SHEmeT / SAHEmeT 3.6/6 kV to 20/35 kV Three-Core XLPE Insulated Copper & Aluminium Conductor Medium Voltage Power Cable – BDS 2581-86
SHEmeT and SAHEmeT are three-core medium voltage XLPE-insulated power cables designed for reliable electrical power transmission and distribution in urban networks, transformer substations, and industrial installations. Manufactured according to BDS 2581-86, these cables feature stranded and compacted Class 2 copper or aluminium conductors, semiconductive XLPE layers, XLPE insulation, and individual copper wire screening with contact copper tape. The three screened cores are assembled with filling materials and tape support, followed by a PVC inner sheath and protective red PVC Type P-5 outer sheath. Available in voltage ratings from 3.6/6 kV to 20/35 kV, they are suitable for underground installations, cable ducts, conduits, shafts, and industrial power distribution systems.
Application
SHEmeT and SAHEmeT three-core cables with XLPE (Cross-Linked Polyethylene) insulation are designed for the transmission and distribution of electrical power at nominal voltages of 3.6/6 kV, 6/10 kV, 12/20 kV, 18/30 kV, and 20/35 kV, with a frequency of 50 Hz.
They are mainly used in urban and district electrical networks, transformer substations, small and medium industrial plants, and electrical power distribution systems.
These cables are suitable for fixed installation in lines with unlimited differences in level, indoor installations, cable ducts, conduits, shafts, over shelves and grills, direct underground installation in ditches, and outdoor installations under shelters.
Cable Construction
Manufactured according to BDS 2581-86.
-
Conductor: Stranded and compacted copper or aluminium conductors according to BDS 904 (IEC 60228), Class 2.
-
Inner semiconductive layer: Semiconductive XLPE compound.
-
Insulation: XLPE (Cross-Linked Polyethylene) compound.
-
Outer semiconductive layer: Semiconductive XLPE compound.
-
Metal screen: Copper wires concentrically laid with one contact copper tape of 0.1 mm thickness, or copper tapes laid with overlap over each phase.
-
Cable assembly: Three insulated and screened phases are twisted with fillings and tape support.
-
Inner sheath: PVC compound.
-
Outer sheath: PVC compound, Type P-5 according to BDS 2581.
-
Outer sheath colour: Red.
-
Compliance: RoHS compliant.
Cable Type Identification
| Cable designation | Conductor material |
|---|---|
| SHEmeT | Copper |
| SAHEmeT | Aluminium |
Technical Data
| Parameter | Specification |
|---|---|
| Applicable standard | BDS 2581-86 |
| Conductor standard | BDS 904 (IEC 60228), Class 2 |
| Conductor material | Copper / Aluminium |
| Number of cores | 3 |
| Conductor resistance at 20°C | According to BDS 904 (IEC 60228), Class 2 |
| Continuous operating temperature | +90°C |
| Overload temperature | +130°C / 100 hours per year maximum |
| Maximum short-circuit temperature | +250°C / 5 seconds maximum |
| Nominal voltage (Uo/U) | 3.6/6, 6/10, 12/20, 18/30, 20/35 kV |
| Highest system voltage (U) | 7.2, 12, 24, 36, 42 kV |
| AC test duration | 5 minutes |
| DC test duration | 15 minutes |
| Partial discharge at 2 × Uo | Maximum 5 pC |
| Minimum bending radius | 15 × D (cable diameter) |
| Minimum laying temperature | Not less than -5°C |
| Operating temperature range | -30°C to +50°C |
| Tests | According to BDS 2581 |
Voltage Test Data
| Nominal voltage (Uo/U) | AC test voltage | DC test voltage |
|---|---|---|
| 3.6/6 kV | 11 kV | 29 kV |
| 6/10 kV | 15 kV | 48 kV |
| 12/20 kV | 30 kV | 98 kV |
| 18/30 kV | 45 kV | 144 kV |
| 20/35 kV | 50 kV | 160 kV |
AC test duration: 5 minutes. DC test duration: 15 minutes.
Colour Coding
-
Outer sheath colour: Red.
-
Individual core insulation colour coding is not specified in the supplied catalogue.
3. Construction Data Tables
All dimensions are in mm and all material and cable weights are in kg/km.
Column identification:
-
Ins. = Insulation thickness
-
Sheath = Inner/outer sheath thickness
-
Screen = Nominal cross-section of screen
-
Dia. = Approximate cable diameter
-
Cu = Copper conductor weight
-
Al = Aluminium conductor weight
-
Cable = Approximate total cable weight
Construction Data – 3.6/6 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEmeT Cu | SHEmeT Cable | SAHEmeT Al | SAHEmeT Cu | SAHEmeT Cable |
|---|---|---|---|---|---|---|---|---|---|
| 3×35rm/16 | 2.5 | 2.5 | 16 | 42 | 1155 | 2605 | 295 | 176 | 1930 |
| 3×50rm/16 | 2.5 | 2.5 | 16 | 44 | 1565 | 3075 | 405 | 176 | 2165 |
| 3×70rm/16 | 2.5 | 2.5 | 16 | 48 | 2125 | 3900 | 585 | 176 | 2590 |
| 3×95rm/16 | 2.5 | 2.7 | 16 | 52 | 2825 | 4910 | 810 | 176 | 3085 |
| 3×120rm/16 | 2.5 | 2.8 | 16 | 55 | 3525 | 5785 | 1020 | 176 | 3485 |
| 3×150rm/16 | 2.5 | 2.9 | 16 | 58.5 | 4360 | 6860 | 1255 | 176 | 4025 |
| 3×185rm/16 | 2.5 | 3.0 | 16 | 62.5 | 5335 | 8180 | 1560 | 176 | 4635 |
| 3×240rm/16 | 2.5 | 3.2 | 16 | 68 | 6895 | 10235 | 2055 | 176 | 5570 |
| 3×150rm/25 | 2.5 | 2.9 | 25 | 59 | 4450 | 6940 | 1255 | 265 | 4105 |
| 3×185rm/25 | 2.5 | 3.0 | 25 | 63 | 5425 | 8265 | 1560 | 265 | 4720 |
| 3×240rm/25 | 2.6 | 3.2 | 25 | 68.5 | 6985 | 10330 | 2055 | 265 | 5665 |
Construction Data – 6/10 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEmeT Cu | SHEmeT Cable | SAHEmeT Al | SAHEmeT Cu | SAHEmeT Cable |
|---|---|---|---|---|---|---|---|---|---|
| 3×35rm/16 | 3.4 | 2.5 | 16 | 45 | 1155 | 2905 | 295 | 176 | 2230 |
| 3×50rm/16 | 3.4 | 2.5 | 16 | 47.5 | 1565 | 3405 | 405 | 176 | 2495 |
| 3×70rm/16 | 3.4 | 2.6 | 16 | 52.5 | 2125 | 4275 | 585 | 176 | 2965 |
| 3×95rm/16 | 3.4 | 2.8 | 16 | 56 | 2825 | 5305 | 810 | 176 | 3480 |
| 3×120rm/16 | 3.4 | 2.9 | 16 | 59 | 3525 | 6195 | 1020 | 176 | 3895 |
| 3×150rm/16 | 3.4 | 3.0 | 16 | 62 | 4360 | 7295 | 1255 | 176 | 5105 |
| 3×185rm/16 | 3.4 | 3.1 | 16 | 65 | 5335 | 8655 | 1560 | 176 | 6060 |
| 3×240rm/16 | 3.4 | 3.3 | 16 | 72 | 6895 | 10730 | 2055 | 176 | 5105 |
| 3×150rm/25 | 3.4 | 3.0 | 25 | 62.5 | 4450 | 7380 | 1255 | 265 | 5195 |
| 3×185rm/25 | 3.4 | 3.2 | 25 | 65.5 | 5425 | 8740 | 1560 | 265 | 6150 |
| 3×240rm/25 | 3.4 | 3.4 | 25 | 73 | 6985 | 10815 | 2055 | 265 | 7135 |
Construction Data – 12/20 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEmeT Cu | SHEmeT Cable | SAHEmeT Al | SAHEmeT Cu | SAHEmeT Cable |
|---|---|---|---|---|---|---|---|---|---|
| 3×35rm/16 | 5.5 | 2.8 | 16 | 55.5 | 1155 | 3790 | 295 | 176 | 3115 |
| 3×50rm/16 | 5.5 | 2.9 | 16 | 57.5 | 1565 | 4345 | 405 | 176 | 3430 |
| 3×70rm/16 | 5.5 | 3.0 | 16 | 62 | 2125 | 5245 | 585 | 176 | 3930 |
| 3×95rm/16 | 5.5 | 3.1 | 16 | 66 | 2825 | 6330 | 810 | 176 | 4500 |
| 3×120rm/16 | 5.5 | 3.2 | 16 | 68 | 3525 | 7275 | 1020 | 176 | 4975 |
| 3×150rm/16 | 5.5 | 3.4 | 16 | 72 | 4360 | 8475 | 1255 | 176 | 5635 |
| 3×185rm/16 | 5.5 | 3.5 | 16 | 76 | 5335 | 9875 | 1560 | 176 | 6330 |
| 3×240rm/16 | 5.5 | 3.7 | 16 | 82 | 6895 | 12065 | 2055 | 176 | 7400 |
| 3×150rm/25 | 5.5 | 3.4 | 25 | 73 | 4450 | 8565 | 1255 | 265 | 5725 |
| 3×185rm/25 | 5.5 | 3.5 | 25 | 77 | 5425 | 9865 | 1560 | 265 | 6420 |
| 3×240rm/25 | 5.5 | 3.7 | 25 | 83 | 6985 | 12155 | 2055 | 265 | 7490 |
Construction Data – 18/30 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEmeT Cu | SHEmeT Cable | SAHEmeT Al | SAHEmeT Cu | SAHEmeT Cable |
|---|---|---|---|---|---|---|---|---|---|
| 3×50rm/16 | 8.0 | 3.3 | 16 | 70 | 1565 | 5625 | 405 | 176 | 4710 |
| 3×70rm/16 | 8.0 | 3.4 | 16 | 74 | 2125 | 6610 | 585 | 176 | 5295 |
| 3×95rm/16 | 8.0 | 3.5 | 16 | 78 | 2825 | 7790 | 810 | 176 | 5960 |
| 3×120rm/16 | 8.0 | 3.6 | 16 | 82 | 3525 | 8815 | 1020 | 176 | 6520 |
| 3×150rm/25 | 8.0 | 3.8 | 25 | 86 | 4450 | 10185 | 1255 | 265 | 7345 |
Construction Data – 20/35 kV
| Nominal construction | Ins. | Sheath | Screen | Dia. | SHEmeT Cu | SHEmeT Cable | SAHEmeT Al | SAHEmeT Cu | SAHEmeT Cable |
|---|---|---|---|---|---|---|---|---|---|
| 3×50rm/16 | 8.8 | 3.4 | 16 | 74 | 1565 | 6075 | 405 | 176 | 5165 |
| 3×70rm/16 | 8.8 | 3.5 | 16 | 78 | 2125 | 7080 | 585 | 176 | 5765 |
| 3×95rm/16 | 8.8 | 3.7 | 16 | 82 | 2825 | 8280 | 810 | 176 | 6455 |
| 3×120rm/16 | 8.8 | 3.8 | 16 | 86 | 3525 | 9345 | 1020 | 176 | 7050 |
| 3×150rm/25 | 8.8 | 3.9 | 25 | 89 | 4450 | 10720 | 1255 | 265 | 7885 |
Factory Overview
Packaging & Shipping
Frequently Asked Questions (FAQ)
Q:- What is the primary application of SHEmeT and SAHEmeT cables?
A:- These cables are designed for medium-voltage electrical power transmission and distribution in urban networks, transformer substations, industrial plants, and electrical power stations.
Q:- What is the difference between SHEmeT and SAHEmeT cables?
A:- SHEmeT uses copper conductors, while SAHEmeT uses aluminium conductors. Both feature XLPE insulation, copper wire screening, PVC inner sheath, and PVC outer sheath.
Q:- What standards do these cables follow?
A:- They are manufactured according to BDS 2581-86.
Q:- What type of conductor is used?
A:- Both variants use stranded and compacted Class 2 copper or aluminium conductors according to IEC 60228.
Q:- What insulation material is used?
A:- They use XLPE (Cross-Linked Polyethylene) insulation with inner and outer semiconductive layers.
Q:- What type of metallic screen is used?
A:- The cables use concentrically laid copper wires with a 0.1 mm contact copper tape, or overlapping copper tapes over each phase.
Q:- How are the three cores assembled?
A:- Three individually insulated and screened phases are twisted together with filling materials and tape support.
Q:- What is the maximum continuous operating temperature?
A:- The maximum continuous conductor operating temperature is +90°C.
Q:- What is the maximum short-circuit temperature?
A:- The maximum short-circuit temperature is +250°C for a maximum of 5 seconds.
Q:- What voltage ratings are available?
A:- The cables are available in 3.6/6 kV, 6/10 kV, 12/20 kV, 18/30 kV, and 20/35 kV voltage ratings.




Reviews