FRT-XCSH Flame Retardant Screened 4-Core Cable
This flame retardant screened 4-core cable is engineered for Variable Speed Drive (VSD) and instrumentation applications. It features plain annealed copper conductors with XLPE insulation and a copper tape/tinned copper wire braid screen for excellent interference protection. The LSZH outer sheath and galvanized steel wire armour ensure safety with low smoke, zero halogen, and flame retardant properties. Available in sizes from 1.5mm² to 300mm², it is compliant with IEC 60502 and IEC 60332-3 standards.
This 4-core flame retardant screened cable is specifically designed for a broad spectrum of Variable Speed Drive (VSD) applications and also includes instrumentation and control cable applications. Because it is manufactured with plain annealed copper conductors and XLPE insulation, it is exceptionally reliable for demanding industrial power and control circuits. Furthermore, the cable features a screen of copper tapes and a tinned copper wire braid that drastically reduces interferences from electrical noise, especially in VSD applications. Consequently, these cables are highly suitable for critical installations where both performance and fire safety are paramount.
The cable structure features a plain annealed copper conductor with Class 2 stranding, insulated with XLPE compound. The assembly includes a bedding and sheath made of LSZH compound, copper tapes for screening, and galvanized steel wire armour for mechanical protection. The outer sheath is a robust LSZH (Low Smoke Zero Halogen) compound in black, with insulation colors of red, yellow, blue, green/yellow for easy identification.
Technical Data & Construction Overview:
-
Reference Standard: IEC 60502
-
Test Standard: IEC 60332-3, BS 4066, IEC 60754, BS 6425, IEC 61034, BS 7622-Part-2
-
Voltage Uo/U: 600/1000V
-
Conductor Stranding: Class 2
-
Operating Temperature: (a) Max 90°C for XLPE; (b) Max 110°C for XLEVA
-
Minimum Bending Radius: 12D for 1.5mm² to 300mm²
Construction Data (FRT-XCSH)
| Size | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Nominal Conductor Area (mm²) | No. & Dia. of Wires (no./mm) | Radial Thick. of Insulation (mm) | Radial Thick. of Sheath (mm) | Dia. Under Screen (mm) | Dia. Over Bedding (mm) | Armour Wire Dia. (mm) | Cable Overall Dia. (mm) | Approx. Weight (kg/km) | |
| 4 x 1.5 | 7 / 0.53 | 0.7 | 1.8 | 9.7 | 12.1 | 13.9 | 17.7 | 640 | |
| 4 x 2.5 | 7 / 0.67 | 0.7 | 1.8 | 10.7 | 13.1 | 14.9 | 18.7 | 730 | |
| 4 x 4 | 7 / 0.85 | 0.7 | 1.8 | 12.0 | 14.4 | 16.2 | 20.0 | 870 | |
| 4 x 6 | 7 / 1.04 | 0.7 | 1.8 | 13.4 | 15.8 | 18.3 | 22.1 | 1130 | |
| 4 x 10 | 7 / 1.35 | 0.7 | 1.8 | 15.6 | 18.0 | 20.5 | 24.3 | 1480 | |
| 4 x 16 | 7 / 1.70 | 0.7 | 1.8 | 18.1 | 20.5 | 23.7 | 27.6 | 2070 | |
| 4 x 25 | 7 / 2.14 | 0.9 | 1.8 | 22.3 | 24.1 | 27.3 | 31.1 | 2790 | |
| 4 x 35 (S) | 7 / 2.52 | 0.9 | 1.8 | 25.0 | 26.8 | 30.0 | 33.8 | 2940 | |
| 4 x 50 (S) | 19 / 1.78 | 1.0 | 2.0 | 27.8 | 29.6 | 32.8 | 37.0 | 3500 | |
| 4 x 70 (S) | 19 / 2.14 | 1.1 | 2.2 | 31.6 | 33.4 | 37.4 | 42.0 | 5000 | |
| 4 x 95 (S) | 19 / 2.52 | 1.1 | 2.3 | 35.4 | 37.2 | 41.2 | 46.0 | 6300 | |
| 4 x 120 (S) | 37 / 2.03 | 1.2 | 2.5 | 39.0 | 40.8 | 45.8 | 51.0 | 8200 | |
| 4 x 150 (S) | 37 / 2.25 | 1.4 | 2.6 | 42.0 | 43.8 | 48.8 | 54.2 | 9600 | |
| 4 x 185 (S) | 37 / 2.52 | 1.6 | 2.8 | 47.8 | 49.6 | 54.6 | 60.0 | 11500 | |
| 4 x 240 (S) | 61 / 2.25 | 1.7 | 3.0 | 54.0 | 55.8 | 60.8 | 67.0 | 14400 | |
| 4 x 300 (S) | 61 / 2.52 | 1.8 | 3.0 | 58.0 | 59.8 | 64.8 | 71.4 | 17200 |
(S): Sectional Stranded Conductor.
This cable is designed specifically to suit the broad spectrum of requirements of Variable Speed Drives and also includes instrumentation and control cable applications. This range of screened cables drastically reduce interferences from electrical noise, especially in Variable Speed Drive (VSD) applications and are manufactured with fixed conductors. With shield conductivity of 1/10th of phase conductor conductivity, this range of VSD cables effectively restrain radiated and conducted radio-frequency emissions. An additional trait of these cables that are designed to be Low Smoke, Zero Halogen and Flame Retardant. Applicable standards include IEC 60754, IEC 60332-3 and IEC 61034.
Factory Overview
Packaging & Shipping
Frequently asked questions and answer (Q:- A:-)
Q:- What is the primary application of the FRT-XCSH cable?
A:- It is designed for Variable Speed Drive (VSD) applications and instrumentation and control cable applications.
Q:- What type of conductor is used?
A:- It features a plain annealed copper conductor with Class 2 stranding.
Q:- What is the reference standard for this cable?
A:- The reference standard is IEC 60502.
Q:- What is the voltage rating?
A:- The voltage rating is Uo/U 600/1000V.
Q:- What is the maximum operating temperature?
A:- The maximum operating temperature is 90°C for XLPE insulation.
Q:- What is the minimum bending radius?
A:- The minimum bending radius is 12D for cable sizes from 1.5mm² to 300mm².
Q:- What type of screen is used?
A:- The cable features copper tapes and a tinned copper wire braid screen.
Q:- What material is used for the outer sheath?
A:- The outer sheath is made of LSZH (Low Smoke Zero Halogen) compound in black.
Q:- How does the screen help with VSD applications?
A:- The screen drastically reduces interferences from electrical noise and restrains radiated and conducted radio-frequency emissions.
Q:- What is the armour wire diameter for the 4×1.5 cable?
A:- The armour wire diameter is 13.9mm for the 4×1.5 cable.




Reviews
There are no reviews yet.