LSZH/OSCR/LSZH/SWA/LSZH Armoured Screened Halogen-Free Control Cable – ESI 09-6

The LSZH/OSCR/LSZH/SWA/LSZH cable delivers dependable communication and control connections for industrial and infrastructure applications. Constructed with solid tinned copper conductors, halogen-free polymer insulation, twisted pairs, an aluminum tape screen, steel wire armour, and a halogen-free outer sheath, it offers exceptional fire safety and high mechanical resistance. Because it meets ESI 09-6 standards and is RoHS compliant, it provides a safe and reliable solution for electrical instrument circuits in fire-risk environments.

Application
LSZH/OSCR/LSZH/SWA/LSZH cables provide reliable communication and control connections for industrial and infrastructure applications. Because they feature low smoke zero halogen (LSZH) materials, a robust screen, and steel wire armour, installers use them in electrical instrument circuits to provide communication services. Furthermore, they are explicitly designed for areas where a fire could create dense smoke and toxic fumes, ensuring safety for personnel and equipment.

Cable construction
This cable adheres to ESI 09-6, issue 6 standards. It features a solid tinned copper conductor with a diameter of 0.8 mm. The insulation uses a halogen-free polymer compound. Each pair is twisted, with pairs stranded into layers with a minimum of 1 layer of plastic tape. A screen of aluminum tape (one side coated with polyester and 1 solid tinned copper wire with a diameter of 0.8mm) provides overall shielding. A halogen-free polymer compound forms the inner sheath (complying to BS 7655, part 6.1). A single layer of galvanized steel wires (according to BS 1442) provides the armour. The outer sheath uses a halogen-free polymer compound (complying to BS 7655, part 6.1). Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C of max. 36.8 MΩ/km. The insulation resistance is min. 150 MΩ.km. The mutual capacitance at 800 Hz is max. 150 nF/km. The capacitance unbalance at 800 Hz is max. 270 pF/500m. The test voltage is 50 Hz, 1 min for 800V (wire-wire) and 1500V (wire-screen). The operating voltage is 150V. The temperature range is mobile -5 °C to +50 °C and fixed -30 °C to +70 °C. The minimum bending radius is 15 x cable diameter.

Cable core construction
The pairs are arranged in layers or units for larger counts. For instance, a 30-pair cable consists of one unit of 3×10-pair, one unit of 5×10-pair, and one unit of 2×20-pair. Units are identified by color tape: Unit 1 (Blue), Unit 2 (Orange), Unit 3 (Green), Unit 4 (Brown), and Unit 5 (Grey).

Color coding
Clear color coding ensures safe and accurate wiring. The 2-pair (quad cables) use white, red, blue, and orange. For multi-pair cables, the a-wire colors include white, black, red, etc., and the b-wire colors include blue, orange, green, etc.

Type codes
LSZH = halogen-free polymer compound, SWA = armour, OSCR = screen of aluminum tape.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Mechanical data LSZH/OSCR/LSZH/SWA/LSZH …x2x0.8

Number of pairs Diameter of armour wire External diameter approx. Copper weight Cable weight approx.
mm mm kg/km kg/km
1x2x0.8 0,90 8,1 14 175
2x2x0.8 0,90 10,3 24 259
5x2x0.8 0,90 13,3 52 365
10x2x0.8 1,25 17,0 98 620
15x2x0.8 1,25 18,6 145 745
20x2x0.8 1,25 20,8 192 899
30x2x0.8 1,25 24,2 285 1139
40x2x0.8 1,60 27,3 380 1559
50x2x0.8 1,60 31,6 475 1870

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the LSZH/OSCR/LSZH/SWA/LSZH cable?
A:- It is used in electrical instrument circuits to provide communication services, particularly in areas where a fire could create dense smoke and toxic fumes.

Q:- What are the key safety and mechanical features of this cable?
A:- It features halogen-free polymer compounds for low smoke and zero halogen emissions, an aluminum tape screen (OSCR) for signal protection, and galvanized steel wire armour (SWA) for high mechanical resistance.

Q:- What standards does the cable construction follow?
A:- The construction adheres to ESI 09-6, issue 6 standards, and the sheath compounds comply with BS 7655, part 6.1.

Q:- What type of conductor and insulation does it use?
A:- It uses a solid tinned copper conductor with a halogen-free polymer compound insulation.

Q:- What is the temperature range for this cable?
A:- The fixed temperature range is -30°C to +70°C, and the mobile temperature range is -5°C to +50°C.

Q:- What is the mutual capacitance of this cable?
A:- The mutual capacitance at 800 Hz is max. 150 nF/km.

Q:- What is the test voltage for this cable?
A:- The test voltage is 50 Hz, 1 min for 800V (wire-wire) and 1500V (wire-screen).

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter.

Q:- What is the conductor resistance at 20°C?
A:- The conductor resistance at 20°C is max. 36.8 MΩ/km.

Q:- What do the type codes LSZH, SWA, and OSCR stand for?
A:- LSZH indicates a halogen-free polymer compound, SWA indicates armour, and OSCR indicates a screen of aluminum tape.