Cu/XLPE/LSF/SWA/LSF 0.6/1 kV Halogen-Free Flame Retardant Armoured Cable – BS 6724-1997
The Cu/XLPE/LSF/SWA/LSF 0.6/1 kV cable delivers dependable power and control distribution for industrial and infrastructure networks. Constructed with copper or aluminum conductors, XLPE insulation, galvanized steel wire armour, and a halogen-free flame retardant outer sheath, it offers exceptional fire safety and mechanical protection. Because it meets BS 6724-97 standards and is CE/RoHS compliant, it provides a safe and reliable solution for power stations, metro networks, and substations.
Application
Cu/XLPE/LSF/SWA/LSF cables provide reliable power and control distribution for industrial and infrastructure networks. They operate efficiently at a nominal voltage of Uo/U 0.6/1 kV. Because the XLPE type LSOH insulation is flame retardant with low halogen fire smoke emission and corrosion at fire conditions, installers use them in safety-critical electrical installations. Furthermore, they are highly suitable for distribution networks, electrical power stations, and non-magnetic armoured applications like NPPs and TPPs. Additionally, they are essential for substations, metro networks, and industrial sites. These cables are suitable for fixed assembly in lines with unlimited difference levels, indoor installations, and cable ducts. Finally, they perform reliably in conduits, shafts, on shelves and grilles, and outdoor under shelters.
Cable construction
This cable strictly adheres to BS 6724-97 standards. It features copper or aluminum stranded compacted wires according to BS 6360 (IEC 228) cl.2. The insulation uses an XLPE compound. Core identification includes 2-cores: red, black; 3-cores: red, yellow, blue; 4-cores: red, yellow, blue, black; 5-cores: red, yellow, blue, black, black; Control: black with white numbers or white with black numbers. A halogen-free compound forms the inner sheath. The armour consists of galvanized steel wires laid concentrically. Finally, a black halogen-free compound flame retardant type LTS 1 outer sheath protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BS 6360 (IEC228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of 0.6/1 kV and a highest system voltage of 1.2 kV. Test voltage is AC – 5 min for 3.5 kV between cores and 3.5 kV between core and armour. Installers must respect a minimum bending radius of 6 times the cable diameter. The temperature of laying is no less than 0 °C. The temperature of explosion is -30 to 50 °C. Furthermore, it passes the flame retardant test according to BS 4066-3 category C (IEC 332-3 category C). The force of strain in laying max is Cu cores – 50NS core, where N is the number of cores and S is the nominal cross-section of cores in mm.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data Cu/XLPE/LSF/SWA/LSF 0.6/1 kV
| Number of conductors and nominal cross section | Thickness of insulation | Diameter of St wires for arm. | Thickness of sheath | Cable diameter approx. | Mass of Cu approx. | Mass of cable approx. |
|---|---|---|---|---|---|---|
| N x mm² | mm | mm | mm | mm | kg/km | kg/km |
| 2×1.5m | 0,6 | 0,9 | 1,3 | 12,1 | 28 | 293 |
| 2×2.5m | 0,7 | 0,9 | 1,4 | 12,9 | 46 | 337 |
| 2×4.0m | 0,7 | 0,9 | 1,4 | 14,7 | 75 | 411 |
| 2×6.0m | 0,7 | 0,9 | 1,5 | 15,9 | 110 | 493 |
| 2x10m | 0,7 | 1,25 | 1,5 | 18,0 | 183 | 653 |
| 2x16m | 0,7 | 1,25 | 1,5 | 21,9 | 303 | 950 |
| 2x25m | 0,9 | 1,6 | 1,6 | 26,7 | 470 | 1292 |
| 2x35m | 0,9 | 1,6 | 1,7 | 28,8 | 652 | 1686 |
| 3×1.5m | 0,6 | 0,9 | 1,3 | 12,8 | 42 | 300 |
| 3×2.5m | 0,7 | 0,9 | 1,4 | 14,1 | 69 | 379 |
| 3×4.0m | 0,7 | 0,9 | 1,4 | 15,8 | 110 | 462 |
| 3×6.0m | 0,7 | 0,9 | 1,5 | 16,6 | 162 | 525 |
| 3x10m | 0,7 | 1,25 | 1,5 | 21,2 | 275 | 847 |
| 3x16m | 0,7 | 1,25 | 1,6 | 23,1 | 450 | 1111 |
| 3x25m | 0,9 | 1,6 | 1,7 | 28,2 | 700 | 1575 |
| 3x35m | 0,9 | 1,6 | 1,8 | 30,8 | 980 | 2113 |
| 4×1.5m | 0,6 | 0,9 | 1,3 | 13,3 | 55 | 321 |
| 4×2.5m | 0,7 | 0,9 | 1,4 | 15,3 | 92 | 416 |
| 4×4.0m | 0,7 | 0,9 | 1,4 | 16,4 | 146 | 513 |
| 4×6.0m | 0,7 | 1,25 | 1,5 | 18,7 | 218 | 737 |
| 4x10m | 0,7 | 1,25 | 1,6 | 21,1 | 363 | 974 |
| 4x16m | 0,7 | 1,6 | 1,7 | 26,0 | 565 | 1329 |
| 4x25m | 0,9 | 1,6 | 1,8 | 28,9 | 925 | 1972 |
| 4x35m | 0,9 | 1,6 | 1,8 | 33,7 | 1303 | 2470 |
| 4x50m | 1,0 | 1,6 | 1,9 | 35,6 | 1843 | 2924 |
| 4x70sm | 1,0 | 1,6 | 2,0 | 39,7 | 1857 | 2961 |
| 4x95sm | 1,1 | 2,0 | 2,1 | 42,7 | 2601 | 4209 |
| 4x120m | 1,2 | 2,0 | 2,2 | 47,1 | 3460 | 5936 |
| 4x150m | 1,4 | 2,5 | 2,5 | 51,4 | 4575 | 6926 |
| 4x185m | 1,6 | 2,5 | 2,6 | 55,6 | 5575 | 8988 |
| 5×1.5m | 0,6 | 0,9 | 1,4 | 14,3 | 66 | 366 |
| 5×2.5m | 0,7 | 0,9 | 1,5 | 16,3 | 114 | 473 |
| 5×4.0m | 0,7 | 0,9 | 1,6 | 19,0 | 182 | 594 |
| 5×6.0m | 0,7 | 1,25 | 1,6 | 20,0 | 255 | 650 |
| 5x10m | 0,7 | 1,25 | 1,6 | 22,8 | 475 | 1107 |
| 5x16m | 0,7 | 1,6 | 1,7 | 28,4 | 745 | 1662 |
| 5x25m | 0,9 | 1,6 | 1,9 | 33,5 | 1165 | 2384 |
| 7×1.5m | 0,6 | 0,9 | 1,4 | 15,2 | 95 | 421 |
| 7×2.5m | 0,6 | 1,25 | 1,5 | 18,5 | 165 | 717 |
| 12×1.5m | 0,6 | 1,25 | 1,6 | 22,0 | 270 | 1050 |
| 19×1.5m | 0,6 | 1,6 | 1,7 | 26,7 | 373 | 1361 |
| 27×1.5m | 0,6 | 1,6 | 1,7 | 28,7 | 506 | 1629 |
| 37×1.5m | 0,6 | 1,6 | 1,7 | 29,0 | 550 | 1549 |
| 7×2.5m | 0,7 | 1,6 | 1,8 | 23,0 | 300 | 1382 |
| 12×2.5m | 0,7 | 1,6 | 1,8 | 26,6 | 518 | 2092 |
| 19×2.5m | 0,7 | 1,6 | 1,8 | 28,6 | 621 | 2274 |
| 27×2.5m | 0,7 | 1,6 | 1,8 | 33,7 | 845 | 2449 |
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the Cu/XLPE/LSF/SWA/LSF cable?
A:- It is used in distribution networks, electrical power stations, NPPs, TPPs, metro networks, and industrial sites for fixed assembly in lines with unlimited difference levels.
Q:- What are the key fire safety features of this cable?
A:- It features halogen-free flame retardant insulation and sheaths with low smoke and corrosion emissions, passing the BS 4066-3 category C (IEC 332-3 category C) flame test.
Q:- What standards does the cable construction follow?
A:- The construction adheres to BS 6724-97 standards, and the conductor complies with BS 6360 (IEC 228) cl.2.
Q:- What type of conductor and insulation does it use?
A:- It uses Cu or Al stranded compacted conductors with XLPE insulation.
Q:- What kind of armour protects this cable?
A:- The cable features an armour made of galvanized steel wires laid concentrically.
Q:- What is the rated voltage and maximum conductor temperature?
A:- The rated voltage is 0.6/1 kV, and the continuous operating temperature is 90°C.
Q:- What are the short-circuit and overload temperature limits?
A:- It can withstand a short circuit temperature of 250°C for a maximum of 5 seconds and an overload temperature of 130°C for 100% per year max.
Q:- What is the test voltage for this cable?
A:- The test voltage is AC – 5 min for 3.5 kV between cores and 3.5 kV between core and armour.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 6 times the cable diameter (6x D cable).
Q:- What are the temperature limits for laying and explosion?
A:- The temperature of laying is no less than 0°C, and the temperature of explosion is -30 to 50°C.