annealed copper conductors (Class 2 or 5) according to IEC 60228. The insulation uses an XLPE compound or XLPEA compound. For protection, an individual screen of aluminium/polyester tape (with a 0.7/0.3mm tinned drain wire) and an overall screen of aluminium/polyester tape are applied. A bedding of LSZH compound is used, followed by galvanized steel wire armour (for the XIOSL variant). The outer sheath is a black LSZH compound, with core identification via white and black numbering.
Technical Data
The cable delivers consistent performance under specific conditions. The voltage rating is Uo/U 300/500V. The operating temperature is max. 90°C for XLPE and max. 110°C for XLPEA. It passes the flame test according to IEC 60332-3 and BS 4066. The minimum bending radius is 8D for the unarmoured cable and 10D for the armoured cable. The reference standards include BS 5308, BS 7211, BS 6724, IEC 60754, BS 6425, and IEC 61034, BS 7622 Part 2.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
FRT-XIOL (Unarmoured)
| Size | No. of Pairs | Approx. Cable Overall Dia. | Approx. Weight |
|---|---|---|---|
| mm² | mm | kg/km | |
| 2P x 0.5 | 2 | 12,0 | 130 |
| 5P x 0.5 | 5 | 15,2 | 230 |
| 10P x 0.5 | 10 | 21,1 | 400 |
| 15P x 0.5 | 15 | 24,5 | 560 |
| 20P x 0.5 | 20 | 27,3 | 690 |
| 30P x 0.5 | 30 | 32,3 | 990 |
| 50P x 0.5 | 50 | 41,7 | 1610 |
| 2P x 1.0 | 2 | 12,8 | 155 |
| 5P x 1.0 | 5 | 16,2 | 285 |
| 10P x 1.0 | 10 | 22,6 | 500 |
| 15P x 1.0 | 15 | 26,2 | 720 |
| 20P x 1.0 | 20 | 29,8 | 930 |
| 30P x 1.0 | 30 | 35,4 | 1350 |
| 50P x 1.0 | 50 | 44,9 | 2130 |
| 2P x 1.5 | 2 | 14,7 | 210 |
| 5P x 1.5 | 5 | 18,8 | 380 |
| 10P x 1.5 | 10 | 26,5 | 690 |
| 15P x 1.5 | 15 | 30,8 | 990 |
| 20P x 1.5 | 20 | 34,4 | 1240 |
| 30P x 1.5 | 30 | 41,0 | 1820 |
| 50P x 1.5 | 50 | 52,2 | 2890 |
FRT-XIOSL (Armoured)
| Size | No. of Pairs | Approx. Armour Dia. | Approx. Weight |
|---|---|---|---|
| mm² | mm | kg/km | |
| 2P x 0.5 | 2 | 15,2 | 430 |
| 5P x 0.5 | 5 | 18,6 | 720 |
| 10P x 0.5 | 10 | 24,5 | 1240 |
| 15P x 0.5 | 15 | 27,9 | 1530 |
| 20P x 0.5 | 20 | 31,3 | 1770 |
| 30P x 0.5 | 30 | 34,3 | 2550 |
| 50P x 0.5 | 50 | 51,5 | 4090 |
| 2P x 1.0 | 2 | 16,0 | 480 |
| 5P x 1.0 | 5 | 19,6 | 800 |
| 10P x 1.0 | 10 | 25,9 | 1400 |
| 15P x 1.0 | 15 | 29,4 | 1780 |
| 20P x 1.0 | 20 | 33,2 | 2200 |
| 30P x 1.0 | 30 | 37,8 | 3050 |
| 50P x 1.0 | 50 | 54,9 | 4800 |
| 2P x 1.5 | 2 | 20,4 | 670 |
| 5P x 1.5 | 5 | 25,4 | 1110 |
| 10P x 1.5 | 10 | 33,5 | 1750 |
| 15P x 1.5 | 15 | 38,8 | 2460 |
| 20P x 1.5 | 20 | 42,6 | 2910 |
| 30P x 1.5 | 30 | 50,8 | 4250 |
| 50P x 1.5 | 50 | 62,6 | 6040 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of these flame retardant instrumentation cables?
A:- They are used for signal transmission in complex industrial and infrastructure instrumentation systems, providing reliable data communication and interference protection.
Q:- What standards do these cables adhere to?
A:- They are manufactured to rigorous standards including BS 5308, BS 7211, BS 6724, IEC 60332-3, IEC 60754, BS 6425, and IEC 61034.
Q:- What are the differences between the FRT-XIOL and FRT-XIOSL variants?
A:- The FRT-XIOL is the unarmoured version with dual screens, while the FRT-XIOSL is the armoured version featuring dual screens plus a galvanized steel wire braid.
Q:- What type of conductor and insulation do these cables use?
A:- They use plain annealed copper conductors (Class 2 or 5) with an XLPE or XLPEA compound insulation.
Q:- What is the voltage rating of these cables?
A:- The voltage rating is Uo/U 300/500V.
Q:- What is the operating temperature range?
A:- The operating temperature is max. 90°C for XLPE and max. 110°C for XLPEA.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 8D for the unarmoured cable and 10D for the armoured cable.
Q:- What type of outer sheath is used?
A:- A black LSZH (Low Smoke Zero Halogen) compound is used for the outer sheath.
Q:- How are the cores identified?
A:- Core identification is done via white and black numbering.
Q:- Are these cables RoHS compliant?
A:- Yes, the product is RoHS compliant.




Reviews
There are no reviews yet.