2XS(F)2Y / N2XS(F)2Y / A2XS(F)2Y / NA2XS(F)2Y 6/10 kV to 18/30 kV Water-Blocking Cable

The 2XS(F)2Y, N2XS(F)2Y, A2XS(F)2Y, and NA2XS(F)2Y cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, water-blocking elements, and a PE outer sheath, they offer excellent thermal and moisture protection for 6/10 kV, 12/20 kV, and 18/30 kV applications. Because they meet IEC 60502-2 and DIN VDE 0276-620 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
These medium voltage cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 6/10, 12/20, and 18/30 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, and power stations. Because of their robust design, they are suitable for use in distribution installations, cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 and DIN VDE 0276-620 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2 and VDE 0295 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. A layer of semi-conductive water absorbing tapes forms the water resisting element. The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. The water resisting element can be either -i-option (water absorbing insulation) or -ii-option (water absorbing powder and a layer of plastic tape). The sheath uses PE compound type ST7 according to IEC 60502 or type DMP2 according to VDE 0276. The color is black. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BDS904 (IEC60228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 6/10, 12/20, and 18/30 kV, while the highest system voltage Uo/U is not more than 6/10, 12/20, and 18/30 kV. Test voltage is AC (+) – 5 min for 6/10 kV (15 kV), 12/20 kV (30 kV), and 18/30 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XS(F)2Y/N2XS(F)2Y, A2XS(F)2Y/NA2XS(F)2Y

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XS(F)2Y, N2XS(F)2Y Mass of Cu approx. 2XS(F)2Y, N2XS(F)2Y Mass of sheath approx. A2XS(F)2Y, NA2XS(F)2Y Mass of Al approx. A2XS(F)2Y, NA2XS(F)2Y Mass of sheath approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
6/10 kV
1x35m/16 3,4 2,5 16 23 28 693 94 176
1x50m/16 3,4 2,5 16 24 29 804 127 176
1x70m/16 3,4 2,5 16 26 31 904 183 745
1x95m/16 3,4 2,5 16 27 32 1279 187 870
1x120m/16 3,4 2,5 16 28 33 1635 187 917
1x150m/16 3,4 2,5 16 30 35 1555 321 1064
1x185m/25 3,4 2,5 25 32 37 2010 384 1199
1x240m/25 3,4 2,5 25 34 39 2350 494 1294
1x300m/25 3,4 2,5 25 36 41 2980 607 1550
1x400m/35 3,4 2,5 35 39 45 3620 784 1851
1x500m/35 3,4 2,5 35 43 48 4350 1374 2249
1x630m/35 3,4 2,5 35 45 51 4810 363 2549
12/20 kV
1x35m/16 5,5 2,5 16 27 32 483 1081 85
1x50m/16 5,5 2,5 16 28 33 644 758 1053
1x70m/16 5,5 2,5 16 30 35 793 176 1053
1x95m/16 5,5 2,5 16 31 36 1033 251 1055
1x120m/16 5,5 2,5 16 33 38 1309 321 1055
1x150m/16 5,5 2,5 16 34 39 1558 384 1127
1x185m/16 5,5 2,5 16 36 41 1841 384 1403
1x240m/16 5,5 2,5 16 39 44 2345 479 1500
1x300m/25 5,5 2,5 25 41 46 2818 684 1583
1x400m/35 5,5 2,5 35 44 49 3836 812 2149
1x500m/35 5,5 2,5 35 47 52 4867 1043 2317
18/30 kV
1x50m/16 8 2,5 16 33 38 604 127 176
1x70m/16 8 2,5 16 35 41 803 176 1154
1x95m/16 8 2,5 16 37 41 1081 251 1233
1x120m/16 8 2,5 16 38 43 1255 321 1370
1x150m/16 8 2,5 16 39 44 1498 351 1530
1x185m/25 8 2,5 25 41 46 1953 510 1951
1x240m/25 8 2,5 25 43 48 2444 648 1990
1x300m/25 8 2,5 25 46 51 2980 835 2140
1x400m/35 8 2,5 35 48 54 3527 853 2549
1x500m/35 8 2,5 35 52 57 4807 1374 3343

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XS(F)2Y cable?
A:- It is designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cable is available in three nominal voltage levels: Uo/U 6/10 kV, 12/20 kV, and 18/30 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 and DIN VDE 0276-620 standards, and the conductor complies with IEC 60228 class 2 and VDE 0295 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What is the function of the water resisting element?
A:- The water resisting element, which is a layer of semi-conductive water absorbing tapes, prevents water ingress along the cable, with options for water absorbing insulation or water absorbing powder and plastic tape.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.

Q:- What is the maximum force of strain during laying?
A:- The maximum force of strain is 30NS for Al cores and 50NS for Cu cores, where N is the number of cores and S is the cross-section of conductors in mm.