Cu/Al XLPE/CWS/PE-wb 6.35/11 kV to 19/33 kV Water-Blocking Cable – BS 7870-4.10

The Cu/XLPE/CWS/PE-wb and Al/XLPE/CWS/PE-wb cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, water-blocking tapes, and a PE outer sheath, they offer excellent thermal and moisture protection for 6.35/11 kV and 19/33 kV applications. Because they meet BS 7870-4.10 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
These medium voltage single-core cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 6.35/11 and 19/33 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for use in distribution installations and cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to BS 7870-4.10 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2 and BS 6360 with water powder absorbing. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. A layer of semi-conductive water absorbing tapes forms the water resisting element. The metal screen consists of Cu wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. The water resisting element uses water absorbing insulation tape. The sheath uses a PE compound type MDPE according to BS 7870. The color is red for 11kV and black for 33kV. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC60228 class 2 and BS 6360. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 6.35/11 and 19/33 kV, while the highest system voltage Uo/U is not more than 6.35/11, 19/33 kV, and 36 kV. Test voltage is AC (+) – 15 min for 25.4 kV and 76 kV. The level of partial discharge at 2Uo is max. 10 pC. The minimum bending radius is 15 times the cable diameter. The temperature of laying is no less than -5 °C. The temperature of explosion is -30 to 50 °C. Testing follows BS 7870-4.10. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data Cu/XLPE/CWS/PE-wb and Al/XLPE/CWS/PE-wb 6.35/11; 19/33 kV

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. Cu/XLPE/CWS/PE-wb Mass of Cu approx. Cu/XLPE/CWS/PE-wb Mass of cable approx. Al/XLPE/CWS/PE-wb Mass of Al approx. Al/XLPE/CWS/PE-wb Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
6.35/11 kV
1x240m /35 3,4 2,0 35 36,2 36,6 2548 3310 – –
1x300m /35 3,4 2,1 35 38,6 39,1 3078 3925 – –
1x400m /35 3,4 2,2 35 41,1 42,4 3835 4760 – –
1x500m /35 3,4 2,2 35 44,5 45,7 4805 5845 – –
Al/XLPE/CWS/PE-wb
1x70m /35 3,4 1,7 35 27 27 – – 190 383 1028
1x95m /35 3,4 1,8 35 28,9 29 – – 260 383 1170
1x120m /35 3,4 1,9 35 32 32,2 – – 405 383 1445
1x150m /35 3,4 1,9 35 33,6 34 – – 510 383 1580
1x185m /35 3,4 2,0 35 36,6 36,9 – – 690 383 1855
1x240m /35 3,4 2,1 35 38,6 39 – – 630 383 2035
1x300m /35 3,4 2,1 35 38,6 39 – – – – –
19/33 kV
1x120m /35 8,0 2,1 35 39,6 41,1 1443 2417 330 383 1656
1x150m /35 8,0 2,2 35 41,2 44,8 1683 2790 420 383 1935
1x185m /35 8,0 2,2 35 42,9 44,8 2028 3141 510 383 1945
1x240m /35 8,0 2,4 35 47,5 50,0 2548 3767 650 383 2247
1x300m /35 8,0 2,4 35 47,9 50,0 3078 4399 830 383 2515
1x400m /35 8,0 2,5 35 51,6 53,5 3955 5334 1090 383 2922
1x500m /35 8,0 2,6 35 55,0 56,5 4805 6476 1410 383 3444

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the Cu/XLPE/CWS/PE-wb and Al/XLPE/CWS/PE-wb cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available in two nominal voltage levels: Uo/U 6.35/11 kV and 19/33 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to BS 7870-4.10 standards, and the conductor complies with IEC 60228 class 2 and BS 6360.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu or Al stranded compacted conductors with water powder absorbing, and XLPE insulation.

Q:- What is the function of the water resisting element?
A:- The water resisting element, which is a layer of semi-conductive water absorbing tapes, prevents water ingress along the cable.

Q:- What are the color differences between the voltage ratings?
A:- The sheath color is red for the 11kV variant and black for the 33kV variant.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 10 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The temperature of laying is no less than -5°C, and the temperature of explosion is -30 to 50°C.