2XS(F)L2Y / N2XS(F)L2Y / A2XS(F)L2Y / NA2XS(F)L2Y-TRIPLEX 6/10 kV to 18/30 kV Water-Blocking Cable

The 2XS(F)L2Y-TRIPLEX, N2XS(F)L2Y-TRIPLEX, A2XS(F)L2Y-TRIPLEX, and NA2XS(F)L2Y-TRIPLEX cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, water-blocking tapes, and a radial water-absorbing powder, they offer excellent thermal and moisture protection for 6/10 kV, 12/20 kV, and 18/30 kV applications. Because they meet IEC 60502-2 and DIN VDE 0276-620 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
These medium voltage TRIPLEX cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 6/10, 12/20, and 18/30 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for fixed assembly in lines with unlimited difference levels, indoor installations, cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 and DIN VDE 0276-620 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2 and VDE 0295 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. A layer of semi-conductive water absorbing tapes forms the water resisting element. The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. Additionally, a radial water-absorbing powder provides moisture ingress protection. The sheath uses PE compound type ST7 according to IEC 60502 or type DMP 2 according to VDE 0276. The color is black, and these three single-core cables are factory bundled in TRIPLEX. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC60228 class 2 and VDE 0295 class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 6/10, 12/20, and 18/30 kV, while the highest system voltage Uo/U is not more than 6/10, 12/20, and 18/30 kV. Test voltage is AC (+) – 5 min for 6/10 kV (15 kV), 12/20 kV (30 kV), and 18/30 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. Water penetration tests are performed according to the region of metallic screen using IEC 60502-2 annex F. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

 

Construction data 2XS(F)L2Y-TRIPLEX / N2XS(F)L2Y-TRIPLEX, A2XS(F)L2Y-TRIPLEX / NA2XS(F)L2Y-TRIPLEX

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XS(F)L2Y-TRIPLEX Mass of Cu approx. 2XS(F)L2Y-TRIPLEX Mass of cable approx. A2XS(F)L2Y-TRIPLEX Mass of Al approx. A2XS(F)L2Y-TRIPLEX Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
6/10 kV
3x(1x35m/16) 3,4 2,5 16 49,7 60,5 1479 2718 282 2049
3x(1x50m/16) 3,4 2,5 16 51,6 62,2 1812 2979 381 2235
3x(1x70m/16) 3,4 2,5 16 56,2 67,0 2379 3837 549 2538
3x(1x95m/16) 3,4 2,5 16 60,8 69,2 3019 4692 733 2883
3x(1x120m/16) 3,4 2,5 16 64,8 75,6 3765 5438 963 3288
3x(1x150m/25) 3,4 2,5 25 67,3 79,1 4521 6346 1182 3540
3x(1x185m/25) 3,4 2,5 25 69,1 79,9 5538 7025 1485 3975
3x(1x240m/25) 3,4 2,5 25 74,8 79,6 7095 8350 1947 4227
3x(1x300m/25) 3,4 2,5 25 75,7 79,9 8583 9900 2436 4892
3x(1x400m/35) 3,4 2,5 35 77,8 88,8 11641 11256 2947 5547
12/20 kV
3x(1x35m/16) 5,5 2,5 16 58,3 69,2 1479 3243 282 2574
3x(1x50m/16) 5,5 2,5 16 60,0 71,3 1812 3614 381 2811
3x(1x70m/16) 5,5 2,5 16 64,8 75,6 2379 4419 549 3117
3x(1x95m/16) 5,5 2,5 16 66,3 77,1 3019 5199 733 3582
3x(1x120m/16) 5,5 2,5 16 69,1 77,3 3765 5856 963 4089
3x(1x150m/25) 5,5 2,5 25 73,4 84,3 4521 6190 1182 4285
3x(1x185m/25) 5,5 2,5 25 77,8 88,6 5538 7100 1485 4600
3x(1x240m/25) 5,5 2,5 25 84,3 88,6 7000 8092 1947 4971
3x(1x300m/25) 5,5 2,5 25 84,3 88,6 7000 8092 1947 4971
3x(1x400m/35) 5,5 2,5 35 77,8 88,6 5538 7100 2947 4600
18/30 kV
3x(1x50m/16) 8,0 2,5 16 71,3 82,1 1812 4395 381 3402
3x(1x70m/16) 8,0 2,5 16 77,8 88,6 2399 5290 549 4104
3x(1x95m/16) 8,0 2,5 16 82,1 92,9 3059 6504 733 4201
3x(1x120m/16) 8,0 2,5 16 84,3 95,1 3795 6984 963 4550
3x(1x150m/25) 8,0 2,5 25 85,6 96,4 4788 8121 1182 5310
3x(1x185m/25) 8,0 2,5 25 88,6 99,4 5790 9327 1485 5917

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XS(F)L2Y-TRIPLEX cable?
A:- It is designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cable is available in three nominal voltage levels: Uo/U 6/10 kV, 12/20 kV, and 18/30 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 and DIN VDE 0276-620 standards, and the conductor complies with IEC 60228 class 2 and VDE 0295 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What is the function of the water resisting element?
A:- The water resisting element, which is a layer of semi-conductive water absorbing tapes, prevents water ingress along the cable.

Q:- What is the purpose of the radial water-absorbing powder?
A:- The radial water-absorbing powder provides moisture ingress protection by swelling when exposed to water.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What is the maximum force of strain during laying?
A:- The maximum force of strain is 30NS for Al cores and 50NS for Cu cores, where N is the number of cores and S is the cross-section of conductors in mm.

Reviews

There are no reviews yet.

Be the first to review “2XS(F)L2Y / N2XS(F)L2Y / A2XS(F)L2Y / NA2XS(F)L2Y-TRIPLEX 6/10 kV to 18/30 kV Water-Blocking Cable”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS