JE-HCH …x2x0.8 BD Halogen-Free Paired Control Cable – VDE 0815
The JE-HCH …x2x0.8 BD cable delivers dependable signal and data transmission for control circuits. Constructed with bare copper conductors, halogen-free polymer insulation, a tinned copper braid screen, and a flame-retardant halogen-free outer sheath, it offers exceptional fire safety and signal integrity. Because it meets VDE 0815 standards and is RoHS compliant, it provides a safe and reliable solution for safety installations where protection against fire and equipment damage is critical.
Application
JE-HCH cables provide reliable transmission of signals and measuring data in control circuits. Because they are designed with halogen-free materials and a copper braid screen, installers use them for safety installation cables where particular protection against fire and damage to human life and equipment is necessary. Furthermore, these installation cables are not admissible for power installation purposes and direct burial. Consequently, they deliver consistent performance in safety-critical environments.
Cable construction
This cable strictly adheres to VDE 0815 standards. It features a bare copper conductor with a diameter of 0.8 mm. The insulation uses a halogen-free polymer compound type HI according to VDE 0207 part 23, with a thickness of 0.3mm. Each pair is twisted, and 4 pairs are laid up to a bundle, identified by spirally imprinted numbers. The cable core wrapping consists of bundles laid up in layers with polyester tapes. A braid of tinned Cu wires forms the screen. Finally, a halogen-free, flame-retardant polymer compound type HM 2 according to VDE 0207 part 24 sheath protects the entire assembly. The color is grey or black. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C of max. 73.2 MΩ/km. The mutual capacitance at 800 Hz is max. 120 nF/km. The capacitance unbalance at 800 Hz is max. 200 pF/100m. The test voltage is 50 Hz, 1 min for 3000V (wire-wire) and 5000V (wire-screen). The operating voltage peak value is 250V. The temperature range is mobile -5 °C to +50 °C and fixed -30 °C to +70 °C. The minimum bending radius is 7.5 x cable diameter. Furthermore, it passes the flame test according to DIN VDE 0472 and IEC 60332-1.
Core Identification & Construction
The pairs are identified by colors that repeat in each bundle: Pair 1 (a: blue, b: red), Pair 2 (a: grey, b: yellow), Pair 3 (a: green, b: brown), Pair 4 (a: white, b: black). Cables with 2 pairs are laid up as a star quad. Each bundle is identified by an open support spiral with imprinted numbers. The cable uses a drum size (D) and overall width (L) with specific D/L ratios (e.g., 650/340/5.30).
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Mechanical data JE-HCH …x2x0.8 BD
| No. of pairs Conductor | Thickness of the insulation | Overall diameter approx. | Lengths | Type of drums D*/L* | Copper weight approx. | Cable weight approx. |
|---|---|---|---|---|---|---|
| mm | mm | mm | m | mm | kg/km | kg/km |
| 2x2x0.8 | 1,4 | 7,4 | 1000 | 650/340/5.30 | 40 | 87 |
| 4x2x0.8 | 1,4 | 8,8 | 1000 | 710/400/5.60 | 75 | 141 |
| 8x2x0.8 | 1,4 | 11,9 | 1000 | 1000/500/6.30 | 123 | 218 |
| 12x2x0.8 | 1,4 | 13,7 | 1000 | 1000/500/6.30 | 173 | 291 |
| 40x2x0.8 | 1,5 | 22,1 | 1000 | 1400/750/8.80 | 481 | 751 |
(Note: D = flange diameter, d = core diameter, L = overall width).*
Factory Overview

Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the JE-HCH cable?
A:- It is used for the transmission of signals and measuring data in control circuits, specifically in safety installations requiring protection against fire damage.
Q:- What are the key safety features of this cable?
A:- It uses halogen-free polymer compounds for low smoke and zero halogen emissions, features a tinned copper braid screen for signal protection, and passes the DIN VDE 0472 flame test.
Q:- What standards does the cable construction follow?
A:- The construction adheres to VDE 0815 standards, with insulation and sheath compounds following VDE 0207 parts 23 and 24.
Q:- What type of conductor and insulation does it use?
A:- It uses a bare copper conductor with a halogen-free polymer compound type HI insulation.
Q:- What is the temperature range for this cable?
A:- The fixed temperature range is -30°C to +70°C, and the mobile temperature range is -5°C to +50°C.
Q:- What is the mutual capacitance of this cable?
A:- The mutual capacitance at 800 Hz is max. 120 nF/km.
Q:- What is the test voltage for this cable?
A:- The test voltage is 50 Hz, 1 min for 3000V (wire-wire) and 5000V (wire-screen).
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 7.5 times the cable diameter.
Q:- How are the pairs identified within each bundle?
A:- The pairs use color coding (Pair 1: Blue/Red, Pair 2: Grey/Yellow, Pair 3: Green/Brown, Pair 4: White/Black) and each bundle has an open support spiral with imprinted numbers.
Q:- Can this cable be used for power installation or direct burial?
A:- No, these installation cables are not admissible for power installation purposes and direct burial.