2XSEYBY & A2XSEYBY 6/10 kV to 18/30 kV Armoured XLPE Three-Core Cable – IEC 60502-2

The 2XSEYBY and A2XSEYBY cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, steel tape armour, and a red PVC outer sheath, they offer excellent thermal and mechanical protection for 6/10 kV, 12/20 kV, and 18/30 kV applications. Because they meet IEC 60502-2 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
2XSEYBY and A2XSEYBY medium voltage three-core cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 6/10, 12/20, and 18/30 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for use in distribution installations and cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. The metal screen can be either -i-option (Cu tapes laid with overlap over each phase) or -ii-option (Cu wires laid concentrically). The cable assembly features three insulated and screened phases twisted with fillers and a tape separator. A PVC compound forms the inner sheath, and the armour consists of two steel tapes or two galvanized steel tapes. Finally, a red PVC compound type ST2 sheath (according to IEC 60502) protects the entire assembly. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BDS904 (IEC60228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 6/10, 12/20, and 18/30 kV, while the highest system voltage Uo/U is not more than 6/10, 12/20, and 24/36 kV. Test voltage is AC (+) – 5 min for 6/10 kV (15 kV), 12/20 kV (30 kV), and 18/30 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XSEYBY, A2XSEYBY 6/10; 12/20; 18/30 kV

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XSEYBY Mass of Cu approx. 2XSEYBY Mass of cable approx. A2XSEYBY Mass of Al approx. A2XSEYBY Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
6/10 kV
3×35 m/16 3,4 2,5 16 48,4 1010 3639 298 2963
3×50 m/16 3,4 2,6 16 51,0 1363 4095 404 3292
3×70 m/16 3,4 2,7 16 55,5 1983 4733 544 3536
3×95 m/16 3,4 2,9 16 59,3 2732 6239 809 4412
3×120 m/16 3,4 3,0 16 62,5 3440 6799 1023 4809
3×150 m/25 3,4 3,1 25 65,5 4245 7433 1257 5555
3×185 m/25 3,4 3,2 25 70,5 5311 8831 1579 6285
3×240 m/25 3,4 3,4 25 75,3 6981 10031 2071 7337
3×300 m/25 3,4 3,7 25 82,2 8861 13303 2589 8253
12/20 kV
3×35 m/16 5,5 2,9 16 58,7 1010 4717 298 4041
3×50 m/16 5,5 2,9 16 61,3 1363 5286 404 4376
3×70 m/16 5,5 3,1 16 65,5 1968 6281 584 4967
3×95 m/16 5,5 3,1 16 67,5 2730 6579 809 5137
3×120 m/16 5,5 3,3 16 72,8 3440 8430 1023 6134
3×150 m/25 5,5 3,4 25 76,7 4245 9756 1257 6918
3×185 m/25 5,5 3,5 25 81,0 5311 11481 1579 8016
3×240 m/25 5,5 3,8 25 87,7 6981 14364 2071 9700
18/30 kV
3×50 m/16 8,0 3,3 16 73,7 1363 6765 404 5854
3×70 m/16 8,0 3,5 16 78,0 1968 7852 584 6538
3×95 m/16 8,0 3,6 16 81,0 2730 8352 809 6825
3×120 m/16 8,0 3,8 16 86,7 3440 10996 1023 8701
3×150 m/25 8,0 3,9 25 90,5 4245 12482 1257 9623

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XSEYBY and A2XSEYBY cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available in three nominal voltage levels: Uo/U 6/10 kV, 12/20 kV, and 18/30 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 standards, and the conductor complies with IEC 60228 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What type of metal screen and armour are used?
A:- The metal screen uses Cu tapes laid with overlap or Cu wires laid concentrically, and the armour consists of two steel tapes or two galvanized steel tapes.

Q:- What is the cable assembly design?
A:- The cable assembly features three insulated and screened phases twisted with fillers and a tape separator.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.

Reviews

There are no reviews yet.

Be the first to review “2XSEYBY & A2XSEYBY 6/10 kV to 18/30 kV Armoured XLPE Three-Core Cable – IEC 60502-2”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS