Application
2XSEYBY and A2XSEYBY medium voltage three-core cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 3.6/6, 8.7/15, and 20/35 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for fixed assembly in lines with unlimited difference levels, indoor installations, cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. The metal screen uses Cu tapes laid with overlap over each phase, or Cu wires laid concentrically. The cable assembly features three insulated and screened phases twisted with fillers and a tape separator. A PVC compound forms the inner sheath, and the armour consists of two steel tapes or two steel galvanized tapes. Finally, a red PVC compound type ST2 sheath (according to IEC 60502) protects the entire assembly. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BDS904 (IEC60228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 6/10 and 12/20 kV, while the highest system voltage Uo/U is not more than 6/10, 12/20, and 24 kV. Test voltage is AC (+) – 5 min for 6/10 kV (15 kV), 12/20 kV (30 kV), and 18/30 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XSEYBY, A2XSEYBY 3.6/6; 8.7/15; 20/35 kV

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XSEYBY Mass of Cu approx. 2XSEYBY Mass of cable approx. A2XSEYBY Mass of Al approx. A2XSEYBY Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
3.6/6 kV
3×35 m/16 2,5 2,5 16 44,3 1010 3579 298 2694
3×50 m/16 2,5 2,5 16 46,7 1363 3870 404 2871
3×70 m/16 2,5 2,6 16 50,8 1968 4690 584 3382
3×95 m/16 2,5 2,7 16 54,8 2732 5745 809 3937
3×120 m/16 2,5 2,8 16 58,1 3440 6798 1023 4468
3×150 m/25 2,5 3,0 25 62,1 4245 7920 1257 5081
3×185 m/25 2,5 3,1 25 66,0 5311 9489 1579 5719
3×240 m/25 2,5 3,3 25 72,4 6981 11481 2071 6617
3×300 m/25 2,8 3,5 25 76,8 8861 13751 2589 7863
8.7/15 kV
3×35 m/16 4,5 2,7 16 54,0 1010 4210 298 3534
3×50 m/16 4,5 2,7 16 55,5 1363 4813 404 3860
3×70 m/16 4,5 2,9 16 60,6 1968 5714 584 4400
3×95 m/16 4,5 3,0 16 64,6 2730 6867 809 5030
3×120 m/16 4,5 3,1 16 67,6 3440 7810 1023 5529
3×150 m/25 4,5 3,2 25 72,0 4245 9125 1257 6283
3×185 m/25 4,5 3,4 25 76,0 5311 10552 1579 7016
3×240 m/25 4,5 3,5 25 81,6 6981 13146 2071 8206
20/35 kV
3×50 m/16 8,8 3,5 16 77,8 1363 7316 404 6405
3×70 m/16 8,8 3,6 16 81,8 1968 8681 584 7075
3×95 m/16 8,8 3,7 16 85,4 2730 9061 809 7708
3×120 m/16 8,8 3,9 16 90,5 3440 11658 1023 9331
3×150 m/25 8,8 4,0 25 94,4 4245 13106 1257 10268

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XSEYBY and A2XSEYBY cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available in three nominal voltage levels: Uo/U 3.6/6 kV, 8.7/15 kV, and 20/35 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 standards, and the conductor complies with IEC 60228 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What type of metal screen and armour are used?
A:- The metal screen uses Cu tapes laid with overlap or Cu wires laid concentrically, and the armour consists of two steel tapes or two steel galvanized tapes.

Q:- What is the cable assembly design?
A:- The cable assembly features three insulated and screened phases twisted with fillers and a tape separator.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.

Reviews

There are no reviews yet.

Be the first to review “2XSEYBY & A2XSEYBY 3.6/6 kV to 20/35 kV Armoured XLPE Three-Core Cable”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS