FRT-XOL & FRT-XOSL Flame Retardant Instrumentation Cables
The FRT-XOL and FRT-XOSL cables deliver dependable signal transmission for industrial and infrastructure instrumentation systems. Constructed with plain annealed copper conductors, F.R. compound insulation, and LSF sheathing, they offer excellent fire safety and interference protection. Because they meet BS 5308 and IEC 60332-3 standards and are RoHS compliant, they provide a safe and reliable solution for critical data circuits and process control applications.
Application
FRT-XOL and FRT-XOSL cables provide reliable signal transmission for industrial and infrastructure instrumentation systems. Because they feature flame retardant construction and robust screening options, installers use them to protect critical data circuits from electromagnetic interference. Furthermore, these cables are designed to maintain circuit integrity and prevent fire propagation in demanding environments. Consequently, they deliver consistent and safe performance for process control and monitoring applications.
Cable construction
These cables are manufactured to rigorous standards including BS 5308, BS 7621, BS 6724, and IEC 60332-3. They feature plain annealed copper conductors (Class 2 or 5) according to IEC 60228. The insulation uses a specially formulated F.R. compound. A screen of aluminium/polyester tape (with 0.5mm² tinned drain wire) and a galvanized steel wire braid (0.7mm²) provides dual-layer protection for the XOSL variant. The outer sheath is a black LSF (Low Smoke Fume) compound. The operating temperature ranges from -90°C to +90°C for fixed applications and -110°C to +110°C for mobile applications.
Technical Data
The cable delivers consistent performance under specific conditions. The voltage rating is Uo/U 300/500V. It passes the flame test according to IEC 60332-3 and BS 4066. The single-pair variant has a minimum bending radius of 8D (unarmoured) or 10D (armoured), while multi-pair variants are 10D (unarmoured) or 15D (armoured). The reference standards include BS 5308 / BS 7211 / BS 6724.
Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
FRT-XOL (Unarmoured)
| Size | No. of Pairs | Approx. Cable Dia. | Approx. Cable Weight |
|---|---|---|---|
| mm² | mm | kg/km | |
| 1P x 0.5 | 1 | 7.0 | 90 |
| 2P x 0.5 | 2 | 10.8 | 156 |
| 5P x 0.5 | 5 | 13.1 | 170 |
| 10P x 0.5 | 10 | 17.2 | 280 |
| 15P x 0.5 | 15 | 19.8 | 380 |
| 20P x 0.5 | 20 | 22.3 | 460 |
| 30P x 0.5 | 30 | 26.9 | 690 |
| 50P x 0.5 | 50 | 33.9 | 1080 |
| 1P x 0.75 | 1 | 8.2 | 81 |
| 2P x 0.75 | 2 | 12.0 | 202 |
| 5P x 0.75 | 5 | 14.2 | 224 |
| 10P x 0.75 | 10 | 18.4 | 284 |
| 15P x 0.75 | 15 | 21.3 | 424 |
| 20P x 0.75 | 20 | 24.0 | 570 |
| 30P x 0.75 | 30 | 29.0 | 750 |
| 50P x 0.75 | 50 | 37.3 | 1546 |
| 1P x 1.0 | 1 | 8.3 | 85 |
| 2P x 1.0 | 2 | 13.5 | 200 |
| 5P x 1.0 | 5 | 16.6 | 335 |
| 10P x 1.0 | 10 | 21.6 | 540 |
| 15P x 1.0 | 15 | 25.5 | 750 |
| 20P x 1.0 | 20 | 28.8 | 860 |
| 30P x 1.0 | 30 | 34.3 | 1046 |
| 50P x 1.0 | 50 | 43.6 | 2040 |
FRT-XOSL (Armoured)
| Size | No. of Pairs | Approx. Cable Dia. | Approx. Cable Weight |
|---|---|---|---|
| mm² | mm | kg/km | |
| 1P x 0.5 | 1 | 9.0 | 230 |
| 2P x 0.5 | 2 | 11.4 | 262 |
| 5P x 0.5 | 5 | 15.7 | 300 |
| 10P x 0.5 | 10 | 22.9 | 830 |
| 15P x 0.5 | 15 | 24.4 | 1100 |
| 20P x 0.5 | 20 | 26.1 | 1320 |
| 30P x 0.5 | 30 | 33.1 | 1750 |
| 50P x 0.5 | 50 | 42.1 | 2730 |
| 1P x 0.75 | 1 | 9.0 | 230 |
| 2P x 0.75 | 2 | 12.8 | 342 |
| 5P x 0.75 | 5 | 17.0 | 480 |
| 10P x 0.75 | 10 | 24.3 | 880 |
| 15P x 0.75 | 15 | 26.1 | 1380 |
| 20P x 0.75 | 20 | 28.1 | 1650 |
| 30P x 0.75 | 30 | 35.7 | 2600 |
| 50P x 0.75 | 50 | 45.7 | 3430 |
| 1P x 1.0 | 1 | 9.5 | 290 |
| 2P x 1.0 | 2 | 13.0 | 380 |
| 5P x 1.0 | 5 | 18.0 | 470 |
| 10P x 1.0 | 10 | 25.4 | 950 |
| 15P x 1.0 | 15 | 28.6 | 1410 |
| 20P x 1.0 | 20 | 31.1 | 1740 |
| 30P x 1.0 | 30 | 37.5 | 2460 |
| 50P x 1.0 | 50 | 53.4 | 4920 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of these flame retardant instrumentation cables?
A:- They are used for signal transmission in industrial and infrastructure instrumentation systems, providing reliable data communication while preventing fire propagation.
Q:- What standards do these cables adhere to?
A:- They are manufactured to rigorous standards including BS 5308, BS 7211, BS 6724, IEC 60332-3, IEC 60332-3, IEC 60754, and BS 7655.
Q:- What are the differences between the FRT-XOL and FRT-XOSL variants?
A:- The FRT-XOL is the unarmoured version with a single screen, while the FRT-XOSL is the armoured version featuring dual-layer protection with an aluminium/polyester tape screen and a galvanized steel wire braid.
Q:- What type of conductor and insulation do these cables use?
A:- They use plain annealed copper conductors (Class 2 or 5) with a specially formulated flame retardant (F.R.) compound insulation.
Q:- What is the voltage rating of these cables?
A:- The voltage rating is Uo/U 300/500V.
Q:- What is the operating temperature range?
A:- The operating temperature ranges from -90°C to +90°C for fixed applications and -110°C to +110°C for mobile applications.
Q:- What is the minimum bending radius for installation?
A:- For single-pair cables, it is 8D (unarmoured) or 10D (armoured). For multi-pair cables, it is 10D (unarmoured) or 15D (armoured).
Q:- What type of outer sheath is used?
A:- A black LSF (Low Smoke Fume) compound is used for the outer sheath.
Q:- Are these cables RoHS compliant?
A:- Yes, the product is RoHS compliant.
Q:- Are other conductor sizes and pair configurations available?
A:- Yes, other conductor sizes and pair configurations are available upon request.




Reviews
There are no reviews yet.